MES alarm-status API §6.4 (docs/plans/2026-06-30-mes-alarm-status-api.md,
Phase 1 task 1). MES needs a real AckDT for a triggered alarm, and the mirror
carried acked-vs-unacked but never WHEN. AckTime now rides the whole path:
DCL transition -> AlarmStateChanged -> gRPC AlarmStateUpdate -> site SQLite.
Stamping rule, identical on both protocols: non-null ONLY while the condition
is active AND acknowledged. That single predicate yields all three required
behaviours -- null while unacked, cleared on re-raise (a re-raise arrives
unacknowledged), and no phantom ack on a return-to-normal. The last one is
load-bearing for MxGateway, which maps INACTIVE to Acknowledged = true; without
the active check every clear would claim an ack the system never observed.
Provenance is honest, never fabricated:
- OPC UA A&C supplies a TRUE ack instant, so we now select it:
AcknowledgeableConditionType/AckedState/TransitionTime at SelectClause
index 18, APPENDED so the positional reads at 0-17 keep their meaning.
Servers that omit the field fall back to the event's own Time.
- MxAccess Gateway supplies none, so the ack transition's own timestamp is
used -- accurate to when the system SAW the ack. An ACTIVE_ACKED
re-subscribe snapshot restores one from LastTransitionTimestamp rather
than dropping it.
The decision lives in pure mappers (Opc/Mx AlarmMapper.DeriveAckTime), so it is
unit-tested with no live server or gateway.
Additive-only throughout: init-only property on AlarmStateChanged, trailing
optional positional on NativeAlarmTransition (all 14-arg call sites untouched),
proto field 24 (never reusing a number) regenerated via docker/regen-proto.sh
sitestream with the csproj diff verified empty.
Persistence rides native_alarm_state's existing metadata_json blob rather than
a new column -- deliberately. That table is RegisterReplicated in
SiteLocalDbSetup and LocalDb builds its CDC triggers from the column list at
registration time, so an additive JSON property changes no schema, no triggers
and no replication contract; metadata_json is exactly the extension point UA4
introduced for this. Rows written before the field deserialize it as null.
Tests: 4 OPC UA + 6 MxGateway mapper cases, 3 NativeAlarmActor (emit,
failover rehydrate, pre-AckTime row), 1 proto round-trip incl. the null case,
4 Commons additive/back-compat. The OPC UA SelectClause count lock-in moves
18 -> 19 with an index-18 assertion -- intended, the clause is appended, which
is precisely what that guard exists to make visible.
A native OPC UA alarm source's SourceReference has to be two things at once:
it is parsed as a NodeId to open the monitored item, and matched as a plain-name
prefix against the event's SourceName to route the transition to an instance. No
string is both, so a NodeId-form binding subscribed correctly and then silently
dropped every transition — "pymodbus/plc/HR200".StartsWith("nsu=...;s=pymodbus/plc/HR200")
is false. Only the empty (Server-object) binding worked, because StartsWith("")
matches everything, which is why the sole live smoke test never caught it.
Each OPC UA alarm feed is opened for exactly one binding, so every transition on
it belongs to that binding. The adapter now tags each transition's routing
identity (SourceObjectReference) with the binding string verbatim via the pure
OpcUaAlarmMapper.BuildIdentity, making DataConnectionActor's routing key an exact
match regardless of whether the binding is stored as ns=<index> or the durable
nsu=<uri> form. The Server-object aggregate feed keeps an empty routing identity,
so it reaches only "mirror everything" subscribers and never leaks into a
specific-node binding. The per-condition SourceReference key stays the readable
SourceName.ConditionName, so persistence and display are unchanged, and MxGateway
is untouched — its bindings are names and its mapper already emits matching names.
Unblocked by lmxopcua#473 (OtOpcUa now populates SourceNode/SourceName/EventType
on conditions); SourceName is the RawPath, so the per-condition key is unique.
Live end-to-end verification against native alarms still needs a v3 rig.
Fixes: Gitea #17
OPC UA (RealOpcUaClient):
- Append 5 new SelectClauses at indices 13–17 (never renumber 0–12):
- 13: AlarmConditionType/ActiveState/TransitionTime → OriginalRaiseTime
- 14–17: LimitAlarmType HighHighLimit/HighLimit/LowLimit/LowLowLimit → LimitValue
- New OpcUaAlarmMapper.PickLimitValue helper: first non-null in HiHi→Hi→Lo→LoLo
priority order, InvariantCulture-formatted; empty string for non-limit alarm types.
- HandleAlarmEvent reads new indices with fields.Count > N guards; hard minimum (6)
unchanged so base ConditionType events still process without the limit fields.
- Document unavailable-by-protocol fields (Category, Description, OperatorUser,
CurrentValue) inline in BuildAlarmEventFilter and HandleAlarmEvent.
MxGateway (MxGatewayAlarmMapper):
- MapTransition: CurrentValue and LimitValue now populated via MxValueToString
(uses MxValueExtensions.ToClrValue + InvariantCulture) from OnAlarmTransitionEvent
proto fields current_value/limit_value.
- MapSnapshot: same — populated from ActiveAlarmSnapshot.current_value/limit_value.
- MxValueToString helper (internal): null-safe MxValue → string conversion.
Tests (17 new, 40 total pass):
- OpcUaAlarmMapperTests: PickLimitValue priority, InvariantCulture, all-null case.
- MxGatewayAlarmMapperTests: CurrentValue/LimitValue populate from double/string
MxValue; absent fields yield empty strings.
- RealOpcUaClientAlarmFilterTests: index alignment assertions (count=18, per-index
TypeDefinitionId+BrowsePath), regression guard on existing indices 0–12.