fix(alarms): Severity runs one direction, higher = more urgent; raw priority kept (#129)

AlarmConditionState.Severity mixed two conventions: OPC UA rows carried Part 9
Severity (higher = more severe) while MxGateway native alarms and computed
alarms carried a raw AVEVA-style priority (1 = most urgent). Every consumer
ranks higher as worse, so Worst Severity, the severity filter/sort and the
site event-log Error threshold picked the LEAST urgent MxGateway/computed
alarms.

- AlarmPriorityBands: the OtOpcUa GalaxyAlarmPriority table (lmxopcua#887,
  b61f3e05), value for value: 1-250 -> 1000, 251-500 -> 750, 501-750 -> 500,
  751-999 -> 250; <= 0 clamps to Critical, > 999 to Low.
- MxGatewayAlarmMapper bands the gateway severity (= AVEVA priority);
  AlarmConditionStateFactory.ForComputed bands PriorityLevel. OPC UA unchanged.
- AlarmConditionState gains trailing Priority (int?): the raw source number,
  exactly the pre-#129 Severity. AlarmStateChanged.Priority and the wire
  AlarmStateUpdate.priority keep that meaning (no proto change); central derives
  Severity by kind (SeverityFromPriority), so an older site decodes correctly.
- ScriptAlarm gains trailing Priority. The native MES 900-999 band and the MES
  API Severity/MinSeverity/MaxSeverity key off Priority; rig seed scripts moved
  from a.Severity to a.Priority, so MES output is unchanged.
- AlarmActor raise logs Error when the banded severity >= 700 (same threshold
  as NativeAlarmActor): priority 1-500 Error, 501+ Warning (was raw >= 700).
- NativeAlarmActor upgrades pre-#129 native_alarm_state rows on rehydrate.
- Debug snapshot decode restores Condition.Priority from the row's priority.
- Docs: Commons, DCL, SiteRuntime, Communication, CentralUI, InboundAPI,
  HighLevelReqs, MES alarm-status plan, CLAUDE.md.

Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
Joseph Doherty
2026-11-12 13:58:28 -05:00
parent e36cd6055e
commit dd4f1c2aa3
39 changed files with 686 additions and 120 deletions
+1 -1
View File
@@ -133,7 +133,7 @@ Sections 3.4 and 3.4.1 describe **computed alarms** — alarms ScadaBridge evalu
Because the source reference typically varies per physical instance (e.g. `Tank01` vs `Tank02`), an instance may **override** a non-locked binding's connection, source reference, and/or condition filter individually — a null override field keeps the inherited value. Bindings cannot be added or removed at the instance level, only retargeted.
**Unified condition model.** Computed and native alarms share one **condition state** so they present uniformly: orthogonal **Active**, **Acknowledged**, **Confirmed** (when confirmable), **Shelved**, and **Suppressed** flags plus a **0–1000 severity**. An **alarm kind** discriminator distinguishes `Computed`, `NativeOpcUa`, and `NativeMxAccess`. Computed alarms project onto this model as auto-acknowledged with severity equal to their priority; native alarms mirror the source condition directly.
**Unified condition model.** Computed and native alarms share one **condition state** so they present uniformly: orthogonal **Active**, **Acknowledged**, **Confirmed** (when confirmable), **Shelved**, and **Suppressed** flags plus a **0–1000 severity** in one direction for every kind — **higher = more urgent** (OPC UA Part 9) — and the source's raw **priority** alongside it. An **alarm kind** discriminator distinguishes `Computed`, `NativeOpcUa`, and `NativeMxAccess`. Computed alarms project onto this model as auto-acknowledged with their priority (lower = more urgent) banded onto severity with AVEVA's default ranges (1–250 → 1000, 251–500 → 750, 501–750 → 500, 751–999 → 250); MxAccess native alarms band their AVEVA priority the same way; OPC UA native alarms mirror the source Severity directly.
**Runtime behavior:**
- Native alarm sources are **discovered and subscribed at runtime** — at deploy time the site subscribes each resolved binding through the Data Connection Layer, which opens **one alarm feed per connection** and routes transitions to instances by source-object reference. A site-side actor (peer to the computed alarm actor) mirrors each source binding.