QA Warm gate (lmxopcua#907, 2026-11-13): a graceful stop of the Warm Primary
reported ServiceLevel 0 for ~6 s - shorter than the 10 s degraded window - the
next unreadable sample cleared the streak, and the connection retried the stopped
node FailoverRetryCount times: Good on the peer after 66 s, peer Active in 0.2 s.
Two going-away triggers on top of #138, both still requiring a Healthy (>= 200),
higher level on the other endpoint and honouring the minimum dwell:
- ServiceLevel 0 (Part 4 Maintenance) probes the other endpoint at once instead
of waiting out the window - once per degraded streak, so a non-Healthy peer is
re-probed once per window, not every poll. Other Degraded levels (standby 90/50,
booting 1) still wait the window.
- A lost link whose session's last KNOWN ServiceLevel was < 200 (unreadable
samples don't overwrite it) probes the other endpoint before the first
reconnect attempt, holding the reconnect timer. Healthy -> switch and reconnect
at zero delay, the stopped node is never retried; otherwise the ordinary retry
cycle runs (less the probe's time). After only Healthy levels (250/240, Unset),
inside the dwell, or with the feature off: unchanged retry-then-failover.
Tests: DataConnectionGoingAwayFailoverTests (10 cases, each trigger and
non-trigger with positive controls, connect-order artifact assertions) and a real
in-process OPC UA server pair graceful-stop e2e on production defaults: 1.1 s
(lost-link trigger alone 12.1 s, neither 33.1 s -> fails the 10 s bound).
13 mutants, all killed. DCL tests 608/608 (3 full runs); solution 0 warnings.
Docs: Component-DataConnectionLayer, components/DataConnectionLayer.
Not deployed; QA live re-check pending.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Prerequisite for OtOpcUa Warm redundancy (lmxopcua#717): a Warm standby keeps a
healthy session but serves BadOutOfService at a standby ServiceLevel (90/50, boot 1),
so a connection that lands there sat on Bad quality forever.
- OPC UA connections with a backup poll Server_ServiceLevel (i=2267) on the connected
endpoint (IServiceLevelReadable, implemented by OpcUaDataConnection; never raises
Disconnected). A level < 200 sustained for the degraded window (default 10 s), or
the first sample after any (re)connect, triggers a probe of the other endpoint
(short-lived session: connect, read, dispose). Switch only when it reports a
Healthy (>= 200) higher level, and not within the minimum dwell (default 60 s) of
the previous ServiceLevel switch. Both degraded, other unreachable or level
unknown: stay put. 250/240 (today's OtOpcUa) never starts a streak.
- The switch reuses the failover path: SwitchToOtherEndpoint() now shared by all
three triggers, then BecomeReconnecting(ReconnectCause.ServiceLevelFailover) -
zero delay, no unstable accounting, ReSubscribeAll on the new endpoint.
- Config: OpcUaEndpointConfig.ServiceLevelFailover {enabled, degradedWindowSeconds,
minDwellSeconds}, read from the PRIMARY endpoint's JSON only; null = defaults
(enabled, 10, 60). Inside the encrypted protocol JSON, so no schema change or
migration. Central UI: fields in the Backup card next to Failover Retry Count.
Global: ScadaBridge:DataConnection:ServiceLevelPollInterval (2 s) and
ServiceLevelProbeTimeout (15 s).
- Tests: actor tests per trigger/non-trigger with positive controls, an unsolicited
promotion RefreshStart/RefreshEnd test at client and actor level, adapter tests,
and a real in-process OPC UA server pair end to end. All 15 mutants killed.
- Docs: Component-DataConnectionLayer, components/DataConnectionLayer, Component-CLI.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi