merge: Modbus RTU-over-TCP transport (#495)
Wave 1 of the driver-expansion program. The branch was complete and live-gated but had never been merged; it sat 15 commits ahead and 50 behind master. Purely additive behind the existing IModbusTransport seam — the application protocol (function codes, codecs, planner, coalescing, write path, probe, materialisation, HistoryRead) is identical across TCP and RTU; only the wire framing differs ([addr][PDU][CRC-16], no MBAP, no TxId). Zero changes to codecs/planner/health. Selected by a new Transport config field (ModbusTransportMode: Tcp | RtuOverTcp), routed through ModbusTransportFactory (throws on unknown mode), with the string-enum guard on options/DTO/factory and a Transport selector on the AdminUI Modbus form. ModbusSocketLifecycle was extracted from ModbusTcpTransport (behaviour-preserving) and is composed by both transports. Descoped by design: direct-serial (System.IO.Ports) and Modbus ASCII — RTU buses are reached exclusively via a serial->Ethernet gateway. No per-tag config changes; the existing per-tag UnitId already makes a multi-drop bus work. Re-validated against current master at merge time (the branch's own gate predates 50 commits of master): no overlapping files, clean merge, solution builds 0 errors, and Modbus 344/344, Modbus.Addressing 161/161, AdminUI 740/740, Runtime 507/507, Configuration 131/131 all pass. Confirmed the Transport selector is still reachable through master's current authoring path (DriverConfigModal -> ModbusDriverForm), so the branch's live /run gate result still applies.
This commit is contained in:
@@ -130,6 +130,14 @@ public sealed class ModbusDriverOptions
|
||||
/// </summary>
|
||||
public MelsecFamily MelsecSubFamily { get; init; } = MelsecFamily.Q_L_iQR;
|
||||
|
||||
/// <summary>
|
||||
/// Wire transport selector. <see cref="ModbusTransportMode.Tcp"/> (default) is the
|
||||
/// historical Modbus TCP/MBAP framing. <see cref="ModbusTransportMode.RtuOverTcp"/>
|
||||
/// frames Modbus RTU PDUs (CRC16, no MBAP header) over the same TCP socket — for
|
||||
/// serial-to-Ethernet gateways that bridge RS-485 without re-encapsulating to MBAP.
|
||||
/// </summary>
|
||||
public ModbusTransportMode Transport { get; init; } = ModbusTransportMode.Tcp;
|
||||
|
||||
/// <summary>
|
||||
/// When <c>true</c>, the driver suppresses redundant writes: if the most recent
|
||||
/// successful write to a tag carried value V and a new write of V arrives, the second
|
||||
|
||||
@@ -0,0 +1,17 @@
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
|
||||
/// <summary>
|
||||
/// Wire transport for a Modbus driver instance. <see cref="Tcp"/> = Modbus/TCP (MBAP + TxId);
|
||||
/// <see cref="RtuOverTcp"/> = RTU framing (address + CRC-16, no MBAP) tunnelled over a socket to
|
||||
/// a serial→Ethernet gateway. Default <see cref="Tcp"/> — existing configs omit the field.
|
||||
/// A direct-serial <c>Rtu</c> member is intentionally NOT reserved here (descoped 2026-07-15);
|
||||
/// do not number-squat it.
|
||||
/// </summary>
|
||||
public enum ModbusTransportMode
|
||||
{
|
||||
/// <summary>Modbus/TCP — 7-byte MBAP header + transaction id (the historical default).</summary>
|
||||
Tcp,
|
||||
|
||||
/// <summary>RTU framing (<c>[addr][PDU][CRC-16]</c>) tunnelled over a socket to a serial→Ethernet gateway.</summary>
|
||||
RtuOverTcp,
|
||||
}
|
||||
@@ -0,0 +1,48 @@
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
|
||||
/// <summary>
|
||||
/// CRC-16/MODBUS helper: reflected polynomial <c>0xA001</c>, initial value <c>0xFFFF</c>.
|
||||
/// On the wire the CRC is appended low byte first, high byte second — <see cref="Append"/>
|
||||
/// does that; <see cref="Compute"/> just returns the 16-bit value. Byte-stream-agnostic:
|
||||
/// no socket or framing knowledge lives here.
|
||||
/// </summary>
|
||||
public static class ModbusCrc
|
||||
{
|
||||
/// <summary>Computes the CRC-16/MODBUS checksum over <paramref name="data"/>.</summary>
|
||||
/// <param name="data">The bytes to checksum (e.g. the RTU frame minus the trailing CRC).</param>
|
||||
/// <returns>The 16-bit CRC value.</returns>
|
||||
public static ushort Compute(ReadOnlySpan<byte> data)
|
||||
{
|
||||
ushort crc = 0xFFFF;
|
||||
foreach (var b in data)
|
||||
{
|
||||
crc ^= b;
|
||||
for (var i = 0; i < 8; i++)
|
||||
{
|
||||
var carry = (crc & 0x0001) != 0;
|
||||
crc >>= 1;
|
||||
if (carry)
|
||||
{
|
||||
crc ^= 0xA001;
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
return crc;
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Returns <paramref name="body"/> with its CRC-16/MODBUS appended, low byte first.
|
||||
/// </summary>
|
||||
/// <param name="body">The frame body to checksum.</param>
|
||||
/// <returns>A new array: <paramref name="body"/> followed by <c>[crc & 0xFF, crc >> 8]</c>.</returns>
|
||||
public static byte[] Append(ReadOnlySpan<byte> body)
|
||||
{
|
||||
var crc = Compute(body);
|
||||
var result = new byte[body.Length + 2];
|
||||
body.CopyTo(result);
|
||||
result[^2] = (byte)(crc & 0xFF);
|
||||
result[^1] = (byte)(crc >> 8);
|
||||
return result;
|
||||
}
|
||||
}
|
||||
@@ -94,7 +94,8 @@ public sealed class ModbusDriver
|
||||
/// <summary>Initializes a new Modbus TCP driver with the specified options and transport factory.</summary>
|
||||
/// <param name="options">Driver configuration options.</param>
|
||||
/// <param name="driverInstanceId">Unique identifier for this driver instance.</param>
|
||||
/// <param name="transportFactory">Factory to create the Modbus transport; defaults to ModbusTcpTransport.</param>
|
||||
/// <param name="transportFactory">Factory to create the Modbus transport; defaults to
|
||||
/// <see cref="ModbusTransportFactory.Create"/>, which honours <see cref="ModbusDriverOptions.Transport"/>.</param>
|
||||
/// <param name="logger">Logger instance; defaults to null logger if not provided.</param>
|
||||
public ModbusDriver(ModbusDriverOptions options, string driverInstanceId,
|
||||
Func<ModbusDriverOptions, IModbusTransport>? transportFactory = null,
|
||||
@@ -107,11 +108,7 @@ public sealed class ModbusDriver
|
||||
_resolver = new EquipmentTagRefResolver<ModbusTagDefinition>(
|
||||
r => _tagsByRawPath.TryGetValue(r, out var t) ? t : null);
|
||||
_transportFactory = transportFactory
|
||||
?? (o => new ModbusTcpTransport(
|
||||
o.Host, o.Port, o.Timeout, o.AutoReconnect,
|
||||
keepAlive: o.KeepAlive,
|
||||
idleDisconnect: o.IdleDisconnectTimeout,
|
||||
reconnect: o.Reconnect));
|
||||
?? (o => ModbusTransportFactory.Create(o));
|
||||
_poll = new PollGroupEngine(
|
||||
reader: ReadAsync,
|
||||
onChange: (handle, tagRef, snapshot) =>
|
||||
|
||||
@@ -74,6 +74,8 @@ public static class ModbusDriverFactoryExtensions
|
||||
: ParseEnum<ModbusFamily>(dto.Family, "<driver-level>", driverInstanceId, "Family"),
|
||||
MelsecSubFamily = dto.MelsecSubFamily is null ? MelsecFamily.Q_L_iQR
|
||||
: ParseEnum<MelsecFamily>(dto.MelsecSubFamily, "<driver-level>", driverInstanceId, "MelsecSubFamily"),
|
||||
Transport = dto.Transport is null ? ModbusTransportMode.Tcp
|
||||
: ParseEnum<ModbusTransportMode>(dto.Transport, "<driver-level>", driverInstanceId, "Transport"),
|
||||
AutoProhibitReprobeInterval = dto.AutoProhibitReprobeMs is { } reprobeMs ? TimeSpan.FromMilliseconds(reprobeMs) : null,
|
||||
AutoReconnect = dto.AutoReconnect ?? true,
|
||||
// v3: the deploy artifact (Wave C) populates rawTags with the cluster's authored raw Modbus
|
||||
@@ -159,6 +161,8 @@ public static class ModbusDriverFactoryExtensions
|
||||
public string? Family { get; init; }
|
||||
/// <summary>Gets or sets the Melsec subfamily.</summary>
|
||||
public string? MelsecSubFamily { get; init; }
|
||||
/// <summary>Gets or sets the wire transport mode (Tcp / RtuOverTcp). Null defaults to Tcp.</summary>
|
||||
public string? Transport { get; init; }
|
||||
/// <summary>Gets or sets the automatic prohibition reprobei interval in milliseconds.</summary>
|
||||
public int? AutoProhibitReprobeMs { get; init; }
|
||||
/// <summary>Gets or sets a value indicating whether automatic reconnection is enabled.</summary>
|
||||
|
||||
@@ -29,15 +29,19 @@ public sealed class ModbusDriverProbe : IDriverProbe
|
||||
/// <inheritdoc />
|
||||
public string DriverType => "Modbus";
|
||||
|
||||
/// <summary>The parsed probe target — host/port/unitId + the effective connection timeout, all read
|
||||
/// from the SAME factory DTO shape (<c>ModbusDriverConfigDto</c>) the driver factory parses, so
|
||||
/// <c>timeoutMs</c> binds identically to the factory (R2-11, 05/CONV-2; the OpcUaClient parity rule).</summary>
|
||||
internal readonly record struct ProbeTarget(string Host, int Port, byte UnitId, TimeSpan Timeout);
|
||||
/// <summary>The parsed probe target — host/port/unitId + the effective connection timeout + the wire
|
||||
/// transport mode, all read from the SAME factory DTO shape (<c>ModbusDriverConfigDto</c>) the driver
|
||||
/// factory parses, so <c>timeoutMs</c> binds identically to the factory (R2-11, 05/CONV-2; the
|
||||
/// OpcUaClient parity rule) and an <c>RtuOverTcp</c>-authored config probes over RTU framing —
|
||||
/// matching how the driver will actually run.</summary>
|
||||
internal readonly record struct ProbeTarget(string Host, int Port, byte UnitId, TimeSpan Timeout, ModbusTransportMode Transport);
|
||||
|
||||
/// <summary>Parse the driver config JSON into a <see cref="ProbeTarget"/> using the factory DTO shape.
