fix(alarms): Severity runs one direction, higher = more urgent; raw priority kept (#129)
AlarmConditionState.Severity mixed two conventions: OPC UA rows carried Part 9 Severity (higher = more severe) while MxGateway native alarms and computed alarms carried a raw AVEVA-style priority (1 = most urgent). Every consumer ranks higher as worse, so Worst Severity, the severity filter/sort and the site event-log Error threshold picked the LEAST urgent MxGateway/computed alarms. - AlarmPriorityBands: the OtOpcUa GalaxyAlarmPriority table (lmxopcua#887, b61f3e05), value for value: 1-250 -> 1000, 251-500 -> 750, 501-750 -> 500, 751-999 -> 250; <= 0 clamps to Critical, > 999 to Low. - MxGatewayAlarmMapper bands the gateway severity (= AVEVA priority); AlarmConditionStateFactory.ForComputed bands PriorityLevel. OPC UA unchanged. - AlarmConditionState gains trailing Priority (int?): the raw source number, exactly the pre-#129 Severity. AlarmStateChanged.Priority and the wire AlarmStateUpdate.priority keep that meaning (no proto change); central derives Severity by kind (SeverityFromPriority), so an older site decodes correctly. - ScriptAlarm gains trailing Priority. The native MES 900-999 band and the MES API Severity/MinSeverity/MaxSeverity key off Priority; rig seed scripts moved from a.Severity to a.Priority, so MES output is unchanged. - AlarmActor raise logs Error when the banded severity >= 700 (same threshold as NativeAlarmActor): priority 1-500 Error, 501+ Warning (was raw >= 700). - NativeAlarmActor upgrades pre-#129 native_alarm_state rows on rehydrate. - Debug snapshot decode restores Condition.Priority from the row's priority. - Docs: Commons, DCL, SiteRuntime, Communication, CentralUI, InboundAPI, HighLevelReqs, MES alarm-status plan, CLAUDE.md. Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
@@ -355,7 +355,9 @@ All defined in Commons so the feed is identical across protocols:
|
||||
| Type | Shape |
|
||||
|------|-------|
|
||||
| `NativeAlarmTransition` | `SourceReference`, `SourceObjectReference`, `AlarmTypeName`, `Kind`, `Condition`, `Category`, `Description`, `Message`, `OperatorUser`, `OperatorComment`, `OriginalRaiseTime?`, `TransitionTime`, `CurrentValue`, `LimitValue`, `AckTime?` |
|
||||
| `AlarmConditionState` | `Active`, `Acknowledged`, `Confirmed?` (null when not confirmable), `Shelve`, `Suppressed`, `Severity` (0–1000) |
|
||||
| `AlarmConditionState` | `Active`, `Acknowledged`, `Confirmed?` (null when not confirmable), `Shelve`, `Suppressed`, `Severity` (0–1000, higher = more urgent), `Priority?` (raw source number) |
|
||||
|
||||
**Severity direction (Gitea #129).** `Severity` is OPC UA Part 9 direction for both adapters. `OpcUaAlarmMapper` clamps the server's Severity to 0–1000 and repeats it as `Priority`. `MxGatewayAlarmMapper` reads the gateway's `severity` field — which mxaccessgw fills from the AVEVA alarm **priority** (1 = most urgent) — bands it onto `Severity` (AVEVA priority 1–250 → 1000, 251–500 → 750, 501–750 → 500, 751–999 → 250 (`AlarmPriorityBands`, the same table as OtOpcUa `GalaxyAlarmPriority`, lmxopcua#887); out-of-range clamps: ≤ 0 → 1000, > 999 → 250) and keeps it on `Priority` clamped to 0–1000, i.e. the value `Severity` carried before #129. A Galaxy alarm therefore reads the same `Severity` through OtOpcUa and straight from the gateway.
|
||||
| `AlarmTransitionKind` (enum) | `Snapshot`, `SnapshotComplete`, `Raise`, `Acknowledge`, `Clear`, `Retrigger`, `StateChange`, `SnapshotStart` (appended) |
|
||||
|
||||
`OperatorUser` / `OperatorComment` and `CurrentValue` / `LimitValue` are display-only mirrors from the source.
|
||||
|
||||