fix(alarms): Severity runs one direction, higher = more urgent; raw priority kept (#129)
AlarmConditionState.Severity mixed two conventions: OPC UA rows carried Part 9 Severity (higher = more severe) while MxGateway native alarms and computed alarms carried a raw AVEVA-style priority (1 = most urgent). Every consumer ranks higher as worse, so Worst Severity, the severity filter/sort and the site event-log Error threshold picked the LEAST urgent MxGateway/computed alarms. - AlarmPriorityBands: the OtOpcUa GalaxyAlarmPriority table (lmxopcua#887, b61f3e05), value for value: 1-250 -> 1000, 251-500 -> 750, 501-750 -> 500, 751-999 -> 250; <= 0 clamps to Critical, > 999 to Low. - MxGatewayAlarmMapper bands the gateway severity (= AVEVA priority); AlarmConditionStateFactory.ForComputed bands PriorityLevel. OPC UA unchanged. - AlarmConditionState gains trailing Priority (int?): the raw source number, exactly the pre-#129 Severity. AlarmStateChanged.Priority and the wire AlarmStateUpdate.priority keep that meaning (no proto change); central derives Severity by kind (SeverityFromPriority), so an older site decodes correctly. - ScriptAlarm gains trailing Priority. The native MES 900-999 band and the MES API Severity/MinSeverity/MaxSeverity key off Priority; rig seed scripts moved from a.Severity to a.Priority, so MES output is unchanged. - AlarmActor raise logs Error when the banded severity >= 700 (same threshold as NativeAlarmActor): priority 1-500 Error, 501+ Warning (was raw >= 700). - NativeAlarmActor upgrades pre-#129 native_alarm_state rows on rehydrate. - Debug snapshot decode restores Condition.Priority from the row's priority. - Docs: Commons, DCL, SiteRuntime, Communication, CentralUI, InboundAPI, HighLevelReqs, MES alarm-status plan, CLAUDE.md. Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
@@ -98,7 +98,7 @@ public sealed record AlarmSummaryRow(
|
||||
/// Pure point-in-time roll-up over a set of <see cref="AlarmSummaryRow"/>s.
|
||||
/// </summary>
|
||||
/// <param name="TotalActive">Count of rows whose <see cref="AlarmStateChanged.State"/> is <see cref="AlarmState.Active"/>.</param>
|
||||
/// <param name="WorstSeverity">Highest <see cref="Commons.Types.Alarms.AlarmConditionState.Severity"/> among active rows; 0 when none active.</param>
|
||||
/// <param name="WorstSeverity">Highest <see cref="Commons.Types.Alarms.AlarmConditionState.Severity"/> among active rows — the most urgent, since Severity is higher = more urgent for every kind (Gitea #129); 0 when none active.</param>
|
||||
/// <param name="UnackedCount">Active, unacknowledged native conditions (<c>Kind != Computed</c>).</param>
|
||||
/// <param name="CountsByKind">Per-<see cref="AlarmKind"/> row counts (only kinds with at least one row appear).</param>
|
||||
public sealed record AlarmRollup(
|
||||
|
||||