fix(address-space): no UNS value Variable for a reference to an alarm-bearing tag (#896)
v2-ci / unit-tests (push) Has been cancelled

A UnsTagReference to a raw tag that carries an "alarm" object produced a UNS
value Variable that read BadWaitingForInitialData forever (G6 live gate,
TestAlarm002Condition on testmachine-015). BuildUnsReferenceVariables now skips
those references; the equipment gets the alarm only as the raw condition wired
as an event notifier of its folder, which is unchanged (the reference still
feeds RawTagPlan.ReferencingEquipmentPaths).

Why condition-only and not "feed the mirror":
- The raw side has no value node for such a tag: AddressSpaceApplier
  materialises an alarm tag as a condition OR a value variable, never both.
  There is no raw value for the UNS mirror to mirror.
- DriverHostActor skips alarm tags when it builds the value fan-out and write
  routing maps (`continue` before the UNS registration), and the driver leaves
  them out of its value subscription ("subscribed to 5 refs" with 6 tags in
  G6). Feeding the mirror would mean subscribing a value the design says the
  tag does not have.
- Docs already state condition-only: ScriptedAlarms.md ("instead of a value
  variable"), AlarmTracking.md ("only the condition, with no sibling value
  variable"), the v3 design (native alarm = one condition at the raw tag,
  surfaced at equipment via notifiers).
- The composer tests that asserted the mirror were incidental: f4f3e17e
  (v3 B4-WP1) put the alarm on the fixture's Speed tag to test raw alarm
  attachment, and later tests reused Speed for writable / historian / array
  checks of the mirror. No commit or doc chose a value mirror for alarm tags.
- ScadaBridge does not read it: its OtOpcUa alarm path is event subscriptions
  on the equipment/raw folders (v3 alarm B/C live gate), and a node that never
  had a value cannot be a working binding. G6 itself authored the alarm's
  Boolean as a separate value tag (TestAlarm002), which is the supported way to
  read it.

Tests: the composer fixture moves the alarm onto its own HighTemp tag
(Speed is now a plain historized value tag), with a new test asserting no UNS
Variable for the alarm reference, with positive controls (the raw tag still
carries the equipment path; the value references still emit). New real-SDK
test Alarm_bearing_reference_surfaces_as_the_condition_only_against_real_SDK:
no Variable at the UNS path, the Speed mirror present, one condition, the
equipment folder wired as its notifier. Both new tests fail with the skip
removed. Docs: Uns.md, ScriptedAlarms.md, G6 evidence note.

Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
Joseph Doherty
2026-11-12 23:55:49 -05:00
parent d9b2381235
commit 09b373e4db
6 changed files with 147 additions and 14 deletions
+3 -1
View File
@@ -240,7 +240,9 @@ blob and is parsed byte-parity in both the compose (`AddressSpaceComposer`) and
> never one-per-root. Teardown is symmetric (`RemoveNotifier(..., bidirectional:true)` on > never one-per-root. Teardown is symmetric (`RemoveNotifier(..., bidirectional:true)` on
> rebuild / reference removal) so inverse-notifier entries never leak across redeploys. > rebuild / reference removal) so inverse-notifier entries never leak across redeploys.
> Ack/confirm/shelve route on **`ConditionId = RawPath`** (never `SourceNodeId`), and the > Ack/confirm/shelve route on **`ConditionId = RawPath`** (never `SourceNodeId`), and the
> `/alerts` row lists the referencing equipment paths. See > `/alerts` row lists the referencing equipment paths. The equipment gets the condition
> **only**: no UNS value variable is created for a reference to an alarm-bearing tag (#896),
> matching the raw side, which has no value variable either. See
> [AlarmTracking.md](AlarmTracking.md) and the WP4 section of > [AlarmTracking.md](AlarmTracking.md) and the WP4 section of
> `docs/plans/2026-07-15-v3-batch4-address-space-plan.md`. > `docs/plans/2026-07-15-v3-batch4-address-space-plan.md`.
