Code review of a1abbff7 found two edge cases: a discovery/advertised URL with no
explicit port emitted a malformed ':-1' (opc.tcp has no Uri default port), and an
IPv6 literal host could lose/double its brackets. Omit the port when neither URL
carries one; bracket an IPv6 host only when missing. +4 tests (12 total).
An OPC UA server advertises its base address from its own config, not the route
the client took — commonly a 0.0.0.0 wildcard bind or an internal container/NAT
hostname. The OPC Foundation session dials EndpointDescription.EndpointUrl
verbatim, so a 0.0.0.0 advertisement resolved to the client's own loopback and
the connect failed. RealOpcUaClient now swaps the advertised authority for the
reachable host/port (ConnectAsync + VerifyEndpointAsync), preserving scheme+path;
no-op when already reachable. Surfaced live-gating OtOpcUa v3 (#14).
A native OPC UA alarm source's SourceReference has to be two things at once:
it is parsed as a NodeId to open the monitored item, and matched as a plain-name
prefix against the event's SourceName to route the transition to an instance. No
string is both, so a NodeId-form binding subscribed correctly and then silently
dropped every transition — "pymodbus/plc/HR200".StartsWith("nsu=...;s=pymodbus/plc/HR200")
is false. Only the empty (Server-object) binding worked, because StartsWith("")
matches everything, which is why the sole live smoke test never caught it.
Each OPC UA alarm feed is opened for exactly one binding, so every transition on
it belongs to that binding. The adapter now tags each transition's routing
identity (SourceObjectReference) with the binding string verbatim via the pure
OpcUaAlarmMapper.BuildIdentity, making DataConnectionActor's routing key an exact
match regardless of whether the binding is stored as ns=<index> or the durable
nsu=<uri> form. The Server-object aggregate feed keeps an empty routing identity,
so it reaches only "mirror everything" subscribers and never leaks into a
specific-node binding. The per-condition SourceReference key stays the readable
SourceName.ConditionName, so persistence and display are unchanged, and MxGateway
is untouched — its bindings are names and its mapper already emits matching names.
Unblocked by lmxopcua#473 (OtOpcUa now populates SourceNode/SourceName/EventType
on conditions); SourceName is the RawPath, so the per-condition key is unique.
Live end-to-end verification against native alarms still needs a v3 rig.
Fixes: Gitea #17
A stored ns=<index> reference is only meaningful against one server's namespace
table. A server that adds, removes or reorders a namespace silently re-points
every binding: best case BadNodeIdUnknown, worst case the index now names a
different namespace holding a colliding identifier and the binding resolves to
the wrong node with Good quality. Nothing could detect that, because ScadaBridge
stored no namespace URI anywhere.
OtOpcUa v3.0 makes this concrete: v2's sole custom namespace and v3's raw
namespace both sit at index 2, so v2-era bindings resolve against v3 without
error while meaning something else entirely.
Adds OpcUaNodeReference as the single translation seam between stored references
and the wire. Resolve() accepts both ns=<index>;s=<id> (existing bindings, which
keep working unchanged) and the durable nsu=<uri>;s=<id>, mapping the URI to the
live index at use time; it is wired into every parse site — subscribe, read,
write, alarm-subscribe and browse. An unpublished URI now throws naming the URI
rather than binding to whatever occupies that index, and a svr= reference to
another server is rejected instead of being resolved against the wrong address
space.
The browser emits ToDurable(), so what the picker shows is what gets stored and
newly-authored bindings are index-proof from the start. That also closes a
round-trip gap: browse previously emitted ExpandedNodeId.ToString(), which for a
URI- or server-index-carrying reference produced a string NodeId.Parse could not
read back — the same method already resolved it correctly 57 lines later.
Bindings stored before this change keep their ns= form and keep working; they are
only as durable as the server's namespace order. Re-authoring against the picker
is what makes them durable, and that re-bind still needs a live v3 rig.
Refs: Gitea #14
Remove project bookkeeping citations from shipped code comments across the
solution: hyphenated task IDs (WP-14, StoreAndForward-025), milestone/task/
issue refs (M3, Task 4, Audit Log #23, #21), Bundle X task-bundle labels,
and C/D/K/S/T phase labels.
