fix(alarms): Severity runs one direction, higher = more urgent; raw priority kept (#129)
AlarmConditionState.Severity mixed two conventions: OPC UA rows carried Part 9 Severity (higher = more severe) while MxGateway native alarms and computed alarms carried a raw AVEVA-style priority (1 = most urgent). Every consumer ranks higher as worse, so Worst Severity, the severity filter/sort and the site event-log Error threshold picked the LEAST urgent MxGateway/computed alarms. - AlarmPriorityBands: the OtOpcUa GalaxyAlarmPriority table (lmxopcua#887, b61f3e05), value for value: 1-250 -> 1000, 251-500 -> 750, 501-750 -> 500, 751-999 -> 250; <= 0 clamps to Critical, > 999 to Low. - MxGatewayAlarmMapper bands the gateway severity (= AVEVA priority); AlarmConditionStateFactory.ForComputed bands PriorityLevel. OPC UA unchanged. - AlarmConditionState gains trailing Priority (int?): the raw source number, exactly the pre-#129 Severity. AlarmStateChanged.Priority and the wire AlarmStateUpdate.priority keep that meaning (no proto change); central derives Severity by kind (SeverityFromPriority), so an older site decodes correctly. - ScriptAlarm gains trailing Priority. The native MES 900-999 band and the MES API Severity/MinSeverity/MaxSeverity key off Priority; rig seed scripts moved from a.Severity to a.Priority, so MES output is unchanged. - AlarmActor raise logs Error when the banded severity >= 700 (same threshold as NativeAlarmActor): priority 1-500 Error, 501+ Warning (was raw >= 700). - NativeAlarmActor upgrades pre-#129 native_alarm_state rows on rehydrate. - Debug snapshot decode restores Condition.Priority from the row's priority. - Docs: Commons, DCL, SiteRuntime, Communication, CentralUI, InboundAPI, HighLevelReqs, MES alarm-status plan, CLAUDE.md. Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
@@ -164,8 +164,10 @@ The override **routes left vs right off the SAPID suffix** — `_A` ⇒ Left, `_
|
||||
|
||||
```csharp
|
||||
// CvdReactor.SimpleAlarmStatus (sketch)
|
||||
// Q1 DECIDED: MES relevance = dedicated severity band. Galaxy alarm priorities for
|
||||
// Q1 DECIDED: MES relevance = dedicated band. Galaxy alarm priorities for
|
||||
// MES-relevant alarms are configured into 900-999; nothing else may use that band.
|
||||
// Gitea #129: the band is the RAW priority, ScriptAlarm.Priority. ScriptAlarm.Severity is
|
||||
// banded (higher = more urgent) since #129 and never lands in 900-999 for these alarms.
|
||||
const int MesBandMin = 900;
|
||||
const int MesBandMax = 999;
|
||||
try {
|
||||
@@ -189,13 +191,13 @@ try {
|
||||
.Where(a => a.Active && !a.IsConfiguredPlaceholder) // only triggered
|
||||
.Where(a => InScope(a.NativeSourceCanonicalName)) // _A => Left*, _B => Right*, + ReactorAlarms
|
||||
// SimpleAlarmStatus semantics: flagged-only (= MES band, Q1) + acked always included
|
||||
.Where(a => a.Severity >= MesBandMin && a.Severity <= MesBandMax)
|
||||
.Where(a => a.Priority >= MesBandMin && a.Priority <= MesBandMax)
|
||||
.Select(a => new {
|
||||
Name = a.Name,
|
||||
HierarchicalName = code + "." + a.Name,
|
||||
Description = string.IsNullOrEmpty(a.Message) ? a.AlarmTypeName : a.Message, // Q3 DECIDED
|
||||
IsFlaggedForMES = a.Severity >= MesBandMin && a.Severity <= MesBandMax, // Q1 DECIDED: real predicate
|
||||
Severity = a.Severity,
|
||||
IsFlaggedForMES = a.Priority >= MesBandMin && a.Priority <= MesBandMax, // Q1 DECIDED: real predicate
|
||||
Severity = a.Priority, // MES Severity = raw 0-999 priority (#129)
|
||||
StatusCode = a.Acknowledged ? "Triggered.Acked" : "Triggered",
|
||||
TriggeredDT = (a.OriginalRaiseTime ?? a.Timestamp),
|
||||
AckDT = a.AckTime, // Q4 DECIDED: enriched mirror
|
||||
@@ -214,7 +216,7 @@ try {
|
||||
|
||||
## 6. Key design decisions — ALL DECIDED 2026-08-01 (design review with user)
|
||||
|
||||
1. **Superseded for COMPUTED alarms 2026-09-11** by `2026-09-11-mes-reportable-alarm-flag-design.md` — still the rule for native alarms. **`IsFlaggedForMES` for native alarms — DECIDED: severity band.** MES relevance is encoded in the alarm severity itself: MES-relevant alarms are configured (in the Galaxy alarm priority) into a **dedicated band 900–999** reserved exclusively for MES-relevant alarms, so it cannot collide with ordinary criticality tuning. Scripts carry `MesBandMin = 900` / `MesBandMax = 999` as named constants; `IsFlaggedForMES = (Severity in band)` is reported honestly per row; `SimpleAlarmStatus` (always flagged-only) and `AlarmStatus` with `FlaggedOnly=true` filter by the band predicate. Since `Severity` is returned verbatim, MES's own `MinSeverity`/`MaxSeverity` filters compose naturally with the band. No new tables, code flags, or allow-lists. **Operational prerequisite:** the Galaxy alarm priorities for MES-relevant CvdReactor alarms must be set into 900–999 before the endpoints are meaningful.
|
||||
1. **Superseded for COMPUTED alarms 2026-09-11** by `2026-09-11-mes-reportable-alarm-flag-design.md` — still the rule for native alarms. **`IsFlaggedForMES` for native alarms — DECIDED: severity band.** MES relevance is encoded in the alarm severity itself: MES-relevant alarms are configured (in the Galaxy alarm priority) into a **dedicated band 900–999** reserved exclusively for MES-relevant alarms, so it cannot collide with ordinary criticality tuning. Scripts carry `MesBandMin = 900` / `MesBandMax = 999` as named constants; `IsFlaggedForMES = (Priority in band)` is reported honestly per row (**Gitea #129, 2026-11-12:** the band and the MES `Severity` field read `ScriptAlarm.Priority`, the raw priority — `ScriptAlarm.Severity` is now the banded, higher-is-more-urgent severity; deployed scripts that test `a.Severity` must switch to `a.Priority`); `SimpleAlarmStatus` (always flagged-only) and `AlarmStatus` with `FlaggedOnly=true` filter by the band predicate. Since `Severity` is returned verbatim, MES's own `MinSeverity`/`MaxSeverity` filters compose naturally with the band. No new tables, code flags, or allow-lists. **Operational prerequisite:** the Galaxy alarm priorities for MES-relevant CvdReactor alarms must be set into 900–999 before the endpoints are meaningful.
|
||||
|
||||
2. **MESReceiver version — DECIDED: dropped entirely.** With no native alarm sources there is no live state; a config-only catalog answer was judged not worth shipping. Only CvdReactor implements the scripts; other machines get the router's clean "not supported on machine" error (§5.1). No BTDB `MachineAlarm` dependency remains.
|
||||
|
||||
|
||||