+6
View File
@@ -169,6 +169,12 @@ source-timestamp — the two NodeIds never drift.
- **Native alarms** materialize once at the raw tag (`ConditionId = RawPath`) and - **Native alarms** materialize once at the raw tag (`ConditionId = RawPath`) and
fan via SDK notifiers to the raw device folder AND every referencing equipment fan via SDK notifiers to the raw device folder AND every referencing equipment
folder — see [`ScriptedAlarms.md`](ScriptedAlarms.md) / [`AlarmTracking.md`](AlarmTracking.md). folder — see [`ScriptedAlarms.md`](ScriptedAlarms.md) / [`AlarmTracking.md`](AlarmTracking.md).
A reference to an **alarm-bearing** raw tag therefore creates **no UNS variable**
(#896): the raw side has only the condition and no value to fan, so the
reference's only effect is to wire the condition as an event notifier of the
equipment folder. A client reads the alarm's state from the condition's fields
(`ActiveState`, `AckedState`, …) at either folder, not from a value variable. The
reference still counts for effective-name uniqueness.
Note the two distinct identity strings: the wire **NodeId** is the path Note the two distinct identity strings: the wire **NodeId** is the path
`Area/Line/Equipment/EffectiveName`, while the **effective-name uniqueness key** `Area/Line/Equipment/EffectiveName`, while the **effective-name uniqueness key**
@@ -237,9 +237,11 @@ cleanly with it.
never went active, and its ack would dial a reference the gateway refuses. Three unit tests were added to never went active, and its ack would dial a reference the gateway refuses. Three unit tests were added to
`GalaxyDriverRawPathKeyingTests`. The main one fails with the fix reverted, which was checked by reverting `GalaxyDriverRawPathKeyingTests`. The main one fails with the fix reverted, which was checked by reverting
the fix and re-running it. the fix and re-running it.
- **#896 (open).** The UNS mirror of an alarm-bearing raw tag gets a value Variable that stays - **#896 (fixed after this run).** The UNS mirror of an alarm-bearing raw tag gets a value Variable that stays
`BadWaitingForInitialData` forever, against the documented "condition instead of value variable" contract. `BadWaitingForInitialData` forever, against the documented "condition instead of value variable" contract.
It was not fixed here because the composer test fixtures assert that mirror. It was not fixed here because the composer test fixtures assert that mirror.
Fixed afterwards: the composer no longer emits a UNS Variable for a reference to an alarm-bearing tag, so the
equipment shows only the condition (the `<- #896` Variable in the Step 1 browse is gone).
## Cleanup ## Cleanup
@@ -921,7 +921,8 @@ public static class AddressSpaceComposer
/// equipment path resolve, keyed <c>(realm=Uns, s=Area/Line/Equipment/EffectiveName)</c> and carrying /// equipment path resolve, keyed <c>(realm=Uns, s=Area/Line/Equipment/EffectiveName)</c> and carrying
/// the backing RawPath (Organizes target + fan-out) plus the inherited DataType / writable. A /// the backing RawPath (Organizes target + fan-out) plus the inherited DataType / writable. A
/// reference whose backing tag is unknown, whose RawPath is unresolvable, or whose UNS path segments /// reference whose backing tag is unknown, whose RawPath is unresolvable, or whose UNS path segments
/// are invalid is SKIPPED. Sorted by NodeId ordinal. /// are invalid is SKIPPED. A reference to an ALARM-BEARING tag is skipped too (#896): it surfaces at the
/// equipment as the raw condition's event notifier, not as a value Variable. Sorted by NodeId ordinal.
