scadabridge_site_connection_up never counted data connections. It counts open
central->site gRPC subscriber streams (Debug View + the site-wide alarm feed),
so it correctly reads 0 on a healthy site nobody is watching — and the name
invited reading it as device health. That misreading has already cost a live
debugging session: register row 48's 'connection_up is 0 on all six site
nodes' was healthy steady state, not the fault it was diagnosed as.
Two halves, per the row:
RENAME. scadabridge.site.connection.up -> scadabridge.site.stream.subscribers.active
(helpers SiteConnectionOpened/Closed -> SiteStreamSubscriberOpened/Closed), and
the instrument gains the unit:"1" the other gauges already carried. Every
reference updated: the gRPC server, both test suites, Component-Communication.md,
components/Commons.md, docker/README.md and docker/seed-live-probe.sh. A test
now pins the new name AND asserts the old one is gone, so it cannot creep back.
NEW. scadabridge.site.data_connections.connected / .total — the first exported
data-connection signal (the state existed on the health report and in the CLI,
but never as a metric). connected < total is the alert condition; neither
number alone separates 'a device is down' from 'nothing is configured', which
is why the denominator ships with the numerator.
Sourcing is deliberate on two counts. It is fed by the DCL at its four state
transitions rather than derived from the health report, so the metric survives
a dead report pipeline — the exact failure the 'metrics stale' flag exists to
catch, and a derived gauge would go blind at the same moment. And it uses a
static registry reached through ScadaBridgeTelemetry (the SiteConnectionOpened
precedent) rather than a DI-injected holder: the DCL actors already take
ISiteHealthCollector through their constructors, and threading a second
dependency through both would ripple into every test that builds them. It also
keeps SiteHealthCollector untouched, which matters right now — another agent is
concurrently editing that file for the tag-resolution path.
Removal is wired too: an undeployed connection leaves the registry, so it stops
counting toward the total instead of latching connected < total on forever.
Both gauges read 0 on the standby (connections open on the active node only) —
healthy, documented, and called out in the docs so it does not become the next
site_connection_up.
No ObservedMeters allowlist change: all three instruments ride the existing
ZB.MOM.WW.ScadaBridge meter. (An unlisted meter exports nothing, silently.)
Tests: Commons 711 passed (9 new, delta-based against a baseline with unique
per-test connection names, so they do not inherit the register row 32
QueueDepthGaugeTests static-state flake); Communication 717; DCL 319.
A site health report showed tagResolutionCounts 0/0 for a connection whose
dataConnectionTagQuality on the SAME report read good:2 — reproduced live on
the docker rig against site-a's rig-probe-1 instance (2 Good OPC UA tags on
"OPC PLC Simulator"), on the ACTIVE node's own report.
Not a standby-shadowing or keying/removal problem, and not a serialization
problem: both dictionaries live on one collector instance on one node, and the
CentralControlDtoMapper round-trip is correct in both directions. The actor's
own derived counts (TotalSubscribedTagCount / ResolvedTagCount) were right the
whole time — GetHealthReport replied 2/2.
Root cause: HandleSubscribeCompleted — the path that registers tags on a first,
healthy subscribe — mutated _instancesByTag and _subscriptionIds but never
pushed to ISiteHealthCollector. The only pushes were BecomeConnected's (fires
before any instance subscribes, so its 0/0 is legitimate), the batch apply
(reconnect re-subscribe / resolution probe) and unsubscribe (teardown). A
connection whose tags all resolve first time reaches none of those, and
ScheduleTagResolutionRetry cancels the retry timer outright when nothing is
unresolved — so the connect-time 0/0 was never superseded and stood forever.
The blind spot was therefore worst on a perfectly healthy connection, which is
exactly when the "device still booting / tag path unresolved" diagnostic should
read clean rather than empty. Any reconnect masked it (the batch path pushes),
which is why it presented only on a clean first deploy.
Fix: push the derived counts at the end of the first-subscribe apply, mirroring
the existing push site in HandleBatchSubscribeCompleted. No semantic change to
the null/no-data convention — the map entry already existed, its values were
simply stale zeros.
