A site health report showed tagResolutionCounts 0/0 for a connection whose
dataConnectionTagQuality on the SAME report read good:2 — reproduced live on
the docker rig against site-a's rig-probe-1 instance (2 Good OPC UA tags on
"OPC PLC Simulator"), on the ACTIVE node's own report.
Not a standby-shadowing or keying/removal problem, and not a serialization
problem: both dictionaries live on one collector instance on one node, and the
CentralControlDtoMapper round-trip is correct in both directions. The actor's
own derived counts (TotalSubscribedTagCount / ResolvedTagCount) were right the
whole time — GetHealthReport replied 2/2.
Root cause: HandleSubscribeCompleted — the path that registers tags on a first,
healthy subscribe — mutated _instancesByTag and _subscriptionIds but never
pushed to ISiteHealthCollector. The only pushes were BecomeConnected's (fires
before any instance subscribes, so its 0/0 is legitimate), the batch apply
(reconnect re-subscribe / resolution probe) and unsubscribe (teardown). A
connection whose tags all resolve first time reaches none of those, and
ScheduleTagResolutionRetry cancels the retry timer outright when nothing is
unresolved — so the connect-time 0/0 was never superseded and stood forever.
The blind spot was therefore worst on a perfectly healthy connection, which is
exactly when the "device still booting / tag path unresolved" diagnostic should
read clean rather than empty. Any reconnect masked it (the batch path pushes),
which is why it presented only on a clean first deploy.
Fix: push the derived counts at the end of the first-subscribe apply, mirroring
the existing push site in HandleBatchSubscribeCompleted. No semantic change to
the null/no-data convention — the map entry already existed, its values were
simply stale zeros.
Tests: fail-before regression test pins the exact mechanism (NSubstitute records
a single UpdateTagResolution(name, 0, 0) pre-fix while the actor reports 2/2).
DCL 320, HealthMonitoring 97, SiteRuntime 605, Communication 717 all green;
slnx builds clean.
Docs: Component-DataConnectionLayer.md said the counts were "derived at report
time", which implies a pull that cannot go stale and papered over this bug.
Corrected to state they are pushed, name the four push sites, and record why a
healthy connection was the worst case.
STATIC tags (no further OnDataChange after advise) depend entirely on the
seed read. Pre-fix HandleSubscribe seeded only on Success && Value != null,
silently dropping a seed that raced the just-created advise (VT_EMPTY) — so a
static tag stayed Uncertain forever while the source read Good. ReSubscribeAll
did no seeding at all, so a static tag could not self-heal across reconnect.
- New SeedTagsAsync helper: per-tag ReadAsync (not a bulk read — some gateways
time out on large batches) with round-based bounded retry
(SeedReadMaxAttempts/SeedReadRetryDelay), logging any tag that never yields a
value (named — previously zero log trace).
- HandleSubscribe seed loop delegates to SeedTagsAsync.
- ReSubscribeAll re-seeds re-advised tags after reconnect via the
generation-guarded TagValueReceived path (fan-out keys off
_subscriptionsByInstance, preserved across reconnect).
Diagnosed live on wonder-app-vd03 2026-06-17 (see scadabridge-dcl-static-tag-false-bad).
Mechanism #2 (single transient-bad push) left as a follow-up.
DataConnectionActor seeded a tag's initial value by Tell-ing TagValueReceived
from HandleSubscribe's background task, which runs BEFORE HandleSubscribeCompleted
registers the instance's tags in _subscriptionsByInstance. HandleTagValueReceived's
fan-out then found no subscriber and dropped the value. A tag that soon gets a
data-change notification recovers, but a STATIC tag (e.g. an idle MES field that
never changes) was left Uncertain forever — the dropped seed was its only value.
Seeds now ride back on SubscribeCompleted and are delivered after registration,
reusing HandleTagValueReceived's generation guard, fan-out and quality accounting.
+1 regression test (DCL026).