/// </summary> /// </summary>
private static IReadOnlyList<UnsReferenceVariable> BuildUnsReferenceVariables( private static IReadOnlyList<UnsReferenceVariable> BuildUnsReferenceVariables(
IReadOnlyList<UnsTagReference>? unsTagReferences, IReadOnlyList<UnsTagReference>? unsTagReferences,
@@ -965,6 +966,14 @@ public static class AddressSpaceComposer
// doc-comment; 2026-08-15 surgical-deploys review). Parsed from the SAME TagConfigIntent the raw // doc-comment; 2026-08-15 surgical-deploys review). Parsed from the SAME TagConfigIntent the raw
// tag plan uses, so the two sides can never disagree. // tag plan uses, so the two sides can never disagree.
var intent = TagConfigIntent.Parse(tag.TagConfig); var intent = TagConfigIntent.Parse(tag.TagConfig);
// #896: an alarm-bearing backing tag gets NO UNS value Variable. Its raw side is a Part 9 condition
// with no sibling value variable (AddressSpaceApplier.MaterialiseRawSubtree), the driver host keeps
// it out of the value fan-out and the value subscription (DriverHostActor skips Alarm tags), so a
// mirror Variable here could never receive a value and read BadWaitingForInitialData forever. The
// reference still reaches the equipment: it puts the equipment's path on the raw tag's
// ReferencingEquipmentPaths, and the applier wires the single condition as an event notifier of that
// equipment folder. Same TagConfigIntent the raw pass reads, so the two sides cannot disagree.
if (intent.Alarm is not null) continue;
// Same derivation as BuildRawSubtree's ArrayWritable, off the same row, so a mirror is writable // Same derivation as BuildRawSubtree's ArrayWritable, off the same row, so a mirror is writable
// exactly when its raw node is. // exactly when its raw node is.
var backingArrayWritable = intent.IsArray && arrayWritableFor(tag); var backingArrayWritable = intent.IsArray && arrayWritableFor(tag);
@@ -236,6 +236,84 @@ public sealed class AddressSpaceApplierHierarchyTests : IDisposable
sdkServer.NodeManager!.VariableCount.ShouldBe(2); sdkServer.NodeManager!.VariableCount.ShouldBe(2);
} }
/// <summary>
/// Gitea #896, against a real SDK node manager: an equipment that references a value tag AND an alarm-bearing
/// tag gets a UNS Variable for the value tag only. The alarm tag is the single Part 9 condition at its RawPath,
/// wired as an event notifier of the equipment folder, and no UNS Variable is created at
/// <c>filling/line-1/station-1/HighTemp</c> (on the G6 live gate that Variable existed and read
/// <c>BadWaitingForInitialData</c> forever, because nothing ever feeds it). The value-tag mirror and the
/// condition's equipment notifier are the positive controls.
/// </summary>
[Fact]
public async Task Alarm_bearing_reference_surfaces_as_the_condition_only_against_real_SDK()
{
var applicationUri = $"urn:OtOpcUa.AlarmRefE2e:{Guid.NewGuid():N}";
var started = await OpcUaHostStart.StartAsync(
port => new OpcUaApplicationHost(
new OpcUaApplicationHostOptions
{
ApplicationName = "OtOpcUa.AlarmRefE2e",
ApplicationUri = applicationUri,
OpcUaPort = port,
PublicHostname = "localhost",
PkiStoreRoot = _pkiRoot,
},
NullLogger<OpcUaApplicationHost>.Instance),
() => new OtOpcUaSdkServer(), Ct);
await using var host = started.Host;
var sdkServer = started.Server;
sdkServer.NodeManager.ShouldNotBeNull();
var nm = sdkServer.NodeManager!;
var folder = new RawFolder { RawFolderId = "rf-plant", ClusterId = "c1", Name = "Plant", ParentRawFolderId = null };
