fix(dcl): MxGateway adapter treats a graceful end of the event stream as a disconnect — a dashboard 'close session' (or graceful gateway shutdown) completes the stream with OK, leaving the adapter Connected on a dead session: values frozen at last GOOD quality, every write 'Session … was not found' until restart (QA vq03 Z28061 MoveIn, 2026-08-20). Pinned: signals once while connected, silent for superseded loops / own teardown
This commit is contained in:
@@ -80,7 +80,7 @@ All protocols produce the same value tuple consumed by Instance Actors. Before t
|
|||||||
- Session-based: `OpenSession` + `Register` on connect; `AddItem` + `Advise` per subscription; value changes arrive on the gateway's server-streaming event feed (`StreamEvents`), resumable via `worker_sequence`.
|
- Session-based: `OpenSession` + `Register` on connect; `AddItem` + `Advise` per subscription; value changes arrive on the gateway's server-streaming event feed (`StreamEvents`), resumable via `worker_sequence`.
|
||||||
- Read/Write via `ReadBulk` / `WriteBulk`; writes carry a configurable `WriteUserId`. Quality maps the OPC-style quality byte (≥192 Good, ≥64 Uncertain, else Bad), with a failing MXAccess status proxy treated as Bad.
|
- Read/Write via `ReadBulk` / `WriteBulk`; writes carry a configurable `WriteUserId`. Quality maps the OPC-style quality byte (≥192 Good, ≥64 Uncertain, else Bad), with a failing MXAccess status proxy treated as Bad.
|
||||||
- Galaxy hierarchy browse via the separate `GalaxyRepositoryClient` — objects are navigable nodes (keyed by Galaxy gobject id), attributes are selectable leaves (keyed by full tag reference). Browse is **lazy and attribute-light**: navigation uses `BrowseChildren` with `include_attributes=false` (child objects only), and an object's own attributes are fetched only when it is expanded, via `DiscoverHierarchy(root=<object>, max_depth=0)` scoped to that single object. This keeps each browse level's reply small; inlining every child's full attribute set could exceed the Akka remote frame and silently drop the reply.
|
- Galaxy hierarchy browse via the separate `GalaxyRepositoryClient` — objects are navigable nodes (keyed by Galaxy gobject id), attributes are selectable leaves (keyed by full tag reference). Browse is **lazy and attribute-light**: navigation uses `BrowseChildren` with `include_attributes=false` (child objects only), and an object's own attributes are fetched only when it is expanded, via `DiscoverHierarchy(root=<object>, max_depth=0)` scoped to that single object. This keeps each browse level's reply small; inlining every child's full attribute set could exceed the Akka remote frame and silently drop the reply.
|
||||||
- Disconnect detection: a fault on the event stream raises `IDataConnection.Disconnected`, driving the same reconnection state machine as OPC UA.
|
- Disconnect detection: a fault on the event stream raises `IDataConnection.Disconnected`, driving the same reconnection state machine as OPC UA. **A graceful (OK-status) end of the event stream while the adapter did not cancel it is ALSO a disconnect** (fix 2026-08-20): the gateway completes a session's subscriber channels with no error when the session is closed from its dashboard or on a graceful gateway shutdown (`CompleteAllSubscribers(error: null)`), so before the fix `RunEventLoopAsync` simply returned, the adapter stayed `Connected`, subscribed values froze at their last GOOD quality and every write failed with `Session … was not found` until a process restart (QA incident, vq03 Z28061 MoveIn, one hour of silent loss; the 10-second `NotFound` heartbeat in the logs was the unresolved-tag resolution probe re-subscribing on the dead session). Same bug class as the gRPC site-stream client's graceful-completion reconnect. Pinned by `MxGatewayDataConnectionReconnectTests.EventStreamGracefulCompletion_*` (signals once while connected; silent for a superseded loop and after our own `DisconnectAsync`). Follow-up for the gateway SDK: `NotFound` maps to a generic `MxGatewayException` with only the detail text, so a write/subscribe hitting a dead session cannot be classified as a session loss without string matching — a typed session-not-found exception would allow a second, reactive detection layer.
|
||||||
- Implemented as `MxGatewayDataConnection` over an `IMxGatewayClient` seam; the seam is decoupled from the generated gRPC types (only `RealMxGatewayClient` references them), so the adapter is fully unit-testable with a fake.