Comment text only — no code logic, string/log literals, or XML-doc structure
changed. Genuine descriptions are preserved (only the citation is stripped),
and technical lookalikes are retained (UTF-8, SHA-256, T00:00:00, M365,
UTC-5, pre-C4/pre-C5 schema versions). Flagged by the new CommentChecker
TaskReferenceInComment / TrackingReferenceInComment checks plus targeted
grep passes; full solution builds clean, append-only guard tests pass.
Remediation from the full per-module code review at 4307c381 (findings recorded
separately in code-reviews/).
Highs fixed:
- DeploymentManager-025/SiteRuntime-031: stop broadcasting notification lists + SMTP
configs (incl. credentials) to sites; site purges already-persisted rows on apply
(enforces the central-only delivery design; clears plaintext SMTP creds at rest).
- DataConnectionLayer-023: guard the native-alarm subscribe path against the
mid-flight-unsubscribe adapter-feed leak (mirrors the DCL-021 tag-path fix).
- SiteEventLogging-024: normalize From/To query bounds to UTC (the -016 fix the
audit trail claimed but never committed).
- KpiHistory-001: add an in-flight guard to the recorder sample tick.
- ScriptAnalysis-001: harden the trust analyzer's TPA-absent fallback (resolve
forbidden anchors in the minimal reference set; warn on degraded mode) — anchors
added to validation references only, never the compile gate.
(InboundAPI-026 left to the feat/ipsen-movein effort per owner decision.)
Medium/Low: DM-026 deterministic deploy-status tiebreaker; SR-027/028/029/030
native-alarm leak/phantom-active/delete-during-redeploy fixes; AL-013/014/016;
TE-024 (folder-mutation audit rows now persisted)/025; SF-025 gauge-provider
clear-on-stop; ESG-025/026; SEC-023/024/025; SCA-007/008/009; plus doc/test
accuracy COM-023/024, HOST-025/026, HM-024/025, NS-027/028.
Full-solution build 0 warnings; ~3560 tests across 18 touched suites green.
MXAccess silently no-ops a whole-array write unless the item reference
ends in "[]" (e.g. "<object>.MoveInWorkOrderNumbers[]") — the COM Write
returns success but the value never commits. Reads work either way, so
the bug surfaced only on writes. Mirror the AVEVA MES Camstar API, which
registers array tags as "<object>.<attr>[]" (scalars have no brackets).
WriteAsync now resolves/advises/writes array values against tag + "[]"
(scalars unchanged), keeping the original tag for result mapping. Adds
IsArrayValue matching the ToMxValue/PadArrayToDeclaredSizeAsync array set.
Verified live via mxwrtest against the deployed gateway: bare ref write
ok but read-back unchanged; "[]" ref write commits (read-back changes,
fresh source timestamp). No RealMxGatewayClient unit harness exists (the
gRPC session is concrete) — consistent with how the sibling supervisory/
pad/encode fixes are verified.
Even with correct array encoding (30d07b9), Ipsen MoveIn array writes still
hung: the Galaxy MES-receiver arrays are fixed-size SAFEARRAYs (e.g.
MoveInWorkOrderNumbers = SAFEARRAY(VT_BSTR) dimensions:[50]) and MXAccess only
accepts a write that supplies ALL slots. ScadaBridge sent just the N elements
the MES provided (1-2), so the COM write blocked. Verified on the live gateway:
a full-size (50) constructed array writes via WriteBulk in ~34ms; a short one
does not.
RealMxGatewayClient.WriteAsync now, for a list value, reads the tag's current
array to learn its slot count and pads the value to that length with
element-type defaults (empty string / 0 / false / default) — the caller's
values fill slots 0..N-1, the rest are cleared. The PLC reads the valid count
from a separate scalar (MoveInNumberWorkOrders). If the size can't be
determined (read fails / not an array) the value is written unpadded and a
warning is logged. Scalars are unaffected.
The Ipsen MoveIn e2e (after the supervisory-advise fix landed scalar writes)
exposed a second blocker: writes to List-typed attributes
(MoveInWorkOrderNumbers / MoveInPartNumbers, List<string>) hung at the 30s
device-write timeout while scalar writes succeeded.
InstanceActor.HandleSetDataAttribute already decodes a List attribute's
canonical JSON into a typed List<T> before the write (so the DCL can push a
real array), but RealMxGatewayClient.ToMxValue only had scalar cases — a
List<T> fell through to Convert.ToString and wrote the garbage string
"System.Collections.Generic.List`1[System.String]" to the array Galaxy
node, which the gateway's COM write rejected/blocked.
