fix(tagconfig): close the four #551 residuals — accept-gate-first Inspect, three authoring rules, CSV/service gate, doc sweep

Gitea #551.

1. CSV import ran no driver-typed config gate. Its typed columns were always
   strictly parsed, but the free-form TagConfigJson column reached the database
   unread, so a CSV could author a tag the driver rejects — one that deploys
   green and reads BadNodeIdUnknown forever. RawTagCsvMapper.Parse now names the
   offending row in the staged review grid, and RawTreeService enforces the same
   gate on CreateTag/UpdateTag/ImportTags: a form cannot be the guarantee (the
   API and any future caller reach none of them, and this repo has no bUnit).
   A rejected import row is an ERROR — the batch inserts nothing and the row is
   named — never a skip.

   Note the brief's premise that manual entry rides ImportTagsAsync is wrong:
   RawManualTagEntryModal commits row-by-row via CreateTagAsync, which is why
   the gate had to land on all three write paths.

2/3. The seven pre-#549 Inspect methods ran a hand-list of DescribeInvalidEnum
   checks, so every rejection cause not on the list was invisible. They are now
   ACCEPT-GATE-FIRST (the MTConnect/Sql/OpcUaClient/Calculation shape): ask the
   driver's own reader for the verdict, then explain the refusal, with a
   catch-all so "the parse rejects but Inspect said nothing" is unreachable.
   That closes S7's absent dataType, AbCip members[], Modbus stringByteOrder and
   the type-dependent guards, plus causes the issue did not name (absent
   region/address/tagPath/symbolPath/topic, TwinCAT Structure, MQTT's Sparkplug
   tuple). FOCAS and MQTT keep advisories about ACCEPTED blobs, so they
   diagnose rather than return empty.

   Authoring half: ModbusTagConfigModel gains stringByteOrder;
   AbCipTagConfigModel asks the new AbCipTagDefinitionFactory.DescribeInvalidMember;
   S7TagConfigModel captures whether the SOURCE blob declared dataType and asks
   S7TagDefinitionFactory.DataTypeKey/DeclaresDataType. One authority per rule.