Tests: fail-before regression test pins the exact mechanism (NSubstitute records
a single UpdateTagResolution(name, 0, 0) pre-fix while the actor reports 2/2).
DCL 320, HealthMonitoring 97, SiteRuntime 605, Communication 717 all green;
slnx builds clean.
Docs: Component-DataConnectionLayer.md said the counts were "derived at report
time", which implies a pull that cannot go stale and papered over this bug.
Corrected to state they are pushed, name the four push sites, and record why a
healthy connection was the worst case.
Closes arch-review remediation residual #1 (DCL unsubscribe-during-reconnect
count staleness).
DataConnectionActor tracked TotalSubscribedTags/ResolvedTags as two int fields
incremented and decremented at five independent sites. ReSubscribeAll clears the
very maps those decrements key off (_subscriptionIds, _unresolvedTags) while
deliberately preserving _subscriptionsByInstance, so an unsubscribe landing
inside a reconnect window matched NEITHER decrement branch: the total leaked +1
per subscribe/reconnect/unsubscribe churn cycle, permanently and cumulatively.
The 37f13e2e discard gate stopped the orphan-handle half of that race; it could
not stop the counters drifting, because they were state of their own.
Both counts are now DERIVED at report time from the authoritative per-tag
collections, which makes the drift unrepresentable rather than merely guarded:
total = _instancesByTag.Count (the per-tag counted set the residual
called for — distinct tags with at least
one subscribing instance)
resolved = _subscriptionIds.Count (tags for which the adapter holds a handle)
Two semantic corrections fall out of the derivation:
- A tag whose subscribe failed at CONNECTION level now counts toward the total.
It was excluded before, yet the reconnect re-subscribe re-issued it from
_subscriptionsByInstance and booked it as resolved — resolved above total, and
a total driven negative by the eventual unsubscribe.
- _tagSubscriberCount is deleted. It duplicated _instancesByTag exactly, so
HandleUnsubscribe's last-subscriber test is now "did UnindexTag drop the key?"
— still O(1), with no parallel count that can disagree about when a handle is
released. The subscribe-success promotion split (fresh vs. unresolved→resolved)
also goes: it existed only to pick which scalar to bump; set sizes get
DataConnectionLayer-020's double-count cases right for free.
Behavior is otherwise unchanged — same logging, same handle release, same
unresolved-tag probing, same in-flight-unsubscribe discard semantics (the long
comment block there is updated for the mechanics that changed).
Tests: five TagResolutionCounts_* cases in DataConnectionActorBatchTests
covering the churn repro (3 cycles), a shared tag losing one instance mid
reconnect, connection-level failure then recovery, plain subscribe/unsubscribe
cycles, and a completed reconnect re-subscribe. Verified failing against the
pre-fix actor (churn: total 1 not 0; connection-level: total 0 not 1) and
passing after. Full DCL suite 319/319; solution builds with 0 warnings.
Docs: Component-DataConnectionLayer.md health-reporting section describes the
derived counts; residuals register item 1 marked RESOLVED.
MES alarm-status API §6.4 (docs/plans/2026-06-30-mes-alarm-status-api.md,
Phase 1 task 1). MES needs a real AckDT for a triggered alarm, and the mirror
carried acked-vs-unacked but never WHEN. AckTime now rides the whole path:
DCL transition -> AlarmStateChanged -> gRPC AlarmStateUpdate -> site SQLite.
Stamping rule, identical on both protocols: non-null ONLY while the condition
is active AND acknowledged. That single predicate yields all three required
behaviours -- null while unacked, cleared on re-raise (a re-raise arrives
unacknowledged), and no phantom ack on a return-to-normal. The last one is
load-bearing for MxGateway, which maps INACTIVE to Acknowledged = true; without
the active check every clear would claim an ack the system never observed.
Provenance is honest, never fabricated:
- OPC UA A&C supplies a TRUE ack instant, so we now select it:
AcknowledgeableConditionType/AckedState/TransitionTime at SelectClause
index 18, APPENDED so the positional reads at 0-17 keep their meaning.
Servers that omit the field fall back to the event's own Time.