Add IReadOnlyList<bool|int|long|float|double|string|DateTimeOffset|DateTime>
cases that call the client package's typed array encoders
(VT_ARRAY|VT_BSTR etc.); List<DateTime> is mapped to DateTimeOffset. Covers
every element type AttributeValueCodec produces.
Writes through the MxGateway data connection (e.g. the Ipsen MoveIn flow
writing MES-receiver attributes) hung ~30s and changed nothing, while reads
of the same attributes worked. Root cause: MXAccess only accepts a write on
an item that holds a SUPERVISORY advise; the write path did AddItem +
WriteBulk with no advise and the monitoring subscription used a plain Advise,
so the worker's synchronous COM Write blocked until the gateway command
timeout. (Plain, non-secured writes need no user/login.) Verified live: with a
supervisory advise the write returns ok in ~22ms; without it it does not.
When the connection has no MXAccess write-user context (WriteUserId == 0) it
now behaves as a supervisory client: every advise defaults to
AdviseSupervisory — both the monitoring subscription (SubscribeAsync) and the
write path — so one connection can read and write. A supervisory advise still
delivers OnDataChange (the worker treats either advice kind as sufficient for
updates) so monitoring is unaffected, and the worker's UnAdvise tears down
either kind, so unsubscribe is unchanged. AdviseSupervisory is issued as a raw
MxCommandKind.AdviseSupervisory via the session's Invoke (the client package
exposes only plain Advise). The advise runs at most once per handle via a
Lazy<Task> so a concurrent first-time subscribe+write on the same new handle
both await the same advise (neither writes before it completes); a faulted
advise is evicted so the next write retries. Dropped on unsubscribe. A
configured non-zero WriteUserId keeps the prior plain-advise behaviour.
Surface native (Galaxy/MxGateway) alarms by their object-relative reference
(e.g. "Z28061.HeartbeatTimeoutAlarm") instead of the gateway's full provider
reference ("Galaxy!<area>.<object>.<alarm>"). The area is already preserved in
Category and the object reference is globally unique within the galaxy, so the
full provider prefix added only noise to the alarm identity operators see.
MxGatewayAlarmMapper.MapTransition/MapSnapshot now set SourceReference from
SourceObjectReference, falling back to AlarmFullReference only when the gateway
omits the object reference. +2 mapper tests; full DCL suite green (158).
OPC UA (RealOpcUaClient):
- Append 5 new SelectClauses at indices 13–17 (never renumber 0–12):
- 13: AlarmConditionType/ActiveState/TransitionTime → OriginalRaiseTime
- 14–17: LimitAlarmType HighHighLimit/HighLimit/LowLimit/LowLowLimit → LimitValue
- New OpcUaAlarmMapper.PickLimitValue helper: first non-null in HiHi→Hi→Lo→LoLo
priority order, InvariantCulture-formatted; empty string for non-limit alarm types.
- HandleAlarmEvent reads new indices with fields.Count > N guards; hard minimum (6)
unchanged so base ConditionType events still process without the limit fields.
- Document unavailable-by-protocol fields (Category, Description, OperatorUser,
CurrentValue) inline in BuildAlarmEventFilter and HandleAlarmEvent.
MxGateway (MxGatewayAlarmMapper):
- MapTransition: CurrentValue and LimitValue now populated via MxValueToString
(uses MxValueExtensions.ToClrValue + InvariantCulture) from OnAlarmTransitionEvent
proto fields current_value/limit_value.
- MapSnapshot: same — populated from ActiveAlarmSnapshot.current_value/limit_value.
- MxValueToString helper (internal): null-safe MxValue → string conversion.
Tests (17 new, 40 total pass):
- OpcUaAlarmMapperTests: PickLimitValue priority, InvariantCulture, all-null case.
- MxGatewayAlarmMapperTests: CurrentValue/LimitValue populate from double/string
MxValue; absent fields yield empty strings.
- RealOpcUaClientAlarmFilterTests: index alignment assertions (count=18, per-index
TypeDefinitionId+BrowsePath), regression guard on existing indices 0–12.
