AlarmConditionState.Severity mixed two conventions: OPC UA rows carried Part 9
Severity (higher = more severe) while MxGateway native alarms and computed
alarms carried a raw AVEVA-style priority (1 = most urgent). Every consumer
ranks higher as worse, so Worst Severity, the severity filter/sort and the
site event-log Error threshold picked the LEAST urgent MxGateway/computed
alarms.
- AlarmPriorityBands: the OtOpcUa GalaxyAlarmPriority table (lmxopcua#887,
b61f3e05), value for value: 1-250 -> 1000, 251-500 -> 750, 501-750 -> 500,
751-999 -> 250; <= 0 clamps to Critical, > 999 to Low.
- MxGatewayAlarmMapper bands the gateway severity (= AVEVA priority);
AlarmConditionStateFactory.ForComputed bands PriorityLevel. OPC UA unchanged.
- AlarmConditionState gains trailing Priority (int?): the raw source number,
exactly the pre-#129 Severity. AlarmStateChanged.Priority and the wire
AlarmStateUpdate.priority keep that meaning (no proto change); central derives
Severity by kind (SeverityFromPriority), so an older site decodes correctly.
- ScriptAlarm gains trailing Priority. The native MES 900-999 band and the MES
API Severity/MinSeverity/MaxSeverity key off Priority; rig seed scripts moved
from a.Severity to a.Priority, so MES output is unchanged.
- AlarmActor raise logs Error when the banded severity >= 700 (same threshold
as NativeAlarmActor): priority 1-500 Error, 501+ Warning (was raw >= 700).
- NativeAlarmActor upgrades pre-#129 native_alarm_state rows on rehydrate.
- Debug snapshot decode restores Condition.Priority from the row's priority.
- Docs: Commons, DCL, SiteRuntime, Communication, CentralUI, InboundAPI,
HighLevelReqs, MES alarm-status plan, CLAUDE.md.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Design doc and code travel together (CLAUDE.md editing rules), so this records
what the two preceding commits shipped and, more usefully, WHY the non-obvious
choices were made -- the parts a future reader would otherwise re-litigate:
- Component-SiteRuntime.md: the Alarms.CurrentAsync() runtime API entry (why
it is not scope-prefixed, why it is read-only, why placeholder rows are
included), the full ScriptAlarm shape, AckTime on the enriched
AlarmStateChanged, proto field 24, and the metadata_json-vs-new-column
persistence rationale (native_alarm_state is RegisterReplicated; LocalDb
builds its CDC triggers from the column list at registration time).
- Component-DataConnectionLayer.md already carried the AckTime section in the
first commit; this adds the SiteRuntime/ScriptAnalysis/InboundAPI halves.
- Component-ScriptAnalysis.md: accessors returning domain types return the
SAME type on both surfaces, and the trust-model note that a deny-list needs
no entry for a new globals member -- only that its return type resolves in
a permitted namespace.
- Component-InboundAPI.md records the NEGATIVE decision: there is
deliberately no Route.To(...).GetAlarms(...) verb. Alarm state is
per-instance and lives on the site's Instance Actor, so the read goes
through a routed site script and the filtering happens where the data is;
central stays a thin router.
- CLAUDE.md native-alarm bullet gains the enrichment + accessor summary.
- The plan's §7 Phase 1 rows are ticked with 2026-08-01 and annotated with
what was actually built (incl. the two choices that differ from the plan's
"or" options: a dedicated snapshot message rather than DebugSnapshotRequest,
and the extra SandboxScriptHost mirror the plan did not list). Phases 2-4
stay open -- they are deployed config and need a live rig.
Design review 2026-08-01: (1) MES relevance = dedicated severity band 900-999
(script constants, real IsFlaggedForMES predicate); (2) MESReceiver version
DROPPED — CvdReactor is the only implementation, router returns a clean
not-supported error elsewhere; (3) Description = Message else AlarmTypeName;
(4) enrich the native mirror NOW with an additive AckTime (proto +
native_alarm_state + DCL stamping); (5) script names match the endpoints;
(6) shared ReactorAlarms on both sides, suffix behavior as planned;
(7) existing MES API key, no new roles. Plan is now ready to execute.
Ports the legacy WWSupport/APIServer MES alarm-status endpoints onto the
Inbound API, mirroring the MesMoveIn/MesMoveOut pattern; draft for review,
not yet executed. Committed ahead of PLAN-R2-08 T13's hygiene pass.