var driver = new DriverInstance { DriverInstanceId = "drv-modbus", ClusterId = "c1", Name = "Modbus", DriverType = "Modbus", DriverConfig = "{}", RawFolderId = "rf-plant" };
var device = new Device { DeviceId = "dev-1", DriverInstanceId = "drv-modbus", Name = "dev1", DeviceConfig = "{}" };
var speed = new Tag
{
TagId = "tag-speed", DeviceId = "dev-1", Name = "Speed", DataType = "Float",
AccessLevel = TagAccessLevel.Read, TagConfig = "{}",
};
var highTemp = new Tag
{
TagId = "tag-hightemp", DeviceId = "dev-1", Name = "HighTemp", DataType = "Boolean",
AccessLevel = TagAccessLevel.Read,
TagConfig = "{\"alarm\":{\"alarmType\":\"OffNormalAlarm\",\"severity\":700}}",
};
var area = new UnsArea { UnsAreaId = "nw-area-filling", ClusterId = "c1", Name = "filling" };
var line = new UnsLine { UnsLineId = "nw-line-1", UnsAreaId = "nw-area-filling", Name = "line-1" };
var equipment = new Equipment { EquipmentId = "eq-1", UnsLineId = "nw-line-1", Name = "station-1", MachineCode = "STATION_001" };
var composition = AddressSpaceComposer.Compose(
new[] { area }, new[] { line }, new[] { equipment }, new[] { driver },
Array.Empty<ScriptedAlarm>(),
unsTagReferences: new[]
{
new UnsTagReference { UnsTagReferenceId = "ref-speed", EquipmentId = "eq-1", TagId = "tag-speed" },
new UnsTagReference { UnsTagReferenceId = "ref-hightemp", EquipmentId = "eq-1", TagId = "tag-hightemp" },
},
tags: new[] { speed, highTemp },
rawFolders: new[] { folder }, devices: new[] { device });
var applier = new AddressSpaceApplier(new SdkAddressSpaceSink(nm), NullLogger<AddressSpaceApplier>.Instance);
applier.MaterialiseHierarchy(composition);
applier.MaterialiseRawSubtree(composition);
applier.MaterialiseUnsReferences(composition);
// No UNS Variable for the alarm-bearing reference, and none at the raw RawPath either.
nm.TryGetVariable("filling/line-1/station-1/HighTemp", AddressSpaceRealm.Uns).ShouldBeNull();
nm.TryGetVariable("Plant/Modbus/dev1/HighTemp", AddressSpaceRealm.Raw).ShouldBeNull();
// Positive control 1: the value tag still has both its raw node and its UNS mirror (and nothing else).
nm.TryGetVariable("Plant/Modbus/dev1/Speed", AddressSpaceRealm.Raw).ShouldNotBeNull();
nm.TryGetVariable("filling/line-1/station-1/Speed", AddressSpaceRealm.Uns).ShouldNotBeNull();
nm.VariableCount.ShouldBe(2);
// Positive control 2: the alarm reaches the equipment as the single raw condition wired to its folder.
nm.TryGetAlarmCondition("Plant/Modbus/dev1/HighTemp", AddressSpaceRealm.Raw).ShouldNotBeNull();
nm.AlarmConditionCount.ShouldBe(1);
nm.FolderNotifierCount("eq-1", AddressSpaceRealm.Uns).ShouldBe(1);
}
/// <summary>OpcUaServer-001 — a UNS Area / Line rename-only deploy refreshes the EXISTING folder's /// <summary>OpcUaServer-001 — a UNS Area / Line rename-only deploy refreshes the EXISTING folder's
/// DisplayName IN PLACE against a real SDK node manager (no rebuild, no node count change). Proves the /// DisplayName IN PLACE against a real SDK node manager (no rebuild, no node count change). Proves the
/// full chain: planner emits a RenamedFolders delta → applier drives the surgical /// full chain: planner emits a RenamedFolders delta → applier drives the surgical
@@ -17,7 +17,8 @@ namespace ZB.MOM.WW.OtOpcUa.OpcUaServer.Tests;
public sealed class AddressSpaceComposerDualNamespaceTests public sealed class AddressSpaceComposerDualNamespaceTests
{ {
// A raw chain: RawFolder "Plant" → Driver "Modbus1" → Device "PLC-A" → Group "Motors" → tags. // A raw chain: RawFolder "Plant" → Driver "Modbus1" → Device "PLC-A" → Group "Motors" → tags.