|
||||
/// Returns a null target + an error message when the JSON is invalid or has no host/port. The effective
|
||||
/// timeout mirrors the factory (<c>TimeSpan.FromMilliseconds(dto.TimeoutMs ?? …)</c>); when the config
|
||||
/// omits <c>timeoutMs</c> the caller's <paramref name="fallbackTimeout"/> is used.</summary>
|
||||
/// omits <c>timeoutMs</c> the caller's <paramref name="fallbackTimeout"/> is used. <c>Transport</c>
|
||||
/// mirrors the factory's null-defaults-to-Tcp convention (<see cref="ModbusDriverFactoryExtensions"/>);
|
||||
/// an unrecognized value is reported as a probe-target error rather than silently falling back.</summary>
|
||||
/// <param name="configJson">The driver config JSON (factory DTO shape).</param>
|
||||
/// <param name="fallbackTimeout">The timeout used when the config omits <c>timeoutMs</c>.</param>
|
||||
/// <returns>The parsed target, or a null target with an error string.</returns>
|
||||
@@ -52,8 +56,15 @@ public sealed class ModbusDriverProbe : IDriverProbe
|
||||
if (string.IsNullOrWhiteSpace(dto.Host) || port <= 0)
|
||||
return (null, "Config has no host/port to probe.");
|
||||
|
||||
var transportMode = ModbusTransportMode.Tcp;
|
||||
if (dto.Transport is not null && !Enum.TryParse(dto.Transport, ignoreCase: true, out transportMode))
|
||||
{
|
||||
return (null, $"Config has unknown Transport '{dto.Transport}'. " +
|
||||
$"Expected one of {string.Join(", ", Enum.GetNames<ModbusTransportMode>())}");
|
||||
}
|
||||
|
||||
var timeout = dto.TimeoutMs is { } ms && ms > 0 ? TimeSpan.FromMilliseconds(ms) : fallbackTimeout;
|
||||
return (new ProbeTarget(dto.Host!, port, dto.UnitId ?? 1, timeout), null);
|
||||
return (new ProbeTarget(dto.Host!, port, dto.UnitId ?? 1, timeout, transportMode), null);
|
||||
}
|
||||
|
||||
/// <inheritdoc />
|
||||
@@ -72,9 +83,17 @@ public sealed class ModbusDriverProbe : IDriverProbe
|
||||
using var cts = CancellationTokenSource.CreateLinkedTokenSource(ct);
|
||||
cts.CancelAfter(timeout);
|
||||
|
||||
// Phase 1 — TCP connect (using ModbusTcpTransport which handles IPv4 preference).
|
||||
// Phase 1 — TCP connect, over whichever transport the config's Transport mode selects
|
||||
// (ModbusTransportFactory is the single mapping point — same switch the live driver uses).
|
||||
// autoReconnect=false: this is a one-shot probe, no retry loops.
|
||||
var transport = new ModbusTcpTransport(host, port, timeout, autoReconnect: false);
|
||||
var transport = ModbusTransportFactory.Create(new ModbusDriverOptions
|
||||
{
|
||||
Host = host,
|
||||
Port = port,
|
||||
Timeout = timeout,
|
||||
Transport = t.Transport,
|
||||
AutoReconnect = false,
|
||||
});
|
||||
await using (transport.ConfigureAwait(false))
|
||||
{
|
||||
try
|
||||
|
||||
@@ -0,0 +1,187 @@
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
|
||||
/// <summary>
|
||||
/// Modbus RTU framing: builds a request ADU (<c>[unitId] + PDU + CRC</c>) and deframes a
|
||||
/// response back to its bare PDU. Byte-stream-agnostic — it operates on a <see cref="Stream"/>
|
||||
/// and knows nothing about sockets or serial ports, so a future serial transport can reuse it.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// <para>
|
||||
/// The single genuinely-new correctness risk of the RTU path: an RTU frame carries <b>no
|
||||
/// length field</b> (unlike TCP's MBAP header), so the response size must be derived from
|
||||
/// the function code. After reading <c>addr(1)</c> + <c>fc(1)</c>, the remaining byte count
|
||||
/// is one of three shapes:
|
||||
/// </para>
|
||||
/// <list type="table">
|
||||
/// <listheader><term>Shape</term><description>Trailing bytes after <c>addr,fc</c></description></listheader>
|
||||
/// <item>
|
||||
/// <term>Exception (<c>fc & 0x80</c>)</term>
|
||||
/// <description><c>excCode(1)</c> + <c>CRC(2)</c></description>
|
||||
/// </item>
|
||||
/// <item>
|
||||
/// <term>Read (FC 01/02/03/04)</term>
|
||||
/// <description><c>byteCount(1)</c> then <c>byteCount</c> data bytes + <c>CRC(2)</c></description>
|
||||
/// </item>
|
||||
/// <item>
|
||||
/// <term>Write echo (FC 05/06/15/16)</term>
|
||||
/// <description>fixed <c>4</c> bytes + <c>CRC(2)</c></description>
|
||||
/// </item>
|
||||
/// </list>
|
||||
/// <para>
|
||||
/// The trailing CRC is validated over <c>[addr, ...pdu]</c> (everything except the two CRC
|
||||
/// bytes) <b>before</b> the frame is interpreted — so a corrupt exception frame surfaces as a
|
||||
/// desync, never as a bogus <see cref="ModbusException"/>. A CRC mismatch or a short read
|
||||
/// (truncation / stream closed mid-frame) throws <see cref="ModbusTransportDesyncException"/>;
|
||||
/// a CRC-valid exception PDU throws <see cref="ModbusException"/> carrying the original
|
||||
/// function code (<c>fc & 0x7F</c>) and exception code.
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// Once the CRC passes, the response's address byte is validated against the addressed unit.
|
||||
/// On an RS-485 multi-drop bus a CRC-valid reply from the <b>wrong</b> slave would otherwise be
|
||||
/// silently accepted as the addressed unit's data; such a frame is a unit-mismatch
|
||||
/// <see cref="ModbusTransportDesyncException"/>. This ordering is deliberate — a corrupt frame
|
||||
/// stays a CRC/desync failure, and only a coherent-but-mis-addressed frame becomes a
|
||||
/// unit-mismatch desync.
|
||||
/// </para>
|
||||
/// </remarks>
|
||||
public static class ModbusRtuFraming
|
||||
{
|
||||
/// <summary>
|
||||
/// Builds an RTU request ADU: the unit id, the PDU, and the trailing CRC-16/MODBUS
|
||||
/// (appended low byte first).
|
||||
/// </summary>
|
||||
/// <param name="unitId">The RTU slave/unit address.</param>
|
||||
/// <param name="pdu">The bare PDU (function code + data).</param>
|
||||
/// <returns>A new array: <c>[unitId, ...pdu, crcLo, crcHi]</c>.</returns>
|
||||
public static byte[] BuildAdu(byte unitId, ReadOnlySpan<byte> pdu)
|
||||
{
|
||||
var frame = new byte[1 + pdu.Length];
|
||||
frame[0] = unitId;
|
||||
pdu.CopyTo(frame.AsSpan(1));
|
||||
return ModbusCrc.Append(frame);
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Reads a single RTU response frame from <paramref name="stream"/> and returns its bare PDU
|
||||
/// (<c>[fc, ...data]</c>), with the leading unit-id and trailing CRC stripped.
|
||||
/// </summary>
|
||||
/// <param name="stream">The byte stream to read the response from.</param>
|
||||
/// <param name="expectedUnit">
|
||||
/// The unit id the request was addressed to. The response's address byte is validated against
|
||||
/// it after the CRC passes; a mismatch is a unit-mismatch desync.
