Files
ScadaBridge/src/ZB.MOM.WW.ScadaBridge.Commons/Messages/Instance
Joseph Doherty 8aa6bf2270 fix(audit): populate ParentExecutionId on alarm-triggered script runs
M5.4 T4 threaded a `parentExecutionId` parameter through
AlarmActor.SpawnAlarmExecution → AlarmExecutionActor → ScriptRuntimeContext,
but every call site passed null — so alarm on-trigger runs were silently always
execution-tree roots, contradicting the "tag-cascade coverage is complete"
claim in CLAUDE.md and Component-AuditLog.md.

Source the id where a spawner genuinely exists: a static attribute write issued
by a site script (`Instance.SetAttribute`) or by an inbound API request
(`Route.To(...).SetAttributes(...)`, whose ParentExecutionId was already carried
to the site and then dropped). The id rides site-locally through three additive,
nullable fields — no wire, proto or central schema change:

  ScriptRuntimeContext.SetAttribute / RouteToSetAttributesRequest.ParentExecutionId
    → SetStaticAttributeCommand.SourceExecutionId
    → AttributeValueChanged.SourceExecutionId   (InstanceActor static-write path)
    → AlarmActor.SpawnAlarmExecution → AlarmExecutionActor → ScriptRuntimeContext

All four computed trigger types participate. Expression triggers evaluate off
the dispatcher, so the writer of the newest value folded into the snapshot is
captured *with* the snapshot and echoed home on ExpressionEvalResult /
ExpressionEvalFailed — a change arriving mid-flight cannot mis-attribute the
raise.

Deliberately still roots (documented, not deferred): alarms fired by Data
Connection Layer values (external device data has no spawning execution — this
includes the device echo of a script write to a *data-sourced* attribute, so
only static writes cascade), and ScriptActor value-change/conditional/
expression/timer trigger runs (a timer tick has no spawner; a WhileTrue/interval
run has no single identifiable write).

Tests: new SiteRuntime.Tests/Actors/AlarmCascadeParentExecutionTests pins all
three hops — SetAttribute stamps the run's ExecutionId, InstanceActor publishes
it on the change (and publishes null when absent), and ValueMatch/HiLo/
Expression alarms parent the on-trigger run to the writer while a DCL-originated
change leaves it a root.

Docs: CLAUDE.md and Component-AuditLog.md corrected from "complete" to the true
behaviour; Component-SiteRuntime.md gains an "Audit correlation of an on-trigger
run" section with the hop table and the by-design root cases.
2026-08-01 11:22:07 -04:00
..