4. Doc sweep: the six factory Inspect summaries, EquipmentTagConfigInspector's
   class remarks and AdminOperationsActor's comment all claimed invalid enums are
   "silently defaulted by the lenient runtime" — false since R2-11 Phase C made
   the runtime reads strict. They describe rejections now.
This commit is contained in:
Joseph Doherty
2026-08-10 00:08:06 -04:00
parent b0d2fa30e3
commit 05b424788f
24 changed files with 1846 additions and 100 deletions
@@ -111,16 +111,61 @@ public static class S7TagDefinitionFactory
}
/// <summary>
/// Deploy-time inspection (05/CONV-2): warns on a present-but-invalid <c>dataType</c> (silently
/// defaulted by the lenient runtime) and on a structurally unparseable TagConfig (a silent
/// <c>BadNodeIdUnknown</c> at runtime). Empty when clean or not an equipment-tag object. Never throws.
/// The <c>TagConfig</c> key carrying the S7 data type. Shared with the AdminUI authoring model so
/// "does the blob declare a type?" is asked of one spelling, not two (Gitea #551).
/// </summary>
public const string DataTypeKey = "dataType";
/// <summary>
/// The RawPath handed to <see cref="FromTagConfig"/> during inspection — the mapper only copies it
/// onto <see cref="S7TagDefinition.Name"/> and never validates it.
/// </summary>
private const string InspectionRawPath = "(inspect)";
/// <summary>
/// <b>The single authority on whether an S7 blob DECLARES a data type</b>, consulted by
/// <see cref="Inspect"/> and by the AdminUI's <c>S7TagConfigModel.Validate</c> alike.
/// <para>
/// S7 is the one driver in the fleet whose reader <b>requires the key to be present</b>
/// (<see cref="FromTagConfig"/> refuses a blob without it, where every sibling falls back to a
/// default), so a hand-authored / CSV / API blob that omits it used to pass both gates and die
/// at the driver with <c>BadNodeIdUnknown</c> — Gitea #551 item 2.
/// </para>
/// <para>
/// Presence is judged on the KEY, not on the value: a non-string token
/// (<c>"dataType": 8</c>) satisfies the presence check and is then treated as absent by
/// <see cref="TagConfigJson.TryReadEnumStrict{TEnum}"/>, so the blob is ACCEPTED as
/// <see cref="S7DataType.Int16"/>. Judging the value here would make this gate stricter than
/// the reader.
/// </para>
/// </summary>
/// <param name="root">The TagConfig root object.</param>
/// <returns><see langword="true"/> when the blob carries a <c>dataType</c> key of any kind.</returns>
public static bool DeclaresDataType(JsonElement root) => root.TryGetProperty(DataTypeKey, out _);
/// <summary>
/// Deploy-time inspection (05/CONV-2): warns for a blob <see cref="FromTagConfig"/> would
/// <b>reject</b> — a structurally unparseable or non-object document, an absent / non-string /
/// blank <c>address</c>, an <b>absent</b> <c>dataType</c> (see <see cref="DeclaresDataType"/>), a
/// present-but-invalid <c>dataType</c> (the runtime enum read is STRICT since R2-11 Phase C, so a
/// typo rejects the tag), or an out-of-range <c>stringLength</c> on a <c>String</c> tag. Such a tag
/// is skipped by the driver and reads <c>BadNodeIdUnknown</c> forever. Empty when the mapper accepts
/// the blob, when it is blank, or when it is not an equipment-tag object. Never throws.
/// </summary>
/// <remarks>
/// <b>The verdict comes from <see cref="FromTagConfig"/>, not from a mirror</b> (Gitea #551) — see
/// <c>ModbusTagDefinitionFactory.Inspect</c>'s remarks for the full argument.
/// </remarks>
/// <param name="reference">The equipment tag's TagConfig JSON.</param>
/// <returns>The warnings; empty when clean.</returns>
public static IReadOnlyList<string> Inspect(string reference)
{
var warnings = new List<string>();
if (string.IsNullOrWhiteSpace(reference) || reference[0] != '{') return warnings;
// The accept gate: whatever the driver reads draws nothing.
if (FromTagConfig(reference, InspectionRawPath, out _)) return warnings;
try
{
using var doc = JsonDocument.Parse(reference);
@@ -130,16 +175,67 @@ public static class S7TagDefinitionFactory
warnings.Add("S7 TagConfig root is not a JSON object — the tag will not resolve (BadNodeIdUnknown).");
return warnings;
}
var w = TagConfigJson.DescribeInvalidEnum<S7DataType>(root, "dataType");
if (w is not null) warnings.Add(w);
DescribeRejection(root, warnings);
}
catch (JsonException)
{
warnings.Add("S7 TagConfig is not valid JSON — the tag will not resolve (BadNodeIdUnknown).");
return warnings;
}
if (warnings.Count == 0)
{
warnings.Add(
"S7 TagConfig was rejected by the driver's tag reader — the driver will skip this tag and "
+ "it will read BadNodeIdUnknown.");
}
return warnings;
}
/// <summary>
/// Explains why <see cref="FromTagConfig"/> refused an object-rooted blob, walking its checks in the
/// same order. Runs only after the mapper has already refused, so it can never invent strictness.
/// </summary>
/// <param name="root">The TagConfig root object.</param>
/// <param name="warnings">The list to append warnings to.</param>
private static void DescribeRejection(JsonElement root, List<string> warnings)
{
if (!root.TryGetProperty("address", out var addrEl) || addrEl.ValueKind != JsonValueKind.String)
{
warnings.Add(
"S7 TagConfig has no string 'address' (e.g. DB1.DBW0, M0.0, I0.0, QD4) — the driver will "
+ "skip this tag and it will read BadNodeIdUnknown.");
}
else if (string.IsNullOrWhiteSpace(addrEl.GetString()))
{
warnings.Add("S7 TagConfig has a blank 'address' — the tag will not resolve (BadNodeIdUnknown).");
}
if (!DeclaresDataType(root))
{
warnings.Add(
"S7 TagConfig has no 'dataType' — the S7 reader REQUIRES the key to be present (unlike its "
+ "sibling drivers, which default it), so the driver will skip this tag and it will read "
+ "BadNodeIdUnknown. Valid: " + string.Join(", ", Enum.GetNames<S7DataType>()) + ".");
}
if (TagConfigJson.DescribeInvalidEnum<S7DataType>(root, DataTypeKey) is { } w) warnings.Add(w);
if (TagConfigJson.TryReadEnumStrict(root, DataTypeKey, S7DataType.Int16, out var dataType)
&& dataType == S7DataType.String)
{
var stringLength = ReadInt(root, "stringLength");
if (stringLength < 0 || stringLength > MaxStringLength)
{
warnings.Add(
$"S7 String tag has a 'stringLength' of {stringLength} — an S7 string is 0–"
+ $"{MaxStringLength} characters, so the tag is rejected (BadNodeIdUnknown).");
}
}
}
private static int ReadInt(JsonElement o, string name)
=> o.TryGetProperty(name, out var e) && e.ValueKind == JsonValueKind.Number