Files
ScadaBridge/docs
Joseph Doherty 08fe5acfe4 fix(dcl): treat OPC UA BadResourceUnavailable as transient Bad; Bad+null keeps last-known value (ScadaBridge#112)
OtOpcUa's out-of-process script runner publishes 0x80040000 with a null value.
- OpcUaDataConnection: logs entry/recovery once per tag, names the symbolic
  status in read errors; never a disconnect (not in the reconnect status set).
- InstanceActor: a Bad update with no value is a quality-only transition
  (keep value, quality Bad, stream publish, no script/alarm/waiter re-eval),
  matching the connection-drop rule. Bad with a value is unchanged.

Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
2026-11-10 04:38:05 -05:00
..