|
||||
/// </param>
|
||||
/// <param name="ct">A token to cancel the read.</param>
|
||||
/// <returns>The bare response PDU (function code followed by its data).</returns>
|
||||
/// <exception cref="ModbusTransportDesyncException">
|
||||
/// The frame was truncated (stream closed mid-frame), its trailing CRC did not validate, or its
|
||||
/// address byte did not match <paramref name="expectedUnit"/>.
|
||||
/// </exception>
|
||||
/// <exception cref="ModbusException">
|
||||
/// The frame was a CRC-valid Modbus exception PDU (high bit set on the function code).
|
||||
/// </exception>
|
||||
public static async Task<byte[]> ReadResponsePduAsync(
|
||||
Stream stream, byte expectedUnit, CancellationToken ct)
|
||||
{
|
||||
// Header: addr(1) + fc(1). The function code selects how many more bytes to read.
|
||||
var header = new byte[2];
|
||||
await ReadExactlyAsync(stream, header, ct).ConfigureAwait(false);
|
||||
var fc = header[1];
|
||||
|
||||
int trailing; // bytes after addr+fc, up to and including the 2 CRC bytes.
|
||||
if ((fc & 0x80) != 0)
|
||||
{
|
||||
// Exception frame: excCode(1) + CRC(2).
|
||||
trailing = 1 + 2;
|
||||
}
|
||||
else if (fc is 0x01 or 0x02 or 0x03 or 0x04)
|
||||
{
|
||||
// Read response: byteCount(1) then byteCount data bytes + CRC(2).
|
||||
var bc = new byte[1];
|
||||
await ReadExactlyAsync(stream, bc, ct).ConfigureAwait(false);
|
||||
var byteCount = bc[0];
|
||||
var rest = new byte[byteCount + 2];
|
||||
await ReadExactlyAsync(stream, rest, ct).ConfigureAwait(false);
|
||||
return ValidateAndStrip(expectedUnit, header, bc, rest);
|
||||
}
|
||||
else
|
||||
{
|
||||
// Fixed 4-byte echo: correct for the write FCs this driver emits (05/06/0F/10). A future
|
||||
// variable-length response FC outside 01-04 (e.g. FC23) would be mis-sized here and
|
||||
// surface as a desync — revisit the FC-shape table if the driver starts emitting one.
|
||||
trailing = 4 + 2;
|
||||
}
|
||||
|
||||
var tail = new byte[trailing];
|
||||
await ReadExactlyAsync(stream, tail, ct).ConfigureAwait(false);
|
||||
return ValidateAndStrip(expectedUnit, header, ReadOnlySpan<byte>.Empty, tail);
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Assembles the full frame from its pieces, validates the trailing CRC over everything
|
||||
/// except the CRC bytes, then validates the response address against
|
||||
/// <paramref name="expectedUnit"/> and strips <c>addr</c> + <c>CRC</c> to return the bare PDU.
|
||||
/// A CRC-valid exception PDU throws <see cref="ModbusException"/>.
|
||||
/// </summary>
|
||||
private static byte[] ValidateAndStrip(
|
||||
byte expectedUnit, ReadOnlySpan<byte> header, ReadOnlySpan<byte> middle, ReadOnlySpan<byte> tail)
|
||||
{
|
||||
// Reassemble the whole frame: header(addr,fc) + middle(optional byteCount) + tail.
|
||||
var frame = new byte[header.Length + middle.Length + tail.Length];
|
||||
header.CopyTo(frame);
|
||||
middle.CopyTo(frame.AsSpan(header.Length));
|
||||
tail.CopyTo(frame.AsSpan(header.Length + middle.Length));
|
||||
|
||||
// CRC covers everything except the trailing 2 CRC bytes.
|
||||
var body = frame.AsSpan(0, frame.Length - 2);
|
||||
var expected = ModbusCrc.Compute(body);
|
||||
var actual = (ushort)(frame[^2] | (frame[^1] << 8));
|
||||
if (actual != expected)
|
||||
throw new ModbusTransportDesyncException(
|
||||
ModbusTransportDesyncException.DesyncReason.CrcMismatch,
|
||||
$"Modbus RTU CRC mismatch: computed {expected:X4} got {actual:X4}");
|
||||
|
||||
// Unit-address validation runs only AFTER the CRC passes: a corrupt frame is a CRC/desync
|
||||
// failure, and only a coherent-but-mis-addressed frame (a CRC-valid reply from the wrong
|
||||
// RS-485 slave) is a unit-mismatch desync. Never silently accept another unit's data.
|
||||
var addr = frame[0];
|
||||
if (addr != expectedUnit)
|
||||
throw new ModbusTransportDesyncException(
|
||||
ModbusTransportDesyncException.DesyncReason.UnitMismatch,
|
||||
$"Modbus RTU unit mismatch: expected {expectedUnit} got {addr}");
|
||||
|
||||
// Bare PDU = frame minus leading addr and trailing CRC.
|
||||
var pdu = body[1..].ToArray();
|
||||
|
||||
// Exception PDU: high bit set on the function code. The CRC already validated, so this is a
|
||||
// coherent protocol-level error — surface the ORIGINAL function code (fc & 0x7F).
|
||||
if ((pdu[0] & 0x80) != 0)
|
||||
{
|
||||
var fc = (byte)(pdu[0] & 0x7F);
|
||||
var exCode = pdu[1];
|
||||
throw new ModbusException(fc, exCode, $"Modbus exception fc={fc} code={exCode}");
|
||||
}
|
||||
|
||||
return pdu;
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Fills <paramref name="buf"/> completely from <paramref name="stream"/>, throwing a
|
||||
/// truncation desync if the stream ends first. Mirrors
|
||||
/// <c>ModbusTcpTransport.ReadExactlyAsync</c>, but normalises the end-of-stream to a
|
||||
/// <see cref="ModbusTransportDesyncException"/> so a length-less RTU frame that arrives
|
||||
/// short is classified as a desync rather than a bare <see cref="EndOfStreamException"/>.
|
||||
/// </summary>
|
||||
private static async Task ReadExactlyAsync(Stream stream, byte[] buf, CancellationToken ct)
|
||||
{
|
||||
var read = 0;
|
||||
while (read < buf.Length)
|
||||
{
|
||||
var n = await stream.ReadAsync(buf.AsMemory(read), ct).ConfigureAwait(false);
|
||||
if (n == 0)
|
||||
throw new ModbusTransportDesyncException(
|
||||
ModbusTransportDesyncException.DesyncReason.TruncatedFrame,
|
||||
$"Modbus RTU frame truncated: expected {buf.Length} bytes, got {read}");
|
||||
read += n;
|
||||
}
|
||||
}
|
||||
}
|
||||
@@ -0,0 +1,190 @@
|
||||
using System.Net.Sockets;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
|
||||
/// <summary>
|
||||
/// Concrete Modbus RTU-over-TCP transport. Composes <see cref="ModbusSocketLifecycle"/> for the
|
||||
/// connect / reconnect / keep-alive / idle machinery and <see cref="ModbusRtuFraming"/> for the
|
||||
/// wire layout — the same lifecycle <see cref="ModbusTcpTransport"/> uses, but with CRC framing
|
||||
/// instead of MBAP.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// <para>
|
||||
/// Delta from <see cref="ModbusTcpTransport"/>: an RTU ADU is <c>[unitId][PDU][CRC]</c> with
|
||||
/// <b>no MBAP header and no transaction id</b>. Because there is no TxId to correlate
|
||||
/// interleaved responses, at most one transaction may be on the bus at a time — the
|
||||
/// <see cref="_gate"/> single-flight is therefore <b>mandatory</b>, not merely a
|
||||
/// diagnostics convenience.
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// Survives mid-transaction socket drops the same way the TCP transport does: a socket-level
|
||||
/// failure (<see cref="IOException"/> / <see cref="SocketException"/> /
|
||||
/// <see cref="EndOfStreamException"/>, and the <see cref="ModbusTransportDesyncException"/>
|
||||
/// that derives from <see cref="IOException"/>) triggers a single reconnect-then-retry; a
|
||||
/// second failure bubbles up so the driver's health surface reflects the real state.
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// Every transaction runs under a per-op deadline (a linked
|
||||
/// <see cref="CancellationTokenSource.CancelAfter(TimeSpan)"/>, design §7 / R2-01) so a
|
||||
/// frozen gateway can never wedge a poll: the deadline firing is normalised to a
|
||||
/// <see cref="ModbusTransportDesyncException"/> and tears the socket down so the next attempt
|
||||
/// reconnects. A <b>caller</b> cancellation is distinguished from that timeout and propagates
|
||||
/// as a plain <see cref="OperationCanceledException"/> with no teardown.