- MxAccess Gateway supplies none, so the ack transition's own timestamp is
used -- accurate to when the system SAW the ack. An ACTIVE_ACKED
re-subscribe snapshot restores one from LastTransitionTimestamp rather
than dropping it.
The decision lives in pure mappers (Opc/Mx AlarmMapper.DeriveAckTime), so it is
unit-tested with no live server or gateway.
Additive-only throughout: init-only property on AlarmStateChanged, trailing
optional positional on NativeAlarmTransition (all 14-arg call sites untouched),
proto field 24 (never reusing a number) regenerated via docker/regen-proto.sh
sitestream with the csproj diff verified empty.
Persistence rides native_alarm_state's existing metadata_json blob rather than
a new column -- deliberately. That table is RegisterReplicated in
SiteLocalDbSetup and LocalDb builds its CDC triggers from the column list at
registration time, so an additive JSON property changes no schema, no triggers
and no replication contract; metadata_json is exactly the extension point UA4
introduced for this. Rows written before the field deserialize it as null.
Tests: 4 OPC UA + 6 MxGateway mapper cases, 3 NativeAlarmActor (emit,
failover rehydrate, pre-AckTime row), 1 proto round-trip incl. the null case,
4 Commons additive/back-compat. The OPC UA SelectClause count lock-in moves
18 -> 19 with an index-18 assertion -- intended, the clause is appended, which
is precisely what that guard exists to make visible.
Code review of a1abbff7 found two edge cases: a discovery/advertised URL with no
explicit port emitted a malformed ':-1' (opc.tcp has no Uri default port), and an
IPv6 literal host could lose/double its brackets. Omit the port when neither URL
carries one; bracket an IPv6 host only when missing. +4 tests (12 total).
An OPC UA server advertises its base address from its own config, not the route
the client took — commonly a 0.0.0.0 wildcard bind or an internal container/NAT
hostname. The OPC Foundation session dials EndpointDescription.EndpointUrl
verbatim, so a 0.0.0.0 advertisement resolved to the client's own loopback and
the connect failed. RealOpcUaClient now swaps the advertised authority for the
reachable host/port (ConnectAsync + VerifyEndpointAsync), preserving scheme+path;
no-op when already reachable. Surfaced live-gating OtOpcUa v3 (#14).
A native OPC UA alarm source's SourceReference has to be two things at once:
it is parsed as a NodeId to open the monitored item, and matched as a plain-name
prefix against the event's SourceName to route the transition to an instance. No
string is both, so a NodeId-form binding subscribed correctly and then silently
dropped every transition — "pymodbus/plc/HR200".StartsWith("nsu=...;s=pymodbus/plc/HR200")
is false. Only the empty (Server-object) binding worked, because StartsWith("")
matches everything, which is why the sole live smoke test never caught it.
Each OPC UA alarm feed is opened for exactly one binding, so every transition on
it belongs to that binding. The adapter now tags each transition's routing
identity (SourceObjectReference) with the binding string verbatim via the pure
OpcUaAlarmMapper.BuildIdentity, making DataConnectionActor's routing key an exact
match regardless of whether the binding is stored as ns=<index> or the durable
nsu=<uri> form. The Server-object aggregate feed keeps an empty routing identity,
so it reaches only "mirror everything" subscribers and never leaks into a
specific-node binding. The per-condition SourceReference key stays the readable
SourceName.ConditionName, so persistence and display are unchanged, and MxGateway
is untouched — its bindings are names and its mapper already emits matching names.
Unblocked by lmxopcua#473 (OtOpcUa now populates SourceNode/SourceName/EventType
on conditions); SourceName is the RawPath, so the per-condition key is unique.
Live end-to-end verification against native alarms still needs a v3 rig.
Fixes: Gitea #17
A stored ns=<index> reference is only meaningful against one server's namespace
table. A server that adds, removes or reorders a namespace silently re-points
every binding: best case BadNodeIdUnknown, worst case the index now names a
different namespace holding a colliding identifier and the binding resolves to
the wrong node with Good quality. Nothing could detect that, because ScadaBridge
stored no namespace URI anywhere.