HandleAlarmEvent set AlarmTypeName to the event-type NodeId string ("i=9341"),
but the client-side conditionFilter gate (and the OPC UA WhereClause) use friendly
type names — so a friendly-name filter built a correct server WhereClause yet the
client gate dropped every event (zero alarms delivered). Resolve the event-type
NodeId to its friendly name via an inverse of KnownConditionTypeIds (NodeId-string
fallback for custom types) so both sides agree. Also fix a dead-code ternary in
the SourceName derivation.
conditionFilter was plumbed end-to-end but applied nowhere — a filtered source
silently mirrored all conditions. Define the filter as a comma-separated,
case-insensitive list of condition type names (blank = all); enforce it
authoritatively client-side in DataConnectionActor routing (uniform across OPC UA
+ MxGateway) and, for OPC UA, additionally build a server-side EventFilter
WhereClause as a bandwidth optimization.
Resolve all 622 issues flagged by the enhanced CommentChecker: add missing
<returns> tags (incl. the standard phrasing on non-generic Task methods),
add missing <summary> tags, and replace misused/redundant <inheritdoc/> on
members that override or implement nothing with real documentation.
Documentation-only — no behavior change; solution builds clean.
Adds IAlarmSubscribableConnection to MxGatewayDataConnection (shared session-less
feed, ref-counted), IMxGatewayClient.RunAlarmStreamAsync over the package
StreamAlarmsAsync with internal reconnect, and MxGatewayAlarmMapper
(AlarmFeedMessage/OnAlarmTransitionEvent -> NativeAlarmTransition). Behavior
verified against a live gateway in Task 28; mapper unit-tested.
Adds IAlarmSubscribableConnection to OpcUaDataConnection, IOpcUaClient alarm
subscription methods, and RealOpcUaClient A&C event monitored-item +
EventFilter + ConditionRefresh snapshot, mapping fields via OpcUaAlarmMapper.
Behavior verified against a live A&C server in Task 28; mapper unit-tested.
Expanding a Galaxy object in the tag picker hung on "loading…": the browse
reply inlined every child's full attribute set (~152 KB), exceeding Akka's
128 KB remote frame, and remoting silently discarded the oversized reply.
Browse path (DataConnectionLayer):
- RealMxGatewayClient: navigation now uses BrowseChildren(include_attributes=
false) — child objects only — and an object's own attributes load lazily via
DiscoverHierarchy(root, max_depth=0) when it's expanded. Payload drops from
~152 KB/level to a few KB. Seam contract unchanged.
- DataConnectionActor.CapBrowseChildren: protocol-agnostic byte-budget cap
(~100 KB) on every BrowseNodeResult before it crosses the site→central
frame, OR-ing the adapter's own Truncated flag. Byte budget, not a count —
the only bound that holds regardless of NodeId/attribute-name length.
- RealOpcUaClient: requestedMaxReferencesPerNode 1000 → 500 to narrow the
window before the byte budget applies.
- Graceful gRPC Unimplemented handling → NotSupportedException →
BrowseFailureKind.NotBrowsable with an actionable message (older gateway
builds lacking BrowseChildren).
Picker UI (CentralUI):
- NodeBrowserDialog: modal-lg → modal-xl; new scoped .razor.css caps the tree
at 55vh with its own scrollbar so manual entry + Select/Cancel stay visible.
- Protocol-agnostic failure messages (was hardcoded "OPC UA …"); renamed the
leftover opcua-browser-tree class to node-browser-tree.
Tests: new frame-budget cap test + NotSupported=>NotBrowsable mapping test;
DCL suite 88/88. Doc: Component-DataConnectionLayer.md records the lazy
attribute-light browse and the frame-size guard.
Seam implementation wrapping the gateway client + GalaxyRepositoryClient:
OpenSession/Register, AddItem+Advise subscribe, ReadBulk/WriteBulk with handle
tracking, StreamEvents loop with worker_sequence resume + OPC-style quality
mapping, and Galaxy BrowseChildren mapping (objects keyed by gobject id,
attributes by full tag reference). Only type touching the generated contracts.
Implements IDataConnection + IBrowsableDataConnection over the IMxGatewayClient
seam: connect/disconnect with once-only Disconnected guard + background event
loop, subscribe/unsubscribe with tag routing, read/write batch with per-tag
error classification, WriteBatchAndWait, and Galaxy browse mapping. Covers plan
Tasks 6-10. Full unit coverage via FakeMxGatewayClient (12 tests).