|
- Implemented as `MxGatewayDataConnection` over an `IMxGatewayClient` seam; the seam is decoupled from the generated gRPC types (only `RealMxGatewayClient` references them), so the adapter is fully unit-testable with a fake.
|
||||||
|
|
||||||
## Endpoint Redundancy
|
## Endpoint Redundancy
|
||||||
|
|||||||
@@ -182,6 +182,23 @@ public class MxGatewayDataConnection
|
|||||||
if (_tagToSub.TryGetValue(update.TagPath, out var subId) && _subs.TryGetValue(subId, out var s))
|
if (_tagToSub.TryGetValue(update.TagPath, out var subId) && _subs.TryGetValue(subId, out var s))
|
||||||
s.Callback(update.TagPath, new TagValue(update.Value, update.Quality, update.Timestamp));
|
s.Callback(update.TagPath, new TagValue(update.Value, update.Quality, update.Timestamp));
|
||||||
}, ct);
|
}, ct);
|
||||||
|
|
||||||
|
// A GRACEFUL end of the event stream (OK status, no fault) while we did not ask
|
||||||
|
// for it means the gateway closed the session underneath us — a dashboard
|
||||||
|
// "close session", or a graceful gateway shutdown, both complete the per-session
|
||||||
|
// subscriber channels with no error (CompleteAllSubscribers(error: null)).
|
||||||
|
// Before this branch existed the loop simply returned: the adapter stayed
|
||||||
|
// Connected, every subscribed value froze at its last GOOD quality, and every
|
||||||
|
// write hit the dead session ("Session … was not found") until a process
|
||||||
|
// restart — QA incident 2026-08-20, vq03 Z28061 MoveIn, one hour of silent loss.
|
||||||
|
// Same bug class as SiteStreamGrpcClient's graceful-completion reconnect
|
||||||
|
// (commit 34a3f4bb). A cancelled token is our own teardown, never a disconnect.
|
||||||
|
if (!ct.IsCancellationRequested)
|
||||||
|
{
|
||||||
|
_logger.LogWarning(
|
||||||
|
"MxGateway event stream ended without a fault while connected — the gateway closed the session; signalling disconnect");
|
||||||
|
RaiseDisconnected();
|
||||||
|
}
|
||||||
}
|
}
|
||||||
catch (OperationCanceledException)
|
catch (OperationCanceledException)
|
||||||
{
|
{
|
||||||
|
|||||||
+63
@@ -1,6 +1,8 @@
|
|||||||
|
using ZB.MOM.WW.ScadaBridge.Commons.Types.Enums;
|
||||||
using Grpc.Core;
|
using Grpc.Core;
|
||||||
using Microsoft.Extensions.Logging.Abstractions;
|
using Microsoft.Extensions.Logging.Abstractions;
|
||||||
using NSubstitute;
|
using NSubstitute;
|
||||||
|
|
||||||
using ZB.MOM.WW.ScadaBridge.DataConnectionLayer.Adapters;
|
using ZB.MOM.WW.ScadaBridge.DataConnectionLayer.Adapters;
|
||||||
|
|
||||||
namespace ZB.MOM.WW.ScadaBridge.DataConnectionLayer.Tests.Adapters;
|
namespace ZB.MOM.WW.ScadaBridge.DataConnectionLayer.Tests.Adapters;
|
||||||
@@ -93,6 +95,67 @@ public class MxGatewayDataConnectionReconnectTests
|
|||||||
Assert.Equal(0, Volatile.Read(ref disconnectsRef.Value));
|
Assert.Equal(0, Volatile.Read(ref disconnectsRef.Value));
|
||||||
}
|
}
|
||||||
|
|
||||||
|
|
||||||
|
/// <summary>
|
||||||
|
/// QA incident 2026-08-20 (vq03 Z28061 MoveIn): an operator closed ScadaBridge's session
|
||||||
|
/// from the MxAccess Gateway dashboard. The gateway completes the session's event stream
|
||||||
|
/// GRACEFULLY (<c>CompleteAllSubscribers(error: null)</c>, OK status) — the same path a
|
||||||
|
/// graceful gateway shutdown takes — so <c>RunEventLoopAsync</c> returned normally and the
|
||||||
|
/// adapter never raised <c>Disconnected</c>: values froze at their last GOOD quality and
|
||||||
|
/// every write went to the dead session (<c>Session … was not found</c>) for an hour, until
|
||||||
|
/// a process restart. A non-cancelled end of the event stream IS a disconnect.