OtOpcUa v3.0 makes this concrete: v2's sole custom namespace and v3's raw
namespace both sit at index 2, so v2-era bindings resolve against v3 without
error while meaning something else entirely.
Adds OpcUaNodeReference as the single translation seam between stored references
and the wire. Resolve() accepts both ns=<index>;s=<id> (existing bindings, which
keep working unchanged) and the durable nsu=<uri>;s=<id>, mapping the URI to the
live index at use time; it is wired into every parse site — subscribe, read,
write, alarm-subscribe and browse. An unpublished URI now throws naming the URI
rather than binding to whatever occupies that index, and a svr= reference to
another server is rejected instead of being resolved against the wrong address
space.
The browser emits ToDurable(), so what the picker shows is what gets stored and
newly-authored bindings are index-proof from the start. That also closes a
round-trip gap: browse previously emitted ExpandedNodeId.ToString(), which for a
URI- or server-index-carrying reference produced a string NodeId.Parse could not
read back — the same method already resolved it correctly 57 lines later.
Bindings stored before this change keep their ns= form and keep working; they are
only as durable as the server's namespace order. Re-authoring against the picker
is what makes them durable, and that re-bind still needs a live v3 rig.
Refs: Gitea #14
Remove project bookkeeping citations from shipped code comments across the
solution: hyphenated task IDs (WP-14, StoreAndForward-025), milestone/task/
issue refs (M3, Task 4, Audit Log #23, #21), Bundle X task-bundle labels,
and C/D/K/S/T phase labels.
Comment text only — no code logic, string/log literals, or XML-doc structure
changed. Genuine descriptions are preserved (only the citation is stripped),
and technical lookalikes are retained (UTF-8, SHA-256, T00:00:00, M365,
UTC-5, pre-C4/pre-C5 schema versions). Flagged by the new CommentChecker
TaskReferenceInComment / TrackingReferenceInComment checks plus targeted
grep passes; full solution builds clean, append-only guard tests pass.
Fixes the 8 findings from the 2026-06-24 re-review (commit c42bb485), with a
regression test per Medium finding:
- DataConnectionLayer-029 (Med): HandleAlarmSubscribeCompleted now mirrors the
tag-path re-check — if a feed is already stored for the source, release the
redundant just-created subscription instead of overwriting + leaking the first
one (the double-subscribe window DCL-023 reopened). +regression test.
- InboundAPI-031 (Med): remove WaitForAttribute's local 5s grace backstop (tighter
than the CommunicationService Ask's timeout+IntegrationTimeout round-trip budget,
so a slow-but-valid timed-out 'false' got cancelled into a 500). Link only the
client-abort + explicit caller tokens; the lower layer owns the backstop. +test.
- SiteRuntime-032 (Med): derive the deployed count from an authoritative set of
deployed config names (HashSet) instead of a map-presence-gated int, so deleting
a DISABLED instance decrements correctly (SiteRuntime-029's gate leaked it).
+deploy->disable->delete regression test.
- StoreAndForward-028 (Med): reset _bufferedCount in StopAsync alongside the
register-guard so a same-instance Stop->Start re-seeds from a clean base (no ~2N
gauge double-count). +restart regression test.
- AuditLog-017 (Low): test the OnIngestAsync scope-resolution guard (actor survives,
replies empty, counts the failure) — no longer unpinned.
- CentralUI-037 / ScriptAnalysis-009 / SiteRuntime-033 (Low): doc-comment + spec
fixes (Database-throws in the inbound sandbox; baseReferences param wording;
native-alarm cap return-to-normal + per-condition NativeAlarmDropped eviction).
Targeted suites green: SiteRuntime 5, StoreAndForward 6, InboundAPI 31,
DataConnectionLayer 10, AuditLog 5, ScriptAnalysis 40, CentralUI ScriptAnalysis 52.
Remediation from the full per-module code review at 4307c381 (findings recorded
separately in code-reviews/).
Highs fixed:
- DeploymentManager-025/SiteRuntime-031: stop broadcasting notification lists + SMTP
configs (incl. credentials) to sites; site purges already-persisted rows on apply
(enforces the central-only delivery design; clears plaintext SMTP creds at rest).
