722b8663c1
OPC UA (RealOpcUaClient): - Append 5 new SelectClauses at indices 13–17 (never renumber 0–12): - 13: AlarmConditionType/ActiveState/TransitionTime → OriginalRaiseTime - 14–17: LimitAlarmType HighHighLimit/HighLimit/LowLimit/LowLowLimit → LimitValue - New OpcUaAlarmMapper.PickLimitValue helper: first non-null in HiHi→Hi→Lo→LoLo priority order, InvariantCulture-formatted; empty string for non-limit alarm types. - HandleAlarmEvent reads new indices with fields.Count > N guards; hard minimum (6) unchanged so base ConditionType events still process without the limit fields. - Document unavailable-by-protocol fields (Category, Description, OperatorUser, CurrentValue) inline in BuildAlarmEventFilter and HandleAlarmEvent. MxGateway (MxGatewayAlarmMapper): - MapTransition: CurrentValue and LimitValue now populated via MxValueToString (uses MxValueExtensions.ToClrValue + InvariantCulture) from OnAlarmTransitionEvent proto fields current_value/limit_value. - MapSnapshot: same — populated from ActiveAlarmSnapshot.current_value/limit_value. - MxValueToString helper (internal): null-safe MxValue → string conversion. Tests (17 new, 40 total pass): - OpcUaAlarmMapperTests: PickLimitValue priority, InvariantCulture, all-null case. - MxGatewayAlarmMapperTests: CurrentValue/LimitValue populate from double/string MxValue; absent fields yield empty strings. - RealOpcUaClientAlarmFilterTests: index alignment assertions (count=18, per-index TypeDefinitionId+BrowsePath), regression guard on existing indices 0–12.