fix(alarms): Severity runs one direction, higher = more urgent; raw priority kept (#129)
AlarmConditionState.Severity mixed two conventions: OPC UA rows carried Part 9 Severity (higher = more severe) while MxGateway native alarms and computed alarms carried a raw AVEVA-style priority (1 = most urgent). Every consumer ranks higher as worse, so Worst Severity, the severity filter/sort and the site event-log Error threshold picked the LEAST urgent MxGateway/computed alarms. - AlarmPriorityBands: the OtOpcUa GalaxyAlarmPriority table (lmxopcua#887, b61f3e05), value for value: 1-250 -> 1000, 251-500 -> 750, 501-750 -> 500, 751-999 -> 250; <= 0 clamps to Critical, > 999 to Low. - MxGatewayAlarmMapper bands the gateway severity (= AVEVA priority); AlarmConditionStateFactory.ForComputed bands PriorityLevel. OPC UA unchanged. - AlarmConditionState gains trailing Priority (int?): the raw source number, exactly the pre-#129 Severity. AlarmStateChanged.Priority and the wire AlarmStateUpdate.priority keep that meaning (no proto change); central derives Severity by kind (SeverityFromPriority), so an older site decodes correctly. - ScriptAlarm gains trailing Priority. The native MES 900-999 band and the MES API Severity/MinSeverity/MaxSeverity key off Priority; rig seed scripts moved from a.Severity to a.Priority, so MES output is unchanged. - AlarmActor raise logs Error when the banded severity >= 700 (same threshold as NativeAlarmActor): priority 1-500 Error, 501+ Warning (was raw >= 700). - NativeAlarmActor upgrades pre-#129 native_alarm_state rows on rehydrate. - Debug snapshot decode restores Condition.Priority from the row's priority. - Docs: Commons, DCL, SiteRuntime, Communication, CentralUI, InboundAPI, HighLevelReqs, MES alarm-status plan, CLAUDE.md. Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
@@ -477,7 +477,9 @@ The `AlarmStateChanged` message published by both Alarm Actors and Native Alarm
|
||||
- **`Kind`** (`AlarmKind`): `Computed` for ScadaBridge-evaluated alarms; `NativeOpcUa` / `NativeMxAccess` for mirrored native alarms.
|
||||
- **`Condition`** (`AlarmConditionState`): the unified condition view. Computed alarms supply a computed default; native alarms carry the mirrored source condition.
|
||||
- **Native metadata** (populated for native alarms; defaulted/empty for computed): `SourceReference`, `AlarmTypeName`, `Category`, `OperatorUser`, `OperatorComment`, `OriginalRaiseTime`, `CurrentValue`, `LimitValue`.
|
||||
- **Computed-alarm projection**: computed alarms are surfaced as **auto-acknowledged** with `Severity = Priority`, so a single enriched shape carries both computed and native alarms onto the stream and into the DebugView snapshot.
|
||||
- **Computed-alarm projection**: computed alarms are surfaced as **auto-acknowledged** with `Severity` = their priority banded through `AlarmPriorityBands` (AVEVA priority 1–250 → 1000, 251–500 → 750, 501–750 → 500, 751–999 → 250 (`AlarmPriorityBands`, the same table as OtOpcUa `GalaxyAlarmPriority`, lmxopcua#887); Gitea #129 — `PriorityLevel` is lower = more urgent) and `Condition.Priority` = the raw priority, so a single enriched shape carries both computed and native alarms onto the stream and into the DebugView snapshot. `AlarmStateChanged.Priority` is the raw number for every kind (a native row's `Condition.Priority`).
|
||||
- **`alarm` site-event severity**: a raise logs `Error` when its unified `Severity` is ≥ 700 (Critical/High: priority 1–500, or OPC UA Severity ≥ 700), else `Warning` — the same threshold in `AlarmActor` and `NativeAlarmActor`. Before #129 the computed path compared the raw priority, so priority 700+ (the least urgent) logged as `Error`.
|
||||
- **Pre-#129 persisted native rows**: `native_alarm_state.condition_json` written by an older build has the raw number in `Severity` and no `Priority`; `NativeAlarmActor` rehydration moves it to `Priority` and re-derives `Severity` (banded for MxAccess, kept for OPC UA).
|
||||
- **`NativeSourceCanonicalName`** (`string?`): the canonical name of the native alarm source binding a native condition belongs to (e.g. `Motor1.NativeAlarms`). `null` for computed alarms. Stamped by the `NativeAlarmActor` on every emitted event; also carried on idle-binding placeholder rows emitted by the Instance Actor.
|
||||
- **`IsConfiguredPlaceholder`** (`bool`): `true` for a synthetic row emitted by the Instance Actor to represent a configured native source binding that currently has no live conditions. These rows are never persisted or forwarded as operational alarms — they exist solely so the Debug View can render every configured binding as a tree node. `false` on all other rows.
|
||||
- **`AckTime`** (`DateTimeOffset?`): the instant the condition was acknowledged; `null` while unacknowledged, `null` on computed alarms (auto-acked but with no operator ack event), and cleared on re-raise. Stamped by the DCL adapter — the source's own ack instant where the protocol supplies one (OPC UA A&C), the DCL's observation time of the ack transition where it does not (MxAccess Gateway) — and carried verbatim by the `NativeAlarmActor`, which never invents or suppresses one. See [Component-DataConnectionLayer.md](Component-DataConnectionLayer.md) → *Ack Timestamp*.