// Speed sits under the group; Status directly under the device; Levels is an array tag. // Speed sits under the group; Status directly under the device; Levels is an array tag; HighTemp is a
// native-alarm tag under the group. Speed, Status and HighTemp are referenced into equipment station-1.
private static AddressSpaceComposition ComposeFullFixture() private static AddressSpaceComposition ComposeFullFixture()
{ {
var folder = new RawFolder { RawFolderId = "raw-plant", ClusterId = "c1", Name = "Plant" }; var folder = new RawFolder { RawFolderId = "raw-plant", ClusterId = "c1", Name = "Plant" };
@@ -33,8 +34,13 @@ public sealed class AddressSpaceComposerDualNamespaceTests
{ {
TagId = "t-speed", DeviceId = "dev-1", TagGroupId = "g1", Name = "Speed", TagId = "t-speed", DeviceId = "dev-1", TagGroupId = "g1", Name = "Speed",
DataType = "Float", AccessLevel = TagAccessLevel.ReadWrite, DataType = "Float", AccessLevel = TagAccessLevel.ReadWrite,
TagConfig = "{\"isHistorized\":true,\"historianTagname\":\"speed_hist\"," + TagConfig = "{\"isHistorized\":true,\"historianTagname\":\"speed_hist\"}",
"\"alarm\":{\"alarmType\":\"LimitAlarm\",\"severity\":700}}", };
var highTemp = new Tag
{
TagId = "t-hightemp", DeviceId = "dev-1", TagGroupId = "g1", Name = "HighTemp",
DataType = "Boolean", AccessLevel = TagAccessLevel.Read,
TagConfig = "{\"alarm\":{\"alarmType\":\"LimitAlarm\",\"severity\":700}}",
}; };
var status = new Tag var status = new Tag
{ {
@@ -53,6 +59,7 @@ public sealed class AddressSpaceComposerDualNamespaceTests
var equip = new Equipment { EquipmentId = "eq-1", UnsLineId = "line-1", Name = "station-1", MachineCode = "STATION_001" }; var equip = new Equipment { EquipmentId = "eq-1", UnsLineId = "line-1", Name = "station-1", MachineCode = "STATION_001" };
var refSpeed = new UnsTagReference { UnsTagReferenceId = "ref-speed", EquipmentId = "eq-1", TagId = "t-speed" }; var refSpeed = new UnsTagReference { UnsTagReferenceId = "ref-speed", EquipmentId = "eq-1", TagId = "t-speed" };
var refHighTemp = new UnsTagReference { UnsTagReferenceId = "ref-hightemp", EquipmentId = "eq-1", TagId = "t-hightemp" };
var refStatus = new UnsTagReference var refStatus = new UnsTagReference
{ {
UnsTagReferenceId = "ref-status", EquipmentId = "eq-1", TagId = "t-status", UnsTagReferenceId = "ref-status", EquipmentId = "eq-1", TagId = "t-status",
@@ -62,8 +69,8 @@ public sealed class AddressSpaceComposerDualNamespaceTests
return AddressSpaceComposer.Compose( return AddressSpaceComposer.Compose(
new[] { area }, new[] { line }, new[] { equip }, new[] { area }, new[] { line }, new[] { equip },
new[] { driver }, Array.Empty<ScriptedAlarm>(), new[] { driver }, Array.Empty<ScriptedAlarm>(),
unsTagReferences: new[] { refSpeed, refStatus }, unsTagReferences: new[] { refSpeed, refStatus, refHighTemp },
tags: new[] { speed, status, levels }, tags: new[] { speed, status, levels, highTemp },
rawFolders: new[] { folder }, rawFolders: new[] { folder },
devices: new[] { device }, devices: new[] { device },
tagGroups: new[] { group }); tagGroups: new[] { group });
@@ -136,11 +143,12 @@ public sealed class AddressSpaceComposerDualNamespaceTests
{ {
var c = ComposeFullFixture(); var c = ComposeFullFixture();
var speed = c.RawTags.Single(t => t.TagId == "t-speed"); var highTemp = c.RawTags.Single(t => t.TagId == "t-hightemp");
speed.Alarm.ShouldNotBeNull(); highTemp.NodeId.ShouldBe("Plant/Modbus1/PLC-A/Motors/HighTemp"); // ConditionId = RawPath
speed.Alarm!.AlarmType.ShouldBe("LimitAlarm"); highTemp.Alarm.ShouldNotBeNull();
speed.Alarm.Severity.ShouldBe(700); highTemp.Alarm!.AlarmType.ShouldBe("LimitAlarm");
speed.ReferencingEquipmentPaths.ShouldBe(new[] { "filling/line-1/station-1" }); highTemp.Alarm.Severity.ShouldBe(700);
highTemp.ReferencingEquipmentPaths.ShouldBe(new[] { "filling/line-1/station-1" });
// A non-alarm tag carries no condition + its own referencing-equipment list. // A non-alarm tag carries no condition + its own referencing-equipment list.