- DataConnectionLayer-023: guard the native-alarm subscribe path against the
mid-flight-unsubscribe adapter-feed leak (mirrors the DCL-021 tag-path fix).
- SiteEventLogging-024: normalize From/To query bounds to UTC (the -016 fix the
audit trail claimed but never committed).
- KpiHistory-001: add an in-flight guard to the recorder sample tick.
- ScriptAnalysis-001: harden the trust analyzer's TPA-absent fallback (resolve
forbidden anchors in the minimal reference set; warn on degraded mode) — anchors
added to validation references only, never the compile gate.
(InboundAPI-026 left to the feat/ipsen-movein effort per owner decision.)
Medium/Low: DM-026 deterministic deploy-status tiebreaker; SR-027/028/029/030
native-alarm leak/phantom-active/delete-during-redeploy fixes; AL-013/014/016;
TE-024 (folder-mutation audit rows now persisted)/025; SF-025 gauge-provider
clear-on-stop; ESG-025/026; SEC-023/024/025; SCA-007/008/009; plus doc/test
accuracy COM-023/024, HOST-025/026, HM-024/025, NS-027/028.
Full-solution build 0 warnings; ~3560 tests across 18 touched suites green.
STATIC tags (no further OnDataChange after advise) depend entirely on the
seed read. Pre-fix HandleSubscribe seeded only on Success && Value != null,
silently dropping a seed that raced the just-created advise (VT_EMPTY) — so a
static tag stayed Uncertain forever while the source read Good. ReSubscribeAll
did no seeding at all, so a static tag could not self-heal across reconnect.
- New SeedTagsAsync helper: per-tag ReadAsync (not a bulk read — some gateways
time out on large batches) with round-based bounded retry
(SeedReadMaxAttempts/SeedReadRetryDelay), logging any tag that never yields a
value (named — previously zero log trace).
- HandleSubscribe seed loop delegates to SeedTagsAsync.
- ReSubscribeAll re-seeds re-advised tags after reconnect via the
generation-guarded TagValueReceived path (fan-out keys off
_subscriptionsByInstance, preserved across reconnect).
Diagnosed live on wonder-app-vd03 2026-06-17 (see scadabridge-dcl-static-tag-false-bad).
Mechanism #2 (single transient-bad push) left as a follow-up.
MXAccess silently no-ops a whole-array write unless the item reference
ends in "[]" (e.g. "<object>.MoveInWorkOrderNumbers[]") — the COM Write
returns success but the value never commits. Reads work either way, so
the bug surfaced only on writes. Mirror the AVEVA MES Camstar API, which
registers array tags as "<object>.<attr>[]" (scalars have no brackets).
WriteAsync now resolves/advises/writes array values against tag + "[]"
(scalars unchanged), keeping the original tag for result mapping. Adds
IsArrayValue matching the ToMxValue/PadArrayToDeclaredSizeAsync array set.
Verified live via mxwrtest against the deployed gateway: bare ref write
ok but read-back unchanged; "[]" ref write commits (read-back changes,
fresh source timestamp). No RealMxGatewayClient unit harness exists (the
gRPC session is concrete) — consistent with how the sibling supervisory/
pad/encode fixes are verified.
Even with correct array encoding (30d07b9), Ipsen MoveIn array writes still
hung: the Galaxy MES-receiver arrays are fixed-size SAFEARRAYs (e.g.
MoveInWorkOrderNumbers = SAFEARRAY(VT_BSTR) dimensions:[50]) and MXAccess only
accepts a write that supplies ALL slots. ScadaBridge sent just the N elements
the MES provided (1-2), so the COM write blocked. Verified on the live gateway:
a full-size (50) constructed array writes via WriteBulk in ~34ms; a short one
does not.
RealMxGatewayClient.WriteAsync now, for a list value, reads the tag's current
array to learn its slot count and pads the value to that length with
element-type defaults (empty string / 0 / false / default) — the caller's
values fill slots 0..N-1, the rest are cleared. The PLC reads the valid count
from a separate scalar (MoveInNumberWorkOrders). If the size can't be
determined (read fails / not an array) the value is written unpadded and a
warning is logged. Scalars are unaffected.