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// The constructor is connection-free; all socket I/O happens in <see cref="ConnectAsync"/> /
|
||||
/// <see cref="SendAsync"/>. The <see cref="ForTest"/> seam injects a pre-connected
|
||||
/// <see cref="Stream"/> (an in-memory duplex fake) so the send/receive orchestration,
|
||||
/// single-flight, and deadline can be exercised with no socket — in that path
|
||||
/// <see cref="_life"/> is <see langword="null"/> and the idle / reconnect machinery is
|
||||
/// skipped (a raw injected stream cannot reconnect).
|
||||
/// </para>
|
||||
/// </remarks>
|
||||
public sealed class ModbusRtuOverTcpTransport : IModbusTransport
|
||||
{
|
||||
private readonly ModbusSocketLifecycle? _life;
|
||||
private readonly Stream? _testStream;
|
||||
private readonly TimeSpan _timeout;
|
||||
private readonly SemaphoreSlim _gate = new(1, 1);
|
||||
private bool _disposed;
|
||||
|
||||
/// <summary>Initializes a new instance of the <see cref="ModbusRtuOverTcpTransport"/> class.</summary>
|
||||
/// <param name="host">The host address or hostname of the Modbus gateway.</param>
|
||||
/// <param name="port">The TCP port of the Modbus gateway.</param>
|
||||
/// <param name="timeout">The timeout for socket operations and the per-op response deadline.</param>
|
||||
/// <param name="autoReconnect">Whether to automatically reconnect on socket failures.</param>
|
||||
/// <param name="keepAlive">Optional keep-alive configuration for the socket.</param>
|
||||
/// <param name="idleDisconnect">Optional duration after which an idle socket is disconnected.</param>
|
||||
/// <param name="reconnect">Optional reconnect backoff configuration.</param>
|
||||
public ModbusRtuOverTcpTransport(
|
||||
string host, int port, TimeSpan timeout, bool autoReconnect = true,
|
||||
ModbusKeepAliveOptions? keepAlive = null,
|
||||
TimeSpan? idleDisconnect = null,
|
||||
ModbusReconnectOptions? reconnect = null)
|
||||
{
|
||||
_timeout = timeout;
|
||||
_life = new ModbusSocketLifecycle(host, port, timeout, autoReconnect, keepAlive, idleDisconnect, reconnect);
|
||||
}
|
||||
|
||||
private ModbusRtuOverTcpTransport(Stream testStream, TimeSpan timeout)
|
||||
{
|
||||
_timeout = timeout;
|
||||
_testStream = testStream;
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Test seam: builds a transport over a pre-connected, in-memory duplex <paramref name="stream"/>,
|
||||
/// bypassing <see cref="ConnectAsync"/> and the idle / reconnect machinery so the send/receive
|
||||
/// orchestration, single-flight, and per-op deadline can be exercised with no real socket.
|
||||
/// </summary>
|
||||
/// <param name="stream">A pre-connected duplex stream standing in for the socket.</param>
|
||||
/// <param name="timeout">The per-op response deadline.</param>
|
||||
/// <returns>A transport driving <paramref name="stream"/> directly.</returns>
|
||||
internal static ModbusRtuOverTcpTransport ForTest(Stream stream, TimeSpan timeout) => new(stream, timeout);
|
||||
|
||||
/// <inheritdoc />
|
||||
public Task ConnectAsync(CancellationToken ct) =>
|
||||
// The ForTest seam is handed a pre-connected stream — nothing to dial.
|
||||
_life is null ? Task.CompletedTask : _life.ConnectAsync(ct);
|
||||
|
||||
/// <inheritdoc />
|
||||
public async Task<byte[]> SendAsync(byte unitId, byte[] pdu, CancellationToken ct)
|
||||
{
|
||||
if (_disposed) throw new ObjectDisposedException(nameof(ModbusRtuOverTcpTransport));
|
||||
if (CurrentStream is null) throw new InvalidOperationException("Transport not connected");
|
||||
|
||||
// Single-flight: RTU carries no transaction id, so at most one transaction may be on the bus
|
||||
// at a time — serialise every send/receive under the gate.
|
||||
await _gate.WaitAsync(ct).ConfigureAwait(false);
|
||||
try
|
||||
{
|
||||
// Proactive idle-disconnect (real socket only): if the socket has been quiet longer than
|
||||
// the configured threshold, tear it down + reconnect before this PDU lands. Defends
|
||||
// against silent NAT / firewall reaping.
|
||||
if (_life is not null && _life.ShouldReconnectForIdle())
|
||||
{
|
||||
await _life.TearDownAsync().ConfigureAwait(false);
|
||||
await _life.ConnectWithBackoffAsync(ct).ConfigureAwait(false);
|
||||
}
|
||||
|
||||
try
|
||||
{
|
||||
var result = await SendOnceAsync(unitId, pdu, ct).ConfigureAwait(false);
|
||||
_life?.MarkSuccess();
|
||||
return result;
|
||||
}
|
||||
catch (Exception ex) when (_life is not null && _life.AutoReconnect && ModbusSocketLifecycle.IsSocketLevelFailure(ex))
|
||||
{
|
||||
// Mid-transaction drop: tear down the dead socket, reconnect (with backoff if
|
||||
// configured), resend. Single retry — a second failure propagates so health/status
|
||||
// reflect reality. Never reached in the ForTest seam (a raw injected stream has no
|
||||
// lifecycle to reconnect).
|
||||
await _life.TearDownAsync().ConfigureAwait(false);
|
||||
await _life.ConnectWithBackoffAsync(ct).ConfigureAwait(false);
|
||||
var result = await SendOnceAsync(unitId, pdu, ct).ConfigureAwait(false);
|
||||
_life.MarkSuccess();
|
||||
return result;
|
||||
}
|
||||
}
|
||||
finally
|
||||
{
|
||||
_gate.Release();
|
||||
}
|
||||
}
|
||||
|
||||
/// <summary>The live stream: the lifecycle's <see cref="NetworkStream"/>, or the injected test stream.</summary>
|
||||
private Stream? CurrentStream => _life?.Stream ?? _testStream;
|
||||
|
||||
/// <summary>
|
||||
/// Executes exactly one RTU transaction on the current stream: build the ADU, write + flush,
|
||||
/// read back one deframed response PDU. See the class remarks for the desync / timeout /
|
||||
/// caller-cancel handling.
|
||||
/// </summary>
|
||||
private async Task<byte[]> SendOnceAsync(byte unitId, byte[] pdu, CancellationToken ct)
|
||||
{
|
||||
var stream = CurrentStream;
|
||||
if (stream is null) throw new InvalidOperationException("Transport not connected");
|
||||
|
||||
// RTU ADU: [unitId] + PDU + CRC — no MBAP header, no TxId.
|
||||
var adu = ModbusRtuFraming.BuildAdu(unitId, pdu);
|
||||
|
||||
using var cts = CancellationTokenSource.CreateLinkedTokenSource(ct);
|
||||
cts.CancelAfter(_timeout);
|
||||
try
|
||||
{
|
||||
await stream.WriteAsync(adu.AsMemory(), cts.Token).ConfigureAwait(false);
|
||||
await stream.FlushAsync(cts.Token).ConfigureAwait(false);
|
||||
|
||||
// Framing owns the length-less RTU deframe + CRC + unit-address validation. A CRC-valid
|
||||
// exception PDU throws ModbusException (socket still coherent — propagates, no teardown);
|
||||
// truncation / CRC / unit-mismatch throw ModbusTransportDesyncException.
|
||||
return await ModbusRtuFraming.ReadResponsePduAsync(stream, unitId, cts.Token).ConfigureAwait(false);
|
||||
}
|
||||
catch (ModbusTransportDesyncException)
|
||||
{
|
||||
// Framing violation: the stream is desynchronized — never reuse it.
|
||||
if (_life is not null) await _life.TearDownAsync().ConfigureAwait(false);
|
||||
throw;
|
||||
}
|
||||
catch (OperationCanceledException) when (!ct.IsCancellationRequested)
|
||||
{
|
||||
// Per-op timeout fired (NOT the caller). The response is unknown / may still land later
|
||||
// and corrupt the next read — tear the socket down and normalise as a desync so the
|
||||
// reconnect retry / status mapping engages.
|
||||
if (_life is not null) await _life.TearDownAsync().ConfigureAwait(false);
|
||||
throw new ModbusTransportDesyncException(
|
||||
ModbusTransportDesyncException.DesyncReason.Timeout,
|
||||
$"Modbus per-op response timeout after {_timeout.TotalMilliseconds:0}ms");
|
||||
}
|
||||
}
|
||||
|
||||
/// <summary>Asynchronously disposes the transport and underlying socket resources.</summary>
|
||||
/// <returns>A task that represents the asynchronous operation.</returns>
|
||||
public async ValueTask DisposeAsync()
|
||||
{
|
||||
if (_disposed) return;
|
||||
_disposed = true;
|
||||
if (_life is not null) await _life.DisposeAsync().ConfigureAwait(false);
|
||||
_gate.Dispose();
|
||||
}
|
||||
}
|
||||
@@ -0,0 +1,221 @@
|
||||
using System.Net.Sockets;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
|
||||
/// <summary>
|
||||
/// Owns the raw TCP socket lifecycle shared by every Modbus-over-TCP transport (MBAP and
|
||||
/// RTU-over-TCP alike): the IPv4-preference connect, OS-level keep-alive, geometric-backoff
|
||||
/// reconnect, idle-disconnect tracking, and teardown. It exposes the current
|
||||
/// <see cref="NetworkStream"/> so the composing transport can drive its own framing on top —
|
||||
/// the lifecycle knows nothing about MBAP / RTU wire layout.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// <para>
|
||||
/// Extracted verbatim from <see cref="ModbusTcpTransport"/> so the connect / reconnect /
|
||||
/// keep-alive / idle behaviour is written once and composed by both transports. The
|
||||
/// constructor is connection-free — all socket I/O happens in <see cref="ConnectAsync"/> /
|
||||
/// <see cref="ConnectWithBackoffAsync"/>.