var status = c.RawTags.Single(t => t.TagId == "t-status"); var status = c.RawTags.Single(t => t.TagId == "t-status");
@@ -152,7 +160,35 @@ public sealed class AddressSpaceComposerDualNamespaceTests
levels.ReferencingEquipmentPaths.ShouldBeEmpty(); levels.ReferencingEquipmentPaths.ShouldBeEmpty();
} }
/// <summary>Each UnsTagReference emits a UNS Variable keyed /// <summary>
/// Gitea #896: a reference to an ALARM-BEARING raw tag emits NO UNS value Variable. The raw side of such a
/// tag is a Part 9 condition with no sibling value variable, and the driver host keeps it out of the value
/// fan-out, so a mirror Variable could never receive a value (it read <c>BadWaitingForInitialData</c>
/// forever on the G6 live gate). The equipment still gets the alarm: the reference puts the equipment's
/// path on the raw tag's <c>ReferencingEquipmentPaths</c>, which is what wires the condition as a notifier
/// of the equipment folder. Positive controls: that path is present, and the value references in the same
/// equipment still emit their Variables.
/// </summary>
[Fact]
public void A_reference_to_an_alarm_bearing_tag_emits_no_uns_variable_but_still_reaches_the_equipment()
{
var c = ComposeFullFixture();
c.UnsReferenceVariables.ShouldNotContain(v => v.UnsTagReferenceId == "ref-hightemp");
c.UnsReferenceVariables.ShouldNotContain(v => v.BackingRawPath == "Plant/Modbus1/PLC-A/Motors/HighTemp");
c.UnsReferenceVariables.ShouldNotContain(v => v.NodeId == "filling/line-1/station-1/HighTemp");
// Positive control 1: the condition still reaches station-1 through the raw tag's notifier fan-out.
var highTemp = c.RawTags.Single(t => t.TagId == "t-hightemp");
highTemp.Alarm.ShouldNotBeNull();
highTemp.ReferencingEquipmentPaths.ShouldBe(new[] { "filling/line-1/station-1" });
// Positive control 2: the value references in the same equipment still get their Variables.
c.UnsReferenceVariables.Select(v => v.UnsTagReferenceId).OrderBy(x => x, StringComparer.Ordinal)
.ShouldBe(new[] { "ref-speed", "ref-status" });
}
/// <summary>Each value-tag UnsTagReference emits a UNS Variable keyed
/// <c>s=&lt;Area&gt;/&lt;Line&gt;/&lt;Equipment&gt;/&lt;EffectiveName&gt;</c> (realm=Uns), carrying its backing /// <c>s=&lt;Area&gt;/&lt;Line&gt;/&lt;Equipment&gt;/&lt;EffectiveName&gt;</c> (realm=Uns), carrying its backing
/// RawPath (the Organizes target + fan-out) and inheriting DataType + writable from the raw tag. Effective /// RawPath (the Organizes target + fan-out) and inheriting DataType + writable from the raw tag. Effective
/// name = DisplayNameOverride else the backing raw tag's Name.</summary> /// name = DisplayNameOverride else the backing raw tag's Name.</summary>