Joseph Doherty 00304a26e6 fix(dcl): resolve OPC UA alarm type NodeId to friendly name so conditionFilter works (#8)
HandleAlarmEvent set AlarmTypeName to the event-type NodeId string ("i=9341"),
but the client-side conditionFilter gate (and the OPC UA WhereClause) use friendly
type names — so a friendly-name filter built a correct server WhereClause yet the
client gate dropped every event (zero alarms delivered). Resolve the event-type
NodeId to its friendly name via an inverse of KnownConditionTypeIds (NodeId-string
fallback for custom types) so both sides agree. Also fix a dead-code ternary in
the SourceName derivation.