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// Why keep-alive matters for DL205/DL260: the AutomationDirect H2-ECOM100 does NOT send
|
||||
/// TCP keepalives per <c>docs/v2/dl205.md</c> §behavioral-oddities, so any NAT/firewall
|
||||
/// between the gateway and PLC can silently close an idle socket after 2-5 minutes.
|
||||
/// Enabling OS-level <c>SO_KEEPALIVE</c> lets the driver's own side detect a stuck socket
|
||||
/// in reasonable time even when the application is mostly idle.
|
||||
/// </para>
|
||||
/// </remarks>
|
||||
public sealed class ModbusSocketLifecycle : IAsyncDisposable
|
||||
{
|
||||
private readonly string _host;
|
||||
private readonly int _port;
|
||||
private readonly TimeSpan _timeout;
|
||||
private readonly bool _autoReconnect;
|
||||
private readonly ModbusKeepAliveOptions _keepAlive;
|
||||
private readonly TimeSpan? _idleDisconnect;
|
||||
private readonly ModbusReconnectOptions _reconnect;
|
||||
private TcpClient? _client;
|
||||
private NetworkStream? _stream;
|
||||
private DateTime _lastSuccessUtc = DateTime.UtcNow;
|
||||
|
||||
/// <summary>Initializes a new instance of the <see cref="ModbusSocketLifecycle"/> class.</summary>
|
||||
/// <param name="host">The host address or hostname of the Modbus server.</param>
|
||||
/// <param name="port">The TCP port of the Modbus server.</param>
|
||||
/// <param name="timeout">The timeout for socket operations.</param>
|
||||
/// <param name="autoReconnect">Whether to automatically reconnect on socket failures.</param>
|
||||
/// <param name="keepAlive">Optional keep-alive configuration for the socket.</param>
|
||||
/// <param name="idleDisconnect">Optional duration after which an idle socket is disconnected.</param>
|
||||
/// <param name="reconnect">Optional reconnect backoff configuration.</param>
|
||||
public ModbusSocketLifecycle(
|
||||
string host, int port, TimeSpan timeout, bool autoReconnect = true,
|
||||
ModbusKeepAliveOptions? keepAlive = null,
|
||||
TimeSpan? idleDisconnect = null,
|
||||
ModbusReconnectOptions? reconnect = null)
|
||||
{
|
||||
_host = host;
|
||||
_port = port;
|
||||
_timeout = timeout;
|
||||
_autoReconnect = autoReconnect;
|
||||
_keepAlive = keepAlive ?? new ModbusKeepAliveOptions();
|
||||
_idleDisconnect = idleDisconnect;
|
||||
_reconnect = reconnect ?? new ModbusReconnectOptions();
|
||||
}
|
||||
|
||||
/// <summary>Gets the current live <see cref="NetworkStream"/>, or <see langword="null"/> when not connected.</summary>
|
||||
public NetworkStream? Stream => _stream;
|
||||
|
||||
/// <summary>Gets a value indicating whether auto-reconnect on socket failures is enabled.</summary>
|
||||
public bool AutoReconnect => _autoReconnect;
|
||||
|
||||
/// <summary>Establishes a connection to the Modbus server, preferring IPv4.</summary>
|
||||
/// <param name="ct">A cancellation token to observe for cancellation.</param>
|
||||
/// <returns>A task representing the asynchronous connection operation.</returns>
|
||||
public async Task ConnectAsync(CancellationToken ct)
|
||||
{
|
||||
// Resolve the host explicitly + prefer IPv4. .NET's TcpClient default-constructor is
|
||||
// dual-stack (IPv6 first, fallback to IPv4) — but most Modbus TCP devices (PLCs and
|
||||
// simulators like pymodbus) bind 0.0.0.0 only, so the IPv6 attempt times out and we
|
||||
// burn the entire ConnectAsync budget before even trying IPv4. Resolving first +
|
||||
// dialing the IPv4 address directly sidesteps that.
|
||||
var addresses = await System.Net.Dns.GetHostAddressesAsync(_host, ct).ConfigureAwait(false);
|
||||
var ipv4 = System.Linq.Enumerable.FirstOrDefault(addresses,
|
||||
a => a.AddressFamily == System.Net.Sockets.AddressFamily.InterNetwork);
|
||||
var target = ipv4 ?? (addresses.Length > 0 ? addresses[0] : System.Net.IPAddress.Loopback);
|
||||
|
||||
_client = new TcpClient(target.AddressFamily);
|
||||
EnableKeepAlive(_client, _keepAlive);
|
||||
|
||||
using var cts = CancellationTokenSource.CreateLinkedTokenSource(ct);
|
||||
cts.CancelAfter(_timeout);
|
||||
await _client.ConnectAsync(target, _port, cts.Token).ConfigureAwait(false);
|
||||
_stream = _client.GetStream();
|
||||
_lastSuccessUtc = DateTime.UtcNow;
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Connect attempt with the configured geometric backoff. The first attempt fires after
|
||||
/// <see cref="ModbusReconnectOptions.InitialDelay"/> (default zero — immediate); each
|
||||
/// subsequent attempt sleeps for the previous delay times <c>BackoffMultiplier</c>,
|
||||
/// capped at <c>MaxDelay</c>. Caller's cancellation token aborts the loop.
|
||||
/// </summary>
|
||||
/// <param name="ct">A cancellation token to observe for cancellation.</param>
|
||||
/// <returns>A task representing the asynchronous reconnect operation.</returns>
|
||||
public async Task ConnectWithBackoffAsync(CancellationToken ct)
|
||||
{
|
||||
var delay = _reconnect.InitialDelay;
|
||||
var attempt = 0;
|
||||
while (true)
|
||||
{
|
||||
if (delay > TimeSpan.Zero)
|
||||
await Task.Delay(delay, ct).ConfigureAwait(false);
|
||||
try
|
||||
{
|
||||
await ConnectAsync(ct).ConfigureAwait(false);
|
||||
return;
|
||||
}
|
||||
catch (Exception ex) when (IsSocketLevelFailure(ex) && _autoReconnect)
|
||||
{
|
||||
attempt++;
|
||||
// Geometric growth, capped. Use Math.Min on ticks so we don't overflow with
|
||||
// pathological multipliers / long deployments.
|
||||
var nextTicks = (long)(Math.Max(delay.Ticks, TimeSpan.FromMilliseconds(100).Ticks) * _reconnect.BackoffMultiplier);
|
||||
delay = TimeSpan.FromTicks(Math.Min(nextTicks, _reconnect.MaxDelay.Ticks));
|
||||
if (attempt >= 10)
|
||||
{
|
||||
// Bail after 10 attempts to surface persistent failure to the caller. With
|
||||
// the default backoff (1s base, 2.0x mult, 30s cap) this is roughly 4 minutes
|
||||
// of attempts; with InitialDelay=0 it's immediate up to the same cap.
|
||||
throw;
|
||||
}
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Reports whether the socket has been idle longer than the configured idle-disconnect
|
||||
/// threshold and should be proactively torn down + reconnected before the next transaction.
|
||||
/// Always <see langword="false"/> when no idle-disconnect timeout is configured.
|
||||
/// </summary>
|
||||
/// <returns><see langword="true"/> when the idle threshold has been exceeded.</returns>
|
||||
public bool ShouldReconnectForIdle() =>
|
||||
_idleDisconnect.HasValue && DateTime.UtcNow - _lastSuccessUtc > _idleDisconnect.Value;
|
||||
|
||||
/// <summary>Records that a transaction just succeeded, resetting the idle-disconnect clock.</summary>
|
||||
public void MarkSuccess() => _lastSuccessUtc = DateTime.UtcNow;
|
||||
|
||||
/// <summary>Tears down the current socket + stream, leaving the lifecycle ready to reconnect.</summary>
|
||||
/// <returns>A task representing the asynchronous teardown operation.</returns>
|
||||
public async Task TearDownAsync()
|
||||
{
|
||||
try { if (_stream is not null) await _stream.DisposeAsync().ConfigureAwait(false); }
|
||||
catch { /* best-effort */ }
|
||||
_stream = null;
|
||||
try { _client?.Dispose(); } catch { }
|
||||
_client = null;
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Enable SO_KEEPALIVE with aggressive probe timing. DL205/DL260 doesn't send keepalives
|
||||
/// itself; having the OS probe the socket every ~30s lets the driver notice a dead PLC
|
||||
/// or broken NAT path long before the default 2-hour Windows idle timeout fires.
|
||||
/// Non-fatal if the underlying OS rejects the option (some older Linux / container
|
||||
/// sandboxes don't expose the fine-grained timing levers — the driver still works,
|
||||
/// application-level probe still detects problems).
|
||||
/// </summary>
|
||||
private static void EnableKeepAlive(TcpClient client, ModbusKeepAliveOptions opts)
|
||||
{
|
||||
if (!opts.Enabled) return;
|
||||
try
|
||||
{
|
||||
client.Client.SetSocketOption(SocketOptionLevel.Socket, SocketOptionName.KeepAlive, true);
|
||||
// A TimeSpan < 1s previously truncated to 0 via the int cast,
|
||||
// which Windows / Linux interpret as "use the default" — silently defeating the
|
||||
// configured keep-alive timing. Round up to at least 1 second so a sub-second
|
||||
// configuration still produces a real keep-alive cadence. Negative values are
|
||||
// also clamped to 1 to avoid surfacing as OS errors.
