Phase 3 PR 23 — Modbus IHostConnectivityProbe. ModbusDriver now implements 6 of 8 capability interfaces (adds IHostConnectivityProbe alongside IDriver + ITagDiscovery + IReadable + IWritable + ISubscribable from the earlier PRs). Background probe loop kicks off in InitializeAsync when ModbusProbeOptions.Enabled is true, sends a cheap FC03 read-1-register at ProbeAddress (default 0) every Interval (default 5s) with a per-tick Timeout (default 2s), and tracks the single Modbus endpoint's state in the HostState machine. Initial state = Unknown; first successful probe transitions to Running; any transport/timeout failure transitions to Stopped; recovery transitions back to Running. OnHostStatusChanged fires exactly on transitions (not on repeat successes — prevents event-spam on a healthy connection). HostName format is 'host:port' so the Admin UI can display the endpoint uniformly with Galaxy platforms/engines in the fleet status dashboard. GetHostStatuses returns a single-item list with the current state + last-change timestamp (Modbus driver talks to exactly one endpoint per instance — operators spin up multiple driver instances for multi-PLC deployments). ShutdownAsync cancels the probe CTS before tearing down the transport so the loop can't log a spurious Stopped after intentional shutdown (OperationCanceledException caught separately from the 'real' transport errors). ModbusDriverOptions extended with ModbusProbeOptions sub-record (Enabled default true, Interval 5s, Timeout 2s, ProbeAddress ushort for PLCs that have register-0 policies; most PLCs tolerate an FC03 at 0 but some industrial gateways lock it). Tests (7 new ModbusProbeTests): Initial_state_is_Unknown_before_first_probe_tick (probe disabled, state stays Unknown, HostName formatted); First_successful_probe_transitions_to_Running (enabled, waits for probe count + event queue, asserts Unknown → Running with correct OldState/NewState); Transport_failure_transitions_to_Stopped (flip fake.Reachable = false mid-run, wait for state diff); Recovery_transitions_Stopped_back_to_Running (up → down → up, asserts ≥ 3 transitions); Repeated_successful_probes_do_not_generate_duplicate_Running_events (several hundred ms of stable probes, count stays at 1); Disabled_probe_stays_Unknown_and_fires_no_events (safety guard when operator wants to disable probing); Shutdown_stops_the_probe_loop (probe count captured at shutdown, delay 400ms, assert ≤ 1 extra to tolerate the narrow race where an in-flight tick completes after shutdown — the contract is 'no new ticks scheduled' not 'instantaneous freeze'). FlappyTransport fake exposes a volatile Reachable flag so tests can toggle the PLC availability mid-run, + ProbeCount counter so tests can assert the loop actually issued requests. WaitForStateAsync helper polls GetHostStatuses up to a deadline; tolerates scheduler jitter on slow CI runners. Full solution: 0 errors, 202 unit + integration tests pass (22 Modbus + 180 pre-existing).
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -1,3 +1,5 @@
|
||||
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
|
||||
/// <summary>
|
||||
@@ -14,6 +16,24 @@ public sealed class ModbusDriverOptions
|
||||
|
||||
/// <summary>Pre-declared tag map. Modbus has no discovery protocol — the driver returns exactly these.</summary>
|
||||
public IReadOnlyList<ModbusTagDefinition> Tags { get; init; } = [];
|
||||
|
||||
/// <summary>
|
||||
/// Background connectivity-probe settings. When <see cref="ModbusProbeOptions.Enabled"/>
|
||||
/// is true the driver runs a tick loop that issues a cheap FC03 at register 0 every
|
||||
/// <see cref="ModbusProbeOptions.Interval"/> and raises <c>OnHostStatusChanged</c> on
|
||||
/// Running ↔ Stopped transitions. The Admin UI / OPC UA clients see the state through
|
||||
/// <see cref="IHostConnectivityProbe"/>.
|
||||
/// </summary>
|
||||
public ModbusProbeOptions Probe { get; init; } = new();
|
||||
}
|
||||
|
||||
public sealed class ModbusProbeOptions
|
||||
{
|
||||
public bool Enabled { get; init; } = true;
|
||||
public TimeSpan Interval { get; init; } = TimeSpan.FromSeconds(5);
|
||||
public TimeSpan Timeout { get; init; } = TimeSpan.FromSeconds(2);
|
||||
/// <summary>Register to read for the probe. Zero is usually safe; override for PLCs that lock register 0.</summary>
|
||||
public ushort ProbeAddress { get; init; } = 0;
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
|
||||