fix(alarms): Severity runs one direction, higher = more urgent; raw priority kept (#129)
AlarmConditionState.Severity mixed two conventions: OPC UA rows carried Part 9 Severity (higher = more severe) while MxGateway native alarms and computed alarms carried a raw AVEVA-style priority (1 = most urgent). Every consumer ranks higher as worse, so Worst Severity, the severity filter/sort and the site event-log Error threshold picked the LEAST urgent MxGateway/computed alarms. - AlarmPriorityBands: the OtOpcUa GalaxyAlarmPriority table (lmxopcua#887, b61f3e05), value for value: 1-250 -> 1000, 251-500 -> 750, 501-750 -> 500, 751-999 -> 250; <= 0 clamps to Critical, > 999 to Low. - MxGatewayAlarmMapper bands the gateway severity (= AVEVA priority); AlarmConditionStateFactory.ForComputed bands PriorityLevel. OPC UA unchanged. - AlarmConditionState gains trailing Priority (int?): the raw source number, exactly the pre-#129 Severity. AlarmStateChanged.Priority and the wire AlarmStateUpdate.priority keep that meaning (no proto change); central derives Severity by kind (SeverityFromPriority), so an older site decodes correctly. - ScriptAlarm gains trailing Priority. The native MES 900-999 band and the MES API Severity/MinSeverity/MaxSeverity key off Priority; rig seed scripts moved from a.Severity to a.Priority, so MES output is unchanged. - AlarmActor raise logs Error when the banded severity >= 700 (same threshold as NativeAlarmActor): priority 1-500 Error, 501+ Warning (was raw >= 700). - NativeAlarmActor upgrades pre-#129 native_alarm_state rows on rehydrate. - Debug snapshot decode restores Condition.Priority from the row's priority. - Docs: Commons, DCL, SiteRuntime, Communication, CentralUI, InboundAPI, HighLevelReqs, MES alarm-status plan, CLAUDE.md. Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
@@ -33,7 +33,8 @@ public class MxGatewayAlarmMapperTests
|
||||
Assert.Equal(CommonsTransitionKind.Acknowledge, t.Kind);
|
||||
Assert.True(t.Condition.Active);
|
||||
Assert.True(t.Condition.Acknowledged);
|
||||
Assert.Equal(600, t.Condition.Severity);
|
||||
Assert.Equal(500, t.Condition.Severity); // AVEVA priority 600 = Medium → 500 (#129)
|
||||
Assert.Equal(600, t.Condition.Priority); // raw priority kept
|
||||
Assert.Equal("operator1", t.OperatorUser);
|
||||
Assert.Equal("Tank01", t.SourceObjectReference);
|
||||
}
|
||||
@@ -45,7 +46,8 @@ public class MxGatewayAlarmMapperTests
|
||||
var c = MxGatewayAlarmMapper.MapConditionState(ProtoConditionState.ActiveAcked, severity: 600);
|
||||
Assert.True(c.Active);
|
||||
Assert.True(c.Acknowledged);
|
||||
Assert.Equal(600, c.Severity);
|
||||
Assert.Equal(500, c.Severity);
|
||||
Assert.Equal(600, c.Priority);
|
||||
}
|
||||
|
||||
/// <summary>Verifies that an active, unacknowledged snapshot maps to the snapshot kind.</summary>
|
||||
@@ -58,7 +60,7 @@ public class MxGatewayAlarmMapperTests
|
||||
SourceObjectReference = "Tank01",
|
||||
AlarmTypeName = "AnalogLimitAlarm.Hi",
|
||||
CurrentState = ProtoConditionState.Active,
|
||||
Severity = 1500 // out of range — must clamp
|
||||
Severity = 1500 // out of range — Priority clamps, Severity reads AVEVA Low
|
||||
};
|
||||
|
||||
var t = MxGatewayAlarmMapper.MapSnapshot(snap);
|
||||
@@ -66,7 +68,8 @@ public class MxGatewayAlarmMapperTests
|
||||
Assert.Equal(CommonsTransitionKind.Snapshot, t.Kind);
|
||||
Assert.True(t.Condition.Active);
|
||||
Assert.False(t.Condition.Acknowledged);
|
||||
Assert.Equal(1000, t.Condition.Severity);
|
||||
Assert.Equal(250, t.Condition.Severity);
|
||||
Assert.Equal(1000, t.Condition.Priority);
|
||||
}
|
||||
|
||||
/// <summary>Verifies that the source reference is object-relative rather than the full provider reference.</summary>
|
||||
@@ -334,4 +337,63 @@ public class MxGatewayAlarmMapperTests
|
||||
// The end-of-snapshot sentinel has no condition payload at all.