The Ipsen MoveIn e2e (after the supervisory-advise fix landed scalar writes)
exposed a second blocker: writes to List-typed attributes
(MoveInWorkOrderNumbers / MoveInPartNumbers, List<string>) hung at the 30s
device-write timeout while scalar writes succeeded.
InstanceActor.HandleSetDataAttribute already decodes a List attribute's
canonical JSON into a typed List<T> before the write (so the DCL can push a
real array), but RealMxGatewayClient.ToMxValue only had scalar cases — a
List<T> fell through to Convert.ToString and wrote the garbage string
"System.Collections.Generic.List`1[System.String]" to the array Galaxy
node, which the gateway's COM write rejected/blocked.
Add IReadOnlyList<bool|int|long|float|double|string|DateTimeOffset|DateTime>
cases that call the client package's typed array encoders
(VT_ARRAY|VT_BSTR etc.); List<DateTime> is mapped to DateTimeOffset. Covers
every element type AttributeValueCodec produces.
Writes through the MxGateway data connection (e.g. the Ipsen MoveIn flow
writing MES-receiver attributes) hung ~30s and changed nothing, while reads
of the same attributes worked. Root cause: MXAccess only accepts a write on
an item that holds a SUPERVISORY advise; the write path did AddItem +
WriteBulk with no advise and the monitoring subscription used a plain Advise,
so the worker's synchronous COM Write blocked until the gateway command
timeout. (Plain, non-secured writes need no user/login.) Verified live: with a
supervisory advise the write returns ok in ~22ms; without it it does not.
When the connection has no MXAccess write-user context (WriteUserId == 0) it
now behaves as a supervisory client: every advise defaults to
AdviseSupervisory — both the monitoring subscription (SubscribeAsync) and the
write path — so one connection can read and write. A supervisory advise still
delivers OnDataChange (the worker treats either advice kind as sufficient for
updates) so monitoring is unaffected, and the worker's UnAdvise tears down
either kind, so unsubscribe is unchanged. AdviseSupervisory is issued as a raw
MxCommandKind.AdviseSupervisory via the session's Invoke (the client package
exposes only plain Advise). The advise runs at most once per handle via a
Lazy<Task> so a concurrent first-time subscribe+write on the same new handle
both await the same advise (neither writes before it completes); a faulted
advise is evicted so the next write retries. Dropped on unsubscribe. A
configured non-zero WriteUserId keeps the prior plain-advise behaviour.
Surface native (Galaxy/MxGateway) alarms by their object-relative reference
(e.g. "Z28061.HeartbeatTimeoutAlarm") instead of the gateway's full provider
reference ("Galaxy!<area>.<object>.<alarm>"). The area is already preserved in
Category and the object reference is globally unique within the galaxy, so the
full provider prefix added only noise to the alarm identity operators see.
MxGatewayAlarmMapper.MapTransition/MapSnapshot now set SourceReference from
SourceObjectReference, falling back to AlarmFullReference only when the gateway
omits the object reference. +2 mapper tests; full DCL suite green (158).
The MxGateway alarm mapper emits the SnapshotComplete framing sentinel with
empty SourceReference/SourceObjectReference. HandleAlarmTransitionReceived
routed every transition by prefix match against the subscriber's source, so
the empty-ref sentinel ('' .StartsWith("<src>.") == false) was dropped for
any specific source. The NativeAlarmActor buffers snapshot conditions and only
flushes them on SnapshotComplete, so statically-active native alarms delivered
only in the initial snapshot (no later live transition) never surfaced.
Broadcast the SnapshotComplete sentinel to all alarm subscribers (bypassing the
source match + type filter) so each NativeAlarmActor's snapshot swap completes.
Adds a regression test using the real empty-ref sentinel against a specific
(prefix) source.
DataConnectionActor seeded a tag's initial value by Tell-ing TagValueReceived
from HandleSubscribe's background task, which runs BEFORE HandleSubscribeCompleted
registers the instance's tags in _subscriptionsByInstance. HandleTagValueReceived's
fan-out then found no subscriber and dropped the value. A tag that soon gets a
data-change notification recovers, but a STATIC tag (e.g. an idle MES field that
never changes) was left Uncertain forever — the dropped seed was its only value.