|
||||
client.Client.SetSocketOption(SocketOptionLevel.Tcp, SocketOptionName.TcpKeepAliveTime,
|
||||
ClampToWholeSeconds(opts.Time));
|
||||
client.Client.SetSocketOption(SocketOptionLevel.Tcp, SocketOptionName.TcpKeepAliveInterval,
|
||||
ClampToWholeSeconds(opts.Interval));
|
||||
client.Client.SetSocketOption(SocketOptionLevel.Tcp, SocketOptionName.TcpKeepAliveRetryCount, opts.RetryCount);
|
||||
}
|
||||
catch { /* best-effort; older OSes may not expose the granular knobs */ }
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Cast a <see cref="TimeSpan"/> to a whole number of seconds with a
|
||||
/// minimum of 1 — protects callers from the int-cast truncation that turned 500 ms
|
||||
/// keep-alive timing into "use the default" on most OSes.
|
||||
/// </summary>
|
||||
/// <param name="ts">The timespan to clamp to whole seconds.</param>
|
||||
/// <returns>The clamped duration expressed as a whole number of seconds, never less than 1.</returns>
|
||||
internal static int ClampToWholeSeconds(TimeSpan ts)
|
||||
{
|
||||
var seconds = (int)Math.Ceiling(ts.TotalSeconds);
|
||||
return seconds < 1 ? 1 : seconds;
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Distinguish socket-layer failures (eligible for reconnect-and-retry) from
|
||||
/// protocol-layer failures (must propagate — retrying the same PDU won't help if the
|
||||
/// PLC just returned exception 02 Illegal Data Address).
|
||||
/// </summary>
|
||||
/// <param name="ex">The exception to classify.</param>
|
||||
/// <returns><see langword="true"/> when the exception is a socket-level failure.</returns>
|
||||
internal static bool IsSocketLevelFailure(Exception ex) =>
|
||||
ex is EndOfStreamException
|
||||
|| ex is IOException
|
||||
|| ex is SocketException
|
||||
|| ex is ObjectDisposedException;
|
||||
|
||||
/// <summary>Asynchronously disposes the underlying socket + stream resources.</summary>
|
||||
/// <returns>A task that represents the asynchronous operation.</returns>
|
||||
public async ValueTask DisposeAsync()
|
||||
{
|
||||
try
|
||||
{
|
||||
if (_stream is not null) await _stream.DisposeAsync().ConfigureAwait(false);
|
||||
}
|
||||
catch { /* best-effort */ }
|
||||
_client?.Dispose();
|
||||
}
|
||||
}
|
||||
@@ -3,13 +3,19 @@ using System.Net.Sockets;
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
|
||||
/// <summary>
|
||||
/// Concrete Modbus TCP transport. Wraps a single <see cref="TcpClient"/> and serializes
|
||||
/// requests so at most one transaction is in-flight at a time — Modbus servers typically
|
||||
/// support concurrent transactions, but the single-flight model keeps the wire trace
|
||||
/// Concrete Modbus TCP transport. Wraps a single socket (owned by <see cref="ModbusSocketLifecycle"/>)
|
||||
/// and serializes requests so at most one transaction is in-flight at a time — Modbus servers
|
||||
/// typically support concurrent transactions, but the single-flight model keeps the wire trace
|
||||
/// easy to diagnose and avoids interleaved-response correlation bugs.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// <para>
|
||||
/// Owns the MBAP framing (<see cref="SendOnceAsync"/>: 7-byte header + transaction-id
|
||||
/// pairing) and composes <see cref="ModbusSocketLifecycle"/> for the connect / reconnect /
|
||||
/// keep-alive / idle-disconnect machinery — the same lifecycle the RTU-over-TCP transport
|
||||
/// reuses with different framing.
|
||||
/// </para>
|
||||
/// <para>
|
||||
/// Survives mid-transaction socket drops: when a send/read fails with a socket-level
|
||||
/// error (<see cref="IOException"/>, <see cref="SocketException"/>, <see cref="EndOfStreamException"/>)
|
||||
/// the transport disposes the dead socket, reconnects, and retries the PDU exactly
|
||||
@@ -26,19 +32,11 @@ namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
/// </remarks>
|
||||
public sealed class ModbusTcpTransport : IModbusTransport
|
||||
{
|
||||
private readonly string _host;
|
||||
private readonly int _port;
|
||||
private readonly ModbusSocketLifecycle _life;
|
||||
private readonly TimeSpan _timeout;
|
||||
private readonly bool _autoReconnect;
|
||||
private readonly ModbusKeepAliveOptions _keepAlive;
|
||||
private readonly TimeSpan? _idleDisconnect;
|
||||
private readonly ModbusReconnectOptions _reconnect;
|
||||
private readonly SemaphoreSlim _gate = new(1, 1);
|
||||
private TcpClient? _client;
|
||||
private NetworkStream? _stream;
|
||||
private ushort _nextTx;
|
||||
private bool _disposed;
|
||||
private DateTime _lastSuccessUtc = DateTime.UtcNow;
|
||||
|
||||
/// <summary>Initializes a new instance of the <see cref="ModbusTcpTransport"/> class.</summary>
|
||||
/// <param name="host">The host address or hostname of the Modbus server.</param>
|
||||
@@ -54,84 +52,18 @@ public sealed class ModbusTcpTransport : IModbusTransport
|
||||
TimeSpan? idleDisconnect = null,
|
||||
ModbusReconnectOptions? reconnect = null)
|
||||
{
|
||||
_host = host;
|
||||
_port = port;
|
||||
_timeout = timeout;
|
||||
_autoReconnect = autoReconnect;
|
||||
_keepAlive = keepAlive ?? new ModbusKeepAliveOptions();
|
||||
_idleDisconnect = idleDisconnect;
|
||||
_reconnect = reconnect ?? new ModbusReconnectOptions();
|
||||
_life = new ModbusSocketLifecycle(host, port, timeout, autoReconnect, keepAlive, idleDisconnect, reconnect);
|
||||
}
|
||||
|
||||
/// <inheritdoc />
|
||||
public async Task ConnectAsync(CancellationToken ct)
|
||||
{
|
||||
// Resolve the host explicitly + prefer IPv4. .NET's TcpClient default-constructor is
|
||||
// dual-stack (IPv6 first, fallback to IPv4) — but most Modbus TCP devices (PLCs and
|
||||
// simulators like pymodbus) bind 0.0.0.0 only, so the IPv6 attempt times out and we
|
||||
// burn the entire ConnectAsync budget before even trying IPv4. Resolving first +
|
||||
// dialing the IPv4 address directly sidesteps that.
|
||||
var addresses = await System.Net.Dns.GetHostAddressesAsync(_host, ct).ConfigureAwait(false);
|
||||
var ipv4 = System.Linq.Enumerable.FirstOrDefault(addresses,
|
||||
a => a.AddressFamily == System.Net.Sockets.AddressFamily.InterNetwork);
|
||||
var target = ipv4 ?? (addresses.Length > 0 ? addresses[0] : System.Net.IPAddress.Loopback);
|
||||
|
||||
_client = new TcpClient(target.AddressFamily);
|
||||
EnableKeepAlive(_client, _keepAlive);
|
||||
|
||||
using var cts = CancellationTokenSource.CreateLinkedTokenSource(ct);
|
||||
cts.CancelAfter(_timeout);
|
||||
await _client.ConnectAsync(target, _port, cts.Token).ConfigureAwait(false);
|
||||
_stream = _client.GetStream();
|
||||
_lastSuccessUtc = DateTime.UtcNow;
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Enable SO_KEEPALIVE with aggressive probe timing. DL205/DL260 doesn't send keepalives
|
||||
/// itself; having the OS probe the socket every ~30s lets the driver notice a dead PLC
|
||||
/// or broken NAT path long before the default 2-hour Windows idle timeout fires.
|
||||
/// Non-fatal if the underlying OS rejects the option (some older Linux / container
|
||||
/// sandboxes don't expose the fine-grained timing levers — the driver still works,
|
||||
/// application-level probe still detects problems).
|
||||
/// </summary>
|
||||
private static void EnableKeepAlive(TcpClient client, ModbusKeepAliveOptions opts)
|
||||
{
|
||||
if (!opts.Enabled) return;
|
||||
try
|
||||
{
|
||||
client.Client.SetSocketOption(SocketOptionLevel.Socket, SocketOptionName.KeepAlive, true);
|
||||
// A TimeSpan < 1s previously truncated to 0 via the int cast,
|
||||
// which Windows / Linux interpret as "use the default" — silently defeating the
|
||||
// configured keep-alive timing. Round up to at least 1 second so a sub-second
|
||||
// configuration still produces a real keep-alive cadence. Negative values are
|
||||
// also clamped to 1 to avoid surfacing as OS errors.
|
||||
client.Client.SetSocketOption(SocketOptionLevel.Tcp, SocketOptionName.TcpKeepAliveTime,
|
||||
ClampToWholeSeconds(opts.Time));
|
||||
client.Client.SetSocketOption(SocketOptionLevel.Tcp, SocketOptionName.TcpKeepAliveInterval,
|
||||
ClampToWholeSeconds(opts.Interval));
|
||||
client.Client.SetSocketOption(SocketOptionLevel.Tcp, SocketOptionName.TcpKeepAliveRetryCount, opts.RetryCount);
|
||||
}
|
||||
catch { /* best-effort; older OSes may not expose the granular knobs */ }
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Cast a <see cref="TimeSpan"/> to a whole number of seconds with a
|
||||
/// minimum of 1 — protects callers from the int-cast truncation that turned 500 ms
|
||||
/// keep-alive timing into "use the default" on most OSes.
