Files
ScadaBridge/tests/ZB.MOM.WW.ScadaBridge.DataConnectionLayer.Tests/OpcUaStatusCodeMappingTests.cs
T
Joseph Doherty fb04b54d62 fix(dcl): map OPC UA status by severity bits so all Good subcodes are Good (ScadaBridge#117)
MapStatusCode returned Uncertain for any non-zero non-Bad code, so GoodLocalOverride,
GoodClamped and info-bit Good variants degraded to Uncertain. Now top two bits decide:
00 Good, 01 Uncertain, 10/11 Bad (BadResourceUnavailable stays Bad, #112 untouched).
The SDK IsGood/IsUncertain(uint) helpers were tried first and failed the subcode tests,
so an explicit mask is used. MxGateway mapper uses the OPC-DA quality byte (>=192 Good)
and is not affected.

Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
2026-11-10 04:48:33 -05:00

25 lines
1.2 KiB
C#

using Opc.Ua;
using ZB.MOM.WW.ScadaBridge.Commons.Interfaces.Protocol;
using ZB.MOM.WW.ScadaBridge.DataConnectionLayer.Adapters;
namespace ZB.MOM.WW.ScadaBridge.DataConnectionLayer.Tests;
/// <summary>ScadaBridge#117: quality follows the StatusCode severity bits, not "== 0".</summary>
public class OpcUaStatusCodeMappingTests
{
[Theory]
[InlineData(StatusCodes.Good, QualityCode.Good)]
[InlineData(StatusCodes.GoodLocalOverride, QualityCode.Good)]
[InlineData(StatusCodes.GoodClamped, QualityCode.Good)]
[InlineData(StatusCodes.Good | 0x0480u, QualityCode.Good)] // info bits set
[InlineData(StatusCodes.Uncertain, QualityCode.Uncertain)]
[InlineData(StatusCodes.UncertainLastUsableValue, QualityCode.Uncertain)]
[InlineData(StatusCodes.UncertainSensorNotAccurate, QualityCode.Uncertain)]
[InlineData(StatusCodes.Bad, QualityCode.Bad)]
[InlineData(StatusCodes.BadNodeIdUnknown, QualityCode.Bad)]
[InlineData(StatusCodes.BadResourceUnavailable, QualityCode.Bad)]
[InlineData(0xC0000000u, QualityCode.Bad)]
public void MapStatusCode_UsesSeverityBits(uint code, QualityCode expected) =>
Assert.Equal(expected, OpcUaDataConnection.MapStatusCode(code));
}