Seeds now ride back on SubscribeCompleted and are delivered after registration,
reusing HandleTagValueReceived's generation guard, fan-out and quality accounting.
+1 regression test (DCL026).
OPC UA (RealOpcUaClient):
- Append 5 new SelectClauses at indices 13–17 (never renumber 0–12):
- 13: AlarmConditionType/ActiveState/TransitionTime → OriginalRaiseTime
- 14–17: LimitAlarmType HighHighLimit/HighLimit/LowLimit/LowLowLimit → LimitValue
- New OpcUaAlarmMapper.PickLimitValue helper: first non-null in HiHi→Hi→Lo→LoLo
priority order, InvariantCulture-formatted; empty string for non-limit alarm types.
- HandleAlarmEvent reads new indices with fields.Count > N guards; hard minimum (6)
unchanged so base ConditionType events still process without the limit fields.
- Document unavailable-by-protocol fields (Category, Description, OperatorUser,
CurrentValue) inline in BuildAlarmEventFilter and HandleAlarmEvent.
MxGateway (MxGatewayAlarmMapper):
- MapTransition: CurrentValue and LimitValue now populated via MxValueToString
(uses MxValueExtensions.ToClrValue + InvariantCulture) from OnAlarmTransitionEvent
proto fields current_value/limit_value.
- MapSnapshot: same — populated from ActiveAlarmSnapshot.current_value/limit_value.
- MxValueToString helper (internal): null-safe MxValue → string conversion.
Tests (17 new, 40 total pass):
- OpcUaAlarmMapperTests: PickLimitValue priority, InvariantCulture, all-null case.
- MxGatewayAlarmMapperTests: CurrentValue/LimitValue populate from double/string
MxValue; absent fields yield empty strings.
- RealOpcUaClientAlarmFilterTests: index alignment assertions (count=18, per-index
TypeDefinitionId+BrowsePath), regression guard on existing indices 0–12.
HandleAlarmEvent set AlarmTypeName to the event-type NodeId string ("i=9341"),
but the client-side conditionFilter gate (and the OPC UA WhereClause) use friendly
type names — so a friendly-name filter built a correct server WhereClause yet the
client gate dropped every event (zero alarms delivered). Resolve the event-type
NodeId to its friendly name via an inverse of KnownConditionTypeIds (NodeId-string
fallback for custom types) so both sides agree. Also fix a dead-code ternary in
the SourceName derivation.
conditionFilter was plumbed end-to-end but applied nowhere — a filtered source
silently mirrored all conditions. Define the filter as a comma-separated,
case-insensitive list of condition type names (blank = all); enforce it
authoritatively client-side in DataConnectionActor routing (uniform across OPC UA
+ MxGateway) and, for OPC UA, additionally build a server-side EventFilter
WhereClause as a bandwidth optimization.
Resolve all 622 issues flagged by the enhanced CommentChecker: add missing
<returns> tags (incl. the standard phrasing on non-generic Task methods),
add missing <summary> tags, and replace misused/redundant <inheritdoc/> on
members that override or implement nothing with real documentation.
Documentation-only — no behavior change; solution builds clean.
The NativeAlarmActor sends SubscribeAlarmsRequest to the DCL manager, but the
manager only routed tag/write/browse messages to the per-connection
DataConnectionActor — alarm subscribe/unsubscribe were unhandled and dead-lettered,
so native alarms never subscribed at runtime. Caught by live T28 deployment.
Mirrors the existing HandleRoute forwarding.
Adds IAlarmSubscribableConnection to MxGatewayDataConnection (shared session-less
feed, ref-counted), IMxGatewayClient.RunAlarmStreamAsync over the package
StreamAlarmsAsync with internal reconnect, and MxGatewayAlarmMapper
(AlarmFeedMessage/OnAlarmTransitionEvent -> NativeAlarmTransition). Behavior
verified against a live gateway in Task 28; mapper unit-tested.