# OtOpcUa v3 raw-path live-gate (Gitea #14) — PASS **Date:** 2026-07-23 · **Scope:** the raw-subtree slice of #14 (decision: "raw gate now, flag B/C"). **Rig:** ScadaBridge docker rig (`scadabridge:latest`, rebuilt with the host-rewrite fix) against the **live `otopcua-dev` v3 cluster** (`otopcua-host:dev`, built 2026-07-23, branch `feat/mesh-phase5`, past the v3 merge `ec6598ce`). Related: scope doc `2026-07-23-otopcua-v3-dual-namespace-cutover-scope.md`, phase-2 plan `2026-07-23-otopcua-v3-nsu-hardening-and-browse-ux.md`. ## Headline ScadaBridge is confirmed **structurally v3-safe against a real dual-namespace server** — durable `nsu=` references are emitted by browse, stored on bindings, and resolved live against the server's `NamespaceArray` to Good-quality reads. The gate also **surfaced and fixed a real DCL robustness bug** (couldn't dial a server advertising `0.0.0.0`). Items **B/C remain deferred** — the dev cluster has no UNS nodes and no native alarms to gate them against. ## Environment findings - v3 cluster publishes both namespaces: `ns=2 = https://zb.com/otopcua/raw`, `ns=3 = https://zb.com/otopcua/uns`. **Raw lands at ns=2 — the exact index collision scope §4 item A predicted** (v2's sole namespace and v3 raw both at ns=2). - Raw tree is **sparsely populated**: one materialized live Variable, `nsu=https://zb.com/otopcua/raw;s=sa-modbus2/plc/SiteAOnly` (Int16, AccessLevel=1 → **read-only**). Other drivers (calc1, opcua1, pymodbus, gate-modbus, Area1) expose folders but no live leaf tags. - **UNS (ns=3) is empty** — `ns=3;s=OtOpcUa` → `BadNodeIdUnknown`; no Equipment authored. - **No native alarms** — zero `HasCondition`/`HasEventSource` refs anywhere in the raw tree. ## The fix this gate produced `RealOpcUaClient` took the server-advertised `EndpointDescription.EndpointUrl` verbatim for the session channel. OtOpcUa advertises `opc.tcp://0.0.0.0:4840/OtOpcUa` (its `OpcUaApplicationHostOptions.PublicHostname` defaults to `0.0.0.0`), and dialling `0.0.0.0` from inside the client container hits its own loopback → connect fails. Added `RealOpcUaClient.RewriteEndpointHostForReachability` (swaps the advertised authority for the reachable discovery host/port, preserves scheme+path, no-op when already reachable), called in both `ConnectAsync` and `VerifyEndpointAsync`. Mirrors `CoreClientUtils.SelectEndpoint` and OtOpcUa's own client (`IEndpointDiscovery`). Commit `a1abbff7` on `fix/opcua-discovery-host-rewrite`; 9 unit tests (`RealOpcUaClientEndpointRewriteTests`). ## Wiring (how the gate was run) 1. Rebuilt `scadabridge:latest` with the fix (`bash docker/deploy.sh`). 2. `docker network connect otopcua-dev_default scadabridge-site-a-a` (and `-b`) — bridged the two docker networks so site-a can resolve `otopcua-dev-site-a-1-1`. 3. `data-connection create --site-id 1 --name OtOpcUa-v3-raw --protocol OpcUa` → `endpointUrl=opc.tcp://otopcua-dev-site-a-1-1:4840/OtOpcUa`, securityMode none (id **3044**). 4. `deploy artifacts --site-id 1` — pushed the def to site-a's LocalDb + made it live in the DCL. 5. Template **2148** (`OtOpcUaV3Probe`) + attribute `SiteA` (Int32, `--data-source nsu=https://zb.com/otopcua/raw;s=sa-modbus2/plc/SiteAOnly`); instance **98** (`otopcua-v3-probe-1`) on site-a; `set-bindings [["SiteA",3044]]`; `deploy instance`. ## Checks | # | Check | Result | |---|-------|--------| | 1 | Connect via `ConnectAsync` (through the rewrite fix) | **PASS** — `data-connection browse` returned the address space | | 2 | Connect via `VerifyEndpointAsync` (second rewrite call site) | **PASS** — `verify-endpoint` → `{"success":true}` | | 3 | Browse emits durable `nsu=` throughout | **PASS** — root `nsu=…/raw;s=OtOpcUa`, drivers + `…;s=sa-modbus2/plc/SiteAOnly` | | 4 | Both namespaces visible / discoverable | **PASS (partial)** — raw browsable; uns registered but empty (nothing to browse) | | 5 | Durable `nsu=` binding resolves live | **PASS** — attribute stores `nsu=…`, subscription resolves it against the live `NamespaceArray` | | 6 | Read round-trip, Good quality, live | **PASS** — `SiteA` Good, values changing 59689→59806→59822→59834 across snapshots | | 7 | Write round-trip | **N/A** — the only materialized tag is read-only (AccessLevel=1); no writable v3 tag to gate | ## Deferred (unchanged — need OtOpcUa-side authoring on the dev cluster) - **Item A** — re-author legacy `ns=2` bindings to `nsu=` (data; the collision is confirmed real here). - **Item B** — native-alarm dedup across raw+uns fan-out: **no native alarms exist** to drive it. - **Item C** — UNS-bound → RawPath alarm routing: **no UNS nodes and no alarms exist** to drive it. To gate B/C, the OtOpcUa dev cluster needs UNS Equipment authored (populate ns=3, referencing raw tags) and at least one alarm-configured tag raising a Part-9 condition that fans to raw + equipment notifiers. ## Rig artifacts created (non-default rig state) - ScadaBridge site-a-a / site-a-b attached to `otopcua-dev_default` (dropped on next `docker/deploy.sh`). - Site-a config: DataConnection **3044** `OtOpcUa-v3-raw`, template **2148**, instance **98** (deployed). Harmless; remove with `instance delete 98` / `template delete 2148` / `data-connection delete 3044` if a clean rig is wanted.