|
||||
Assert.Null(MxGatewayAlarmMapper.SnapshotComplete().AckTime);
|
||||
}
|
||||
|
||||
// ── Gitea #129: one Severity direction, raw priority kept ──
|
||||
|
||||
/// <summary>
|
||||
/// The gateway's <c>severity</c> field is the AVEVA priority (1 = most urgent). Severity uses OtOpcUa's
|
||||
/// band table (lmxopcua#887), so priority 1 is the MOST severe — on a live transition and a snapshot alike.
|
||||
/// </summary>
|
||||
[Theory]
|
||||
[InlineData(1, 1000)]
|
||||
[InlineData(250, 1000)]
|
||||
[InlineData(251, 750)]
|
||||
[InlineData(500, 750)]
|
||||
[InlineData(501, 500)]
|
||||
[InlineData(750, 500)]
|
||||
[InlineData(751, 250)]
|
||||
[InlineData(999, 250)]
|
||||
[InlineData(0, 1000)]
|
||||
[InlineData(-100, 1000)]
|
||||
[InlineData(1000, 250)]
|
||||
[InlineData(int.MaxValue, 250)]
|
||||
public void Severity_follows_the_AVEVA_priority_bands(int rawPriority, int expectedSeverity)
|
||||
{
|
||||
var live = MxGatewayAlarmMapper.MapTransition(new OnAlarmTransitionEvent
|
||||
{
|
||||
AlarmFullReference = "Galaxy!Area.Tank01.Hi", SourceObjectReference = "Tank01.Hi",
|
||||
TransitionKind = ProtoTransitionKind.Raise, Severity = rawPriority
|
||||
});
|
||||
var snap = MxGatewayAlarmMapper.MapSnapshot(new ActiveAlarmSnapshot
|
||||
{
|
||||
AlarmFullReference = "Galaxy!Area.Tank01.Hi", SourceObjectReference = "Tank01.Hi",
|
||||
CurrentState = ProtoConditionState.Active, Severity = rawPriority
|
||||
});
|
||||
|
||||
Assert.Equal(expectedSeverity, live.Condition.Severity);
|
||||
Assert.Equal(expectedSeverity, snap.Condition.Severity);
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// The MES 900–999 band must select exactly the alarms it selected before #129, which tested the old
|
||||
/// Severity — the gateway value clamped to 0–1000. Priority carries exactly that value for every input.
|
||||
/// </summary>
|
||||
[Fact]
|
||||
public void Priority_is_the_pre_129_Severity_so_the_MES_band_is_unchanged()
|
||||
{
|
||||
foreach (var raw in new[] { int.MinValue, -1, 0, 1, 250, 251, 750, 751, 899, 900, 950, 999, 1000, 1001, 1500, int.MaxValue })
|
||||
{
|
||||
var t = MxGatewayAlarmMapper.MapTransition(new OnAlarmTransitionEvent
|
||||
{
|
||||
AlarmFullReference = "A", SourceObjectReference = "A",
|
||||
TransitionKind = ProtoTransitionKind.Raise, Severity = raw
|
||||
});
|
||||
var preFixSeverity = Math.Clamp(raw, 0, 1000);
|
||||
Assert.Equal(preFixSeverity, t.Condition.Priority);
|
||||
|
||||
var inBandBefore = preFixSeverity is >= 900 and <= 999;
|
||||
var inBandNow = t.Condition.Priority is >= 900 and <= 999;
|
||||
Assert.Equal(inBandBefore, inBandNow);
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
@@ -100,6 +100,7 @@ public class OpcUaAlarmMapperTests
|
||||
Assert.True(c.Active);
|
||||
Assert.False(c.Acknowledged);
|
||||
Assert.Equal(700, c.Severity);
|
||||
Assert.Equal(700, c.Priority); // OPC UA has no separate priority (#129)
|
||||
Assert.Equal(AlarmShelveState.Unshelved, c.Shelve);
|
||||
}
|
||||
|
||||
|
||||
Reference in New Issue
Block a user