|
||||||
|
/// </summary>
|
||||||
|
[Fact]
|
||||||
|
public async Task EventStreamGracefulCompletion_WhileConnected_SignalsDisconnected()
|
||||||
|
{
|
||||||
|
var loops = new List<TaskCompletionSource>();
|
||||||
|
var loopTokens = new List<CancellationToken>();
|
||||||
|
var adapter = CreateAdapterWithControllableLoops(loops, loopTokens, out var disconnectsRef);
|
||||||
|
var details = new Dictionary<string, string> { ["Endpoint"] = "http://gw:5000", ["ApiKey"] = "k" };
|
||||||
|
|
||||||
|
await adapter.ConnectAsync(details);
|
||||||
|
await WaitUntilAsync(() => loopTokens.Count == 1);
|
||||||
|
|
||||||
|
loops[0].SetResult(); // server ended the stream with OK — session closed underneath us
|
||||||
|
await WaitUntilAsync(() => Volatile.Read(ref disconnectsRef.Value) == 1);
|
||||||
|
Assert.Equal(ConnectionHealth.Disconnected, adapter.Status);
|
||||||
|
}
|
||||||
|
|
||||||
|
[Fact]
|
||||||
|
public async Task EventStreamGracefulCompletion_OfSupersededLoop_DoesNotSignalDisconnected()
|
||||||
|
{
|
||||||
|
var loops = new List<TaskCompletionSource>();
|
||||||
|
var loopTokens = new List<CancellationToken>();
|
||||||
|
var adapter = CreateAdapterWithControllableLoops(loops, loopTokens, out var disconnectsRef);
|
||||||
|
var details = new Dictionary<string, string> { ["Endpoint"] = "http://gw:5000", ["ApiKey"] = "k" };
|
||||||
|
|
||||||
|
await adapter.ConnectAsync(details);
|
||||||
|
await WaitUntilAsync(() => loopTokens.Count == 1);
|
||||||
|
await adapter.ConnectAsync(details); // reconnect: loop #0 is cancelled
|
||||||
|
await WaitUntilAsync(() => loopTokens.Count == 2);
|
||||||
|
|
||||||
|
loops[0].SetResult(); // the OLD loop winds down normally after its cancel
|
||||||
|
await Task.Delay(200);
|
||||||
|
Assert.Equal(0, Volatile.Read(ref disconnectsRef.Value)); // must not flap the new session
|
||||||
|
}
|
||||||
|
|
||||||
|
[Fact]
|
||||||
|
public async Task EventStreamGracefulCompletion_AfterDisconnectAsync_DoesNotSignalDisconnected()
|
||||||
|
{
|
||||||
|
var loops = new List<TaskCompletionSource>();
|
||||||
|
var loopTokens = new List<CancellationToken>();
|
||||||
|
var adapter = CreateAdapterWithControllableLoops(loops, loopTokens, out var disconnectsRef);
|
||||||
|
var details = new Dictionary<string, string> { ["Endpoint"] = "http://gw:5000", ["ApiKey"] = "k" };
|
||||||
|
|
||||||
|
await adapter.ConnectAsync(details);
|
||||||
|
await WaitUntilAsync(() => loopTokens.Count == 1);
|
||||||
|
await adapter.DisconnectAsync(); // our own teardown cancels the loop
|
||||||
|
|
||||||
|
loops[0].SetResult();
|
||||||
|
await Task.Delay(200);
|
||||||
|
Assert.Equal(0, Volatile.Read(ref disconnectsRef.Value));
|
||||||
|
}
|
||||||
|
|
||||||
private sealed class IntRef { public int Value; }
|
private sealed class IntRef { public int Value; }
|
||||||
|
|
||||||
private static MxGatewayDataConnection CreateAdapterWithControllableLoops(
|
private static MxGatewayDataConnection CreateAdapterWithControllableLoops(
|
||||||
|
|||||||
Reference in New Issue