|
||||
@@ -556,12 +558,12 @@ Available to all script runs and alarm on-trigger runs:
|
||||
|
||||
### Alarm State (read-only)
|
||||
- `Alarms.CurrentAsync()` — Returns a snapshot of the instance's **current** alarm conditions as `IReadOnlyList<ScriptAlarm>` (`Commons.Types.Scripts`), covering computed alarms and mirrored native (OPC UA A&C / MxAccess Gateway) conditions alike. Served by a **local Ask** (`GetAlarmSnapshotRequest`/`GetAlarmSnapshotResponse`) to the script's own Instance Actor — the same mechanism attribute reads use, never a cross-cluster hop.
|
||||
- `Alarms.MesReportableAsync()` — `CurrentAsync()` filtered to rows where `ScriptAlarm.IsMesReportable` is true (2026-09-11). Native alarms carry no per-alarm config row, so they never satisfy the filter — they still convey MES relevance via the 900–999 severity band (see `docs/plans/2026-06-30-mes-alarm-status-api.md`).
|
||||
- `Alarms.MesReportableAsync()` — `CurrentAsync()` filtered to rows where `ScriptAlarm.IsMesReportable` is true (2026-09-11). Native alarms carry no per-alarm config row, so they never satisfy the filter — they still convey MES relevance via the 900–999 **priority** band — tested on `ScriptAlarm.Priority`, never on `Severity` (Gitea #129; see `docs/plans/2026-06-30-mes-alarm-status-api.md`).
|
||||
- Available to **every** script, unlike the `Alarm` global, which exists only inside an on-trigger handler and describes the single alarm that fired. This accessor is what lets an inbound-API-routed `Call` script answer "what is in alarm on this machine right now?"; before it, native mirrored conditions were reachable only from the Debug View.
|
||||
- **Read-only by design** — native alarms are a read-only mirror of the source (no ack-back), so the accessor exposes no acknowledge/shelve operation.
|
||||
- **Not scope-prefixed**, unlike `Attributes`: alarm identity is not a scope-relative attribute name (computed alarms are keyed by configured name, native conditions by a source-supplied reference), so every scope sees the same list rather than a silently truncated one.
|
||||
- The snapshot is built by the same `BuildAlarmStatesSnapshot()` the Debug View uses, so it **includes placeholder rows** for configured-but-quiet native source bindings (`IsConfiguredPlaceholder`). Callers enumerating real alarms filter on `Active && !IsConfiguredPlaceholder`.
|
||||
- `ScriptAlarm` is a flat projection of the retained `AlarmStateChanged`: `Name`, `SourceReference`, `NativeSourceCanonicalName`, `Active`, `Acknowledged`, `Confirmed?`, `Shelved` (all shelve sub-states collapse to one boolean), `Suppressed`, `Severity` (0–1000), `Kind`, `Message`, `AlarmTypeName`, `Category`, `OperatorUser`, `OperatorComment`, `OriginalRaiseTime?`, `Timestamp`, `AckTime?`, `CurrentValue`, `LimitValue`, `IsConfiguredPlaceholder`, `IsMesReportable` (trailing, 2026-09-11 — always `false` on native rows). The `Condition` is the authority for active/acked/severity, so computed and native alarms read identically from one filter expression.
|
||||
- `ScriptAlarm` is a flat projection of the retained `AlarmStateChanged`: `Name`, `SourceReference`, `NativeSourceCanonicalName`, `Active`, `Acknowledged`, `Confirmed?`, `Shelved` (all shelve sub-states collapse to one boolean), `Suppressed`, `Severity` (0–1000, higher = more urgent for every kind — Gitea #129), `Kind`, `Message`, `AlarmTypeName`, `Category`, `OperatorUser`, `OperatorComment`, `OriginalRaiseTime?`, `Timestamp`, `AckTime?`, `CurrentValue`, `LimitValue`, `IsConfiguredPlaceholder`, `IsMesReportable` (trailing, 2026-09-11 — always `false` on native rows), `Priority` (trailing, Gitea #129 — the raw source number: AVEVA priority for MxAccess, `PriorityLevel` for computed, Part 9 Severity for OPC UA; the pre-#129 `Severity` value, which the MES 900–999 band and the MES API's `Severity`/`MinSeverity`/`MaxSeverity` read). The `Condition` is the authority for active/acked/severity, so computed and native alarms read identically from one filter expression.
|
||||
- **`IsMesReportable` is stamped at two points.** `InstanceActor.BuildAlarmStatesSnapshot()` sets `AlarmStateChanged.IsMesReportable` from `ResolvedAlarm.IsMesReportable` on every row it produces — retained (fired/active) rows and the fallback/idle rows alike — and `InstanceActor.HandleAlarmStateChanged` stamps the Alarm Actor's own live events before storing and publishing them, so `Alarms.CurrentAsync()`/`MesReportableAsync()`, the Debug View snapshot and the live stream always agree. Since ScadaBridge#60 the flag rides the wire as `AlarmStateUpdate.is_mes_reportable` (25) and `DebugAlarmStateDto.is_mes_reportable` (20); `DebugAlarmStateDto` also carries `ack_time` (21, ScadaBridge#84). Both are additive — an older peer reads `false`/null.
|
||||
- The type lives in Commons so the runtime accessor and the Script Analysis compile-only surface (`ScriptCompileSurface.CompileAlarmsAccessor`) project to the **same** type — a script binding at the design-time gate binds identically at the site. Parity is pinned by `CompileSurfaceParityTests`.
|
||||
- Design record: `docs/plans/2026-06-30-mes-alarm-status-api.md` §5.2.
|
||||
|
||||