Commit 1fcc4f5 added a Central-only Require for ScadaBridge:InboundApi:ApiKeyPepper
(>=16 chars) to StartupValidator. That Require fires in Program.cs before WebApplicationFactory
can apply any WithWebHostBuilder config overlays, so it must be satisfied via environment
variables (which ARE in the pre-host AddEnvironmentVariables() pass).
Fix (test-only, no src/ changes):
- CentralDbTestEnvironment: add ScadaBridge__InboundApi__ApiKeyPepper env var (TestPepper
constant, 23 chars) alongside the existing db connection string; restore on Dispose.
Fixes HealthCheckTests, MetricsEndpointTests, and HostStartupTests.CentralRole_StartsWithoutError
which all use CentralDbTestEnvironment.
- CentralActorPathTests.InitializeAsync: set the pepper env var before WebApplicationFactory
is constructed (the class uses IAsyncLifetime directly, not CentralDbTestEnvironment).
- CentralCompositionRootTests ctor + Dispose: same env-var pattern; those tests already had
the pepper in AddInMemoryCollection (DI-layer only, too late for pre-host validation).
- CentralAuditWiringTests ctor + Dispose: same env-var pattern for the same reason.
- StartupValidatorTests.ValidCentralConfig(): add pepper so the unit tests that call
StartupValidator.Validate() directly with a Central config stop failing.
- Add guard tests: Central_MissingApiKeyPepper_FailsValidation,
Central_ShortApiKeyPepper_FailsValidation, Site_ApiKeyPepper_NotRequired — these lock
the production behavior introduced by 1fcc4f5.
Renames the 13 SCADALINK_* runtime env vars → SCADABRIDGE_*, the ScadaLink__
.NET config keys → ScadaBridge__, the stale ScadaLink.Host.exe assembly name
→ ZB.MOM.WW.ScadaBridge.Host.exe, the scadalink_app SQL login → scadabridge_app,
and residual identifiers/comments/docs. Migration records (prior rename
tooling/design, DB-rename helper, this scrub script) carved out.
Adds tools/scrub-scadalink-refs.sh.
The NativeAlarmActor sends SubscribeAlarmsRequest to the DCL manager, but the
manager only routed tag/write/browse messages to the per-connection
DataConnectionActor — alarm subscribe/unsubscribe were unhandled and dead-lettered,
so native alarms never subscribed at runtime. Caught by live T28 deployment.
Mirrors the existing HandleRoute forwarding.
Adds IAlarmSubscribableConnection to MxGatewayDataConnection (shared session-less
feed, ref-counted), IMxGatewayClient.RunAlarmStreamAsync over the package
StreamAlarmsAsync with internal reconnect, and MxGatewayAlarmMapper
(AlarmFeedMessage/OnAlarmTransitionEvent -> NativeAlarmTransition). Behavior
verified against a live gateway in Task 28; mapper unit-tested.
The Test Bindings button was disabled (greyed out) for any attribute bound
to a non-OPC-UA connection. BuildTestableRows() filtered to protocol ==
"OpcUa", a stale gate left over from when OPC UA was the only protocol.
ReadTagValuesCommand is protocol-agnostic (routes through
IDataConnection.ReadBatchAsync, which MxGatewayDataConnection implements),
so the filter only blocked the UI — mirroring the already-fixed IsBrowsable.
Remove the OPC-UA-only filter and update the stale comments. Add a bUnit
regression test (theory over MxGateway + OpcUa) asserting the button is
enabled for a readable-protocol binding.
Verified live: dialog opens for an MxGateway binding and returns a
Good-quality read.