fix(alarms): Severity runs one direction, higher = more urgent; raw priority kept (#129)
AlarmConditionState.Severity mixed two conventions: OPC UA rows carried Part 9 Severity (higher = more severe) while MxGateway native alarms and computed alarms carried a raw AVEVA-style priority (1 = most urgent). Every consumer ranks higher as worse, so Worst Severity, the severity filter/sort and the site event-log Error threshold picked the LEAST urgent MxGateway/computed alarms. - AlarmPriorityBands: the OtOpcUa GalaxyAlarmPriority table (lmxopcua#887, b61f3e05), value for value: 1-250 -> 1000, 251-500 -> 750, 501-750 -> 500, 751-999 -> 250; <= 0 clamps to Critical, > 999 to Low. - MxGatewayAlarmMapper bands the gateway severity (= AVEVA priority); AlarmConditionStateFactory.ForComputed bands PriorityLevel. OPC UA unchanged. - AlarmConditionState gains trailing Priority (int?): the raw source number, exactly the pre-#129 Severity. AlarmStateChanged.Priority and the wire AlarmStateUpdate.priority keep that meaning (no proto change); central derives Severity by kind (SeverityFromPriority), so an older site decodes correctly. - ScriptAlarm gains trailing Priority. The native MES 900-999 band and the MES API Severity/MinSeverity/MaxSeverity key off Priority; rig seed scripts moved from a.Severity to a.Priority, so MES output is unchanged. - AlarmActor raise logs Error when the banded severity >= 700 (same threshold as NativeAlarmActor): priority 1-500 Error, 501+ Warning (was raw >= 700). - NativeAlarmActor upgrades pre-#129 native_alarm_state rows on rehydrate. - Debug snapshot decode restores Condition.Priority from the row's priority. - Docs: Commons, DCL, SiteRuntime, Communication, CentralUI, InboundAPI, HighLevelReqs, MES alarm-status plan, CLAUDE.md. Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
@@ -3,6 +3,17 @@ using ZB.MOM.WW.ScadaBridge.Commons.Types.Enums;
|
||||
|
||||
namespace ZB.MOM.WW.ScadaBridge.Commons.Messages.Streaming;
|
||||
|
||||
/// <summary>An alarm's state change, as streamed site → central and kept in the Debug View snapshot.</summary>
|
||||
/// <param name="InstanceUniqueName">The instance the alarm belongs to.</param>
|
||||
/// <param name="AlarmName">The alarm's name (a native condition's source reference).</param>
|
||||
/// <param name="State">Active or Normal.</param>
|
||||
/// <param name="Priority">
|
||||
/// The source's raw number (Gitea #129): the computed alarm's <c>PriorityLevel</c>, the AVEVA priority of an
|
||||
/// MxAccess condition, the Part 9 Severity of an OPC UA condition — i.e. <c>Condition.Priority</c>. This is what
|
||||
/// the stream's <c>AlarmStateUpdate.priority</c> carries (meaning unchanged since before #129). For ranking use
|
||||
/// <see cref="Condition"/>.<see cref="AlarmConditionState.Severity"/>, which is higher = more urgent for every kind.
|
||||
/// </param>
|
||||
/// <param name="Timestamp">When the transition happened.</param>
|
||||
public record AlarmStateChanged(
|
||||
string InstanceUniqueName,
|
||||
string AlarmName,
|
||||
@@ -119,7 +130,7 @@ public record AlarmStateChanged(
|
||||
/// snapshot and on every event it relays to the site stream. For a native condition it is
|
||||
/// the binding-level flag (<c>ResolvedNativeAlarmSource.IsMesReportable</c>, Gitea #59), set by
|
||||
/// the owning <c>NativeAlarmActor</c> — there is still no per-condition config row; the
|
||||
/// 900-999 severity band remains an independent, additive signal. Carried to central on
|
||||
/// 900-999 priority band (on <see cref="Priority"/>, Gitea #129) remains an independent, additive signal. Carried to central on
|
||||
/// <c>AlarmStateUpdate</c> field 25 and <c>DebugAlarmStateDto</c> field 20 (Gitea #60);
|
||||
/// a pre-#60 site sends the proto3 default. Additive; default false.
|
||||
/// </summary>
|
||||
|
||||