fix(alarms): Severity runs one direction, higher = more urgent; raw priority kept (#129)

AlarmConditionState.Severity mixed two conventions: OPC UA rows carried Part 9
Severity (higher = more severe) while MxGateway native alarms and computed
alarms carried a raw AVEVA-style priority (1 = most urgent). Every consumer
ranks higher as worse, so Worst Severity, the severity filter/sort and the
site event-log Error threshold picked the LEAST urgent MxGateway/computed
alarms.

- AlarmPriorityBands: the OtOpcUa GalaxyAlarmPriority table (lmxopcua#887,
  b61f3e05), value for value: 1-250 -> 1000, 251-500 -> 750, 501-750 -> 500,
  751-999 -> 250; <= 0 clamps to Critical, > 999 to Low.
- MxGatewayAlarmMapper bands the gateway severity (= AVEVA priority);
  AlarmConditionStateFactory.ForComputed bands PriorityLevel. OPC UA unchanged.
- AlarmConditionState gains trailing Priority (int?): the raw source number,
  exactly the pre-#129 Severity. AlarmStateChanged.Priority and the wire
  AlarmStateUpdate.priority keep that meaning (no proto change); central derives
  Severity by kind (SeverityFromPriority), so an older site decodes correctly.
- ScriptAlarm gains trailing Priority. The native MES 900-999 band and the MES
  API Severity/MinSeverity/MaxSeverity key off Priority; rig seed scripts moved
  from a.Severity to a.Priority, so MES output is unchanged.
- AlarmActor raise logs Error when the banded severity >= 700 (same threshold
  as NativeAlarmActor): priority 1-500 Error, 501+ Warning (was raw >= 700).
- NativeAlarmActor upgrades pre-#129 native_alarm_state rows on rehydrate.
- Debug snapshot decode restores Condition.Priority from the row's priority.
- Docs: Commons, DCL, SiteRuntime, Communication, CentralUI, InboundAPI,
  HighLevelReqs, MES alarm-status plan, CLAUDE.md.

Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
Joseph Doherty
2026-11-12 13:58:28 -05:00
parent e36cd6055e
commit dd4f1c2aa3
39 changed files with 686 additions and 120 deletions
+1 -1
View File
@@ -236,7 +236,7 @@ Both enriched `AlarmStateChanged` events (live, via the gRPC stream) and the ini
Per-leaf alarm rendering (leaf nodes are individual conditions for native alarms, and the alarm itself for computed alarms):
- **Kind badge** — distinguishes **Computed** alarms from native ones (**OPC UA** or **MxAccess**), driven by the event's `AlarmKind` discriminator.
- **Sev** — the unified **0–1000 severity** (`AlarmConditionState.Severity`). Computed rows surface their integer priority on the same scale.
- **Sev** — the unified **0–1000 severity** (`AlarmConditionState.Severity`), **higher = more urgent for every kind** (Gitea #129). OPC UA rows show their Part 9 Severity; MxAccess and computed rows show their priority banded: AVEVA priority 1–250 → 1000, 251–500 → 750, 501–750 → 500, 751–999 → 250 (`AlarmPriorityBands`, the same table as OtOpcUa `GalaxyAlarmPriority`, lmxopcua#887). The Alarm Summary's worst-severity tile (max), severity-threshold filter (`>=`) and severity sort (descending default) all read this one direction. The raw priority stays on `AlarmConditionState.Priority` / `AlarmStateChanged.Priority`.
- **Source reference subtitle** — for native rows, the `SourceReference` (e.g. `Tank01.Level.HiHi`) renders as a monospace subtitle. Computed rows have no subtitle.
- **State badges** — orthogonal condition sub-states: **Unacked**, **Shelved**, and **Suppressed** appear only when the corresponding `AlarmConditionState` flag is set. Computed alarms are auto-acked and never shelved/suppressed.
- **Row tooltip** — surfaces native metadata not warranting its own column: `AlarmTypeName`, category, operator user and comment, original raise time, current/limit value.