|
||||
/// </summary>
|
||||
/// <param name="ts">The timespan to clamp to whole seconds.</param>
|
||||
/// <returns>The clamped duration expressed as a whole number of seconds, never less than 1.</returns>
|
||||
internal static int ClampToWholeSeconds(TimeSpan ts)
|
||||
{
|
||||
var seconds = (int)Math.Ceiling(ts.TotalSeconds);
|
||||
return seconds < 1 ? 1 : seconds;
|
||||
}
|
||||
public Task ConnectAsync(CancellationToken ct) => _life.ConnectAsync(ct);
|
||||
|
||||
/// <inheritdoc />
|
||||
public async Task<byte[]> SendAsync(byte unitId, byte[] pdu, CancellationToken ct)
|
||||
{
|
||||
if (_disposed) throw new ObjectDisposedException(nameof(ModbusTcpTransport));
|
||||
if (_stream is null) throw new InvalidOperationException("Transport not connected");
|
||||
if (_life.Stream is null) throw new InvalidOperationException("Transport not connected");
|
||||
|
||||
await _gate.WaitAsync(ct).ConfigureAwait(false);
|
||||
try
|
||||
@@ -140,27 +72,27 @@ public sealed class ModbusTcpTransport : IModbusTransport
|
||||
// threshold, tear it down + reconnect before this PDU lands. Defends against silent
|
||||
// NAT / firewall reaping where the socket looks alive locally but the upstream side
|
||||
// dropped it minutes ago.
|
||||
if (_idleDisconnect.HasValue && DateTime.UtcNow - _lastSuccessUtc > _idleDisconnect.Value)
|
||||
if (_life.ShouldReconnectForIdle())
|
||||
{
|
||||
await TearDownAsync().ConfigureAwait(false);
|
||||
await ConnectWithBackoffAsync(ct).ConfigureAwait(false);
|
||||
await _life.TearDownAsync().ConfigureAwait(false);
|
||||
await _life.ConnectWithBackoffAsync(ct).ConfigureAwait(false);
|
||||
}
|
||||
|
||||
try
|
||||
{
|
||||
var result = await SendOnceAsync(unitId, pdu, ct).ConfigureAwait(false);
|
||||
_lastSuccessUtc = DateTime.UtcNow;
|
||||
_life.MarkSuccess();
|
||||
return result;
|
||||
}
|
||||
catch (Exception ex) when (_autoReconnect && IsSocketLevelFailure(ex))
|
||||
catch (Exception ex) when (_life.AutoReconnect && ModbusSocketLifecycle.IsSocketLevelFailure(ex))
|
||||
{
|
||||
// Mid-transaction drop: tear down the dead socket, reconnect (with backoff if
|
||||
// configured), resend. Single retry — if it fails again, let it propagate so
|
||||
// health/status reflect reality.
|
||||
await TearDownAsync().ConfigureAwait(false);
|
||||
await ConnectWithBackoffAsync(ct).ConfigureAwait(false);
|
||||
await _life.TearDownAsync().ConfigureAwait(false);
|
||||
await _life.ConnectWithBackoffAsync(ct).ConfigureAwait(false);
|
||||
var result = await SendOnceAsync(unitId, pdu, ct).ConfigureAwait(false);
|
||||
_lastSuccessUtc = DateTime.UtcNow;
|
||||
_life.MarkSuccess();
|
||||
return result;
|
||||
}
|
||||
}
|
||||
@@ -170,43 +102,6 @@ public sealed class ModbusTcpTransport : IModbusTransport
|
||||
}
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Connect attempt with the configured geometric backoff. The first attempt fires after
|
||||
/// <see cref="ModbusReconnectOptions.InitialDelay"/> (default zero — immediate); each
|
||||
/// subsequent attempt sleeps for the previous delay times <c>BackoffMultiplier</c>,
|
||||
/// capped at <c>MaxDelay</c>. Caller's cancellation token aborts the loop.
|
||||
/// </summary>
|
||||
private async Task ConnectWithBackoffAsync(CancellationToken ct)
|
||||
{
|
||||
var delay = _reconnect.InitialDelay;
|
||||
var attempt = 0;
|
||||
while (true)
|
||||
{
|
||||
if (delay > TimeSpan.Zero)
|
||||
await Task.Delay(delay, ct).ConfigureAwait(false);
|
||||
try
|
||||
{
|
||||
await ConnectAsync(ct).ConfigureAwait(false);
|
||||
return;
|
||||
}
|
||||
catch (Exception ex) when (IsSocketLevelFailure(ex) && _autoReconnect)
|
||||
{
|
||||
attempt++;
|
||||
// Geometric growth, capped. Use Math.Min on ticks so we don't overflow with
|
||||
// pathological multipliers / long deployments.
|
||||
var nextTicks = (long)(Math.Max(delay.Ticks, TimeSpan.FromMilliseconds(100).Ticks) * _reconnect.BackoffMultiplier);
|
||||
delay = TimeSpan.FromTicks(Math.Min(nextTicks, _reconnect.MaxDelay.Ticks));
|
||||
if (attempt >= 10)
|
||||
{
|
||||
// Bail after 10 attempts to surface persistent failure to the caller. With
|
||||
// the default backoff (1s base, 2.0x mult, 30s cap) this is roughly 4 minutes
|
||||
// of attempts; with InitialDelay=0 it's immediate up to the same cap.
|
||||
throw;
|
||||
}
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Executes exactly one Modbus transaction on the current socket.
|
||||
/// </summary>
|
||||
@@ -230,7 +125,8 @@ public sealed class ModbusTcpTransport : IModbusTransport
|
||||
/// </remarks>
|
||||
private async Task<byte[]> SendOnceAsync(byte unitId, byte[] pdu, CancellationToken ct)
|
||||
{
|
||||
if (_stream is null) throw new InvalidOperationException("Transport not connected");
|
||||
var stream = _life.Stream;
|
||||
if (stream is null) throw new InvalidOperationException("Transport not connected");
|
||||
var txId = ++_nextTx;
|
||||
|
||||
// MBAP: [TxId(2)][Proto=0(2)][Length(2)][UnitId(1)] + PDU
|
||||
@@ -248,11 +144,11 @@ public sealed class ModbusTcpTransport : IModbusTransport
|
||||
cts.CancelAfter(_timeout);
|
||||
try
|
||||
{
|
||||
await _stream.WriteAsync(adu.AsMemory(), cts.Token).ConfigureAwait(false);
|
||||
await _stream.FlushAsync(cts.Token).ConfigureAwait(false);
|
||||
await stream.WriteAsync(adu.AsMemory(), cts.Token).ConfigureAwait(false);
|
||||
await stream.FlushAsync(cts.Token).ConfigureAwait(false);
|
||||
|
||||
var header = new byte[7];
|
||||
await ReadExactlyAsync(_stream, header, cts.Token).ConfigureAwait(false);
|
||||
await ReadExactlyAsync(stream, header, cts.Token).ConfigureAwait(false);
|
||||
var respTxId = (ushort)((header[0] << 8) | header[1]);
|
||||
if (respTxId != txId)
|
||||
throw new ModbusTransportDesyncException(
|
||||
@@ -264,7 +160,7 @@ public sealed class ModbusTcpTransport : IModbusTransport
|
||||
ModbusTransportDesyncException.DesyncReason.TruncatedFrame,
|
||||
$"Modbus response length too small: {respLen}");
|
||||
var respPdu = new byte[respLen - 1];
|
||||
await ReadExactlyAsync(_stream, respPdu, cts.Token).ConfigureAwait(false);
|
||||
await ReadExactlyAsync(stream, respPdu, cts.Token).ConfigureAwait(false);
|
||||
|
||||
// Exception PDU: function code has high bit set. This is a well-formed protocol-level
|
||||
// error — the socket is still coherent, so it MUST propagate without teardown.
|
||||
@@ -280,7 +176,7 @@ public sealed class ModbusTcpTransport : IModbusTransport
|
||||
catch (ModbusTransportDesyncException)
|
||||
{
|
||||
// Framing violation: the socket is desynchronized — never reuse it.
|
||||
await TearDownAsync().ConfigureAwait(false);
|
||||
await _life.TearDownAsync().ConfigureAwait(false);
|
||||
throw;
|
||||
}
|
||||
catch (OperationCanceledException) when (!ct.IsCancellationRequested)
|
||||
@@ -288,33 +184,13 @@ public sealed class ModbusTcpTransport : IModbusTransport
|
||||
// Per-op timeout fired (NOT the caller). The response is unknown / may still land later
|
||||
// and corrupt the next read — tear the socket down and normalize as a desync so the
|
||||
// reconnect retry / status mapping engages.
|
||||
await TearDownAsync().ConfigureAwait(false);
|
||||
await _life.TearDownAsync().ConfigureAwait(false);
|
||||
throw new ModbusTransportDesyncException(
|
||||
ModbusTransportDesyncException.DesyncReason.Timeout,
|
||||
$"Modbus per-op response timeout after {_timeout.TotalMilliseconds:0}ms");
|
||||
}
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Distinguish socket-layer failures (eligible for reconnect-and-retry) from
|
||||
/// protocol-layer failures (must propagate — retrying the same PDU won't help if the
|
||||
/// PLC just returned exception 02 Illegal Data Address).
|
||||
/// </summary>
|
||||
private static bool IsSocketLevelFailure(Exception ex) =>
|
||||
ex is EndOfStreamException
|
||||
|| ex is IOException
|
||||
|| ex is SocketException
|
||||
|| ex is ObjectDisposedException;
|
||||
|
||||
private async Task TearDownAsync()
|
||||
{
|
||||
try { if (_stream is not null) await _stream.DisposeAsync().ConfigureAwait(false); }
|
||||
catch { /* best-effort */ }
|
||||
_stream = null;
|
||||
try { _client?.Dispose(); } catch { }
|
||||
_client = null;
|
||||
}
|
||||
|
||||
private static async Task ReadExactlyAsync(Stream s, byte[] buf, CancellationToken ct)
|
||||
{
|
||||
var read = 0;
|
||||
@@ -332,12 +208,7 @@ public sealed class ModbusTcpTransport : IModbusTransport
|
||||
{
|
||||
if (_disposed) return;
|
||||
_disposed = true;
|
||||
try
|
||||
{
|
||||
if (_stream is not null) await _stream.DisposeAsync().ConfigureAwait(false);
|
||||
}
|
||||
catch { /* best-effort */ }
|
||||
_client?.Dispose();
|
||||
await _life.DisposeAsync().ConfigureAwait(false);
|
||||
_gate.Dispose();
|
||||
}
|
||||
}
|
||||
|
||||
@@ -1,9 +1,10 @@
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
|
||||
/// <summary>
|
||||
/// Raised when a Modbus TCP transaction leaves the single-flight socket in an unknown /
|
||||
/// Raised when a Modbus transaction leaves the single-flight socket in an unknown /
|
||||
/// desynchronized state — a per-op response timeout, or a framing violation (transaction-id
|
||||
/// mismatch or truncated MBAP length). Unlike a Modbus <em>exception PDU</em> (a well-formed
|
||||
/// mismatch, truncated frame, RTU CRC mismatch, or RTU unit-address mismatch). Unlike a Modbus
|
||||
/// <em>exception PDU</em> (a well-formed
|
||||
/// protocol-level error where the socket is still coherent and the request must simply
|
||||
/// propagate), a desync means bytes may still be in flight or half-read, so the socket is
|
||||
/// unusable and MUST be torn down before this is thrown.
|
||||
@@ -27,8 +28,20 @@ public sealed class ModbusTransportDesyncException : IOException
|
||||
/// <summary>The response MBAP transaction id did not match the request's.</summary>
|
||||
TxIdMismatch,
|
||||
|
||||
/// <summary>The response MBAP length field was below the mandatory minimum (truncated frame).</summary>
|
||||
/// <summary>
|
||||
/// The frame ended before it was complete — the MBAP length field was below the mandatory
|
||||
/// minimum (TCP), or the stream closed mid-frame while reading a length-less RTU frame.
|
||||
/// </summary>
|
||||
TruncatedFrame,
|
||||
|
||||
/// <summary>The RTU frame's trailing CRC-16 did not validate over the received bytes.</summary>
|
||||
CrcMismatch,
|
||||
|
||||
/// <summary>
|
||||
/// A CRC-valid RTU frame carried a slave/unit address other than the one addressed — on an
|
||||
/// RS-485 multi-drop bus, a reply from the wrong slave.
|
||||
/// </summary>
|
||||
UnitMismatch,
|
||||
}
|
||||
|
||||
/// <summary>Gets the reason the socket was classified desynchronized.</summary>
|
||||
|
||||
@@ -0,0 +1,43 @@
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
||||
|
||||
/// <summary>
|
||||
/// Single mapping point from <see cref="ModbusDriverOptions"/> to the concrete
|
||||
/// <see cref="IModbusTransport"/> its <see cref="ModbusDriverOptions.Transport"/> selects.
|
||||
/// Consumed by both <see cref="ModbusDriver"/>'s default transport-factory closure and the
|
||||
/// AdminUI Test-Connect probe, so the <see cref="ModbusTransportMode"/> switch lives in
|
||||
/// exactly one place.
|
||||
/// </summary>
|
||||
public static class ModbusTransportFactory
|
||||
{
|
||||
/// <summary>
|
||||
/// Builds the transport <paramref name="options"/>.<see cref="ModbusDriverOptions.Transport"/>
|
||||
/// selects, threading every shared connection setting (Host/Port/Timeout/AutoReconnect/
|
||||
/// KeepAlive/IdleDisconnectTimeout/Reconnect) through to whichever concrete transport is built.
|
||||
/// </summary>
|
||||
/// <param name="options">Driver configuration options.</param>
|
||||
/// <returns>A <see cref="ModbusRtuOverTcpTransport"/> when <see cref="ModbusTransportMode.RtuOverTcp"/>
|
||||
/// is selected; a <see cref="ModbusTcpTransport"/> when <see cref="ModbusTransportMode.Tcp"/> is selected.</returns>
|
||||
/// <exception cref="ArgumentOutOfRangeException">
|
||||
/// <paramref name="options"/>.<see cref="ModbusDriverOptions.Transport"/> is not a recognized
|
||||
/// <see cref="ModbusTransportMode"/> member — fail loudly rather than silently falling back to TCP/MBAP.
|
||||
/// </exception>
|
||||
public static IModbusTransport Create(ModbusDriverOptions options)
|
||||
{
|
||||
ArgumentNullException.ThrowIfNull(options);
|
||||
return options.Transport switch
|
||||
{
|
||||
ModbusTransportMode.RtuOverTcp => new ModbusRtuOverTcpTransport(
|
||||
options.Host, options.Port, options.Timeout, options.AutoReconnect,
|
||||
keepAlive: options.KeepAlive,
|
||||
idleDisconnect: options.IdleDisconnectTimeout,
|
||||
reconnect: options.Reconnect),
|
||||
ModbusTransportMode.Tcp => new ModbusTcpTransport(
|
||||
options.Host, options.Port, options.Timeout, options.AutoReconnect,
|
||||
keepAlive: options.KeepAlive,
|
||||
idleDisconnect: options.IdleDisconnectTimeout,
|
||||
reconnect: options.Reconnect),
|
||||
_ => throw new ArgumentOutOfRangeException(
|
||||
nameof(options), options.Transport, "Unknown Modbus transport mode."),
|
||||
};
|
||||
}
|
||||
}
|
||||
+15
@@ -27,6 +27,16 @@
|
||||
}
|
||||
</InputSelect>
|
||||
</div>
|
||||
<div class="col-md-3">
|
||||
<label class="form-label">Transport</label>
|
||||
<InputSelect @bind-Value="_form.Transport" @bind-Value:after="EmitAsync" class="form-select form-select-sm">
|
||||
@foreach (var e in Enum.GetValues<ModbusTransportMode>())
|
||||
{
|
||||
<option value="@e">@e</option>
|
||||
}
|
||||
</InputSelect>
|
||||
<div class="form-text">RtuOverTcp = talk raw RTU frames to a serial→Ethernet gateway; must match the gateway's mode.</div>
|
||||
</div>
|
||||
<div class="col-md-3">
|
||||
<label class="form-label">MELSEC sub-family</label>
|
||||
<InputSelect @bind-Value="_form.MelsecSubFamily" @bind-Value:after="EmitAsync" class="form-select form-select-sm">
|
||||
@@ -290,6 +300,9 @@
|
||||
public ModbusFamily Family { get; set; } = ModbusFamily.Generic;
|
||||
public MelsecFamily MelsecSubFamily { get; set; } = MelsecFamily.Q_L_iQR;
|
||||
|
||||
// Wire transport (Tcp = Modbus/TCP MBAP; RtuOverTcp = RTU framing over a serial→Ethernet gateway)
|
||||
public ModbusTransportMode Transport { get; set; } = ModbusTransportMode.Tcp;
|
||||
|
||||
// Transport flags
|
||||
public bool AutoReconnect { get; set; } = true;
|
||||
public int IdleDisconnectTimeoutSeconds { get; set; } = 0;
|
||||
@@ -337,6 +350,7 @@
|
||||
TimeoutSeconds = (int)o.Timeout.TotalSeconds,
|
||||
Family = o.Family,
|
||||
MelsecSubFamily = o.MelsecSubFamily,
|
||||
Transport = o.Transport,
|
||||
AutoReconnect = o.AutoReconnect,
|
||||
IdleDisconnectTimeoutSeconds = o.IdleDisconnectTimeout.HasValue ? (int)o.IdleDisconnectTimeout.Value.TotalSeconds : 0,
|
||||
MaxRegistersPerRead = o.MaxRegistersPerRead,
|
||||
@@ -387,6 +401,7 @@
|
||||
MaxReadGap = (ushort)Math.Clamp(MaxReadGap, 0, 65535),
|
||||
Family = Family,
|
||||
MelsecSubFamily = MelsecSubFamily,
|
||||
Transport = Transport,
|
||||
WriteOnChangeOnly = WriteOnChangeOnly,
|
||||
AutoReconnect = AutoReconnect,
|
||||
KeepAlive = new ModbusKeepAliveOptions
|
||||
|
||||
Reference in New Issue
Block a user