feat(dcl): ServiceLevel-aware OPC UA failover for primary/backup pairs (#138)
Prerequisite for OtOpcUa Warm redundancy (lmxopcua#717): a Warm standby keeps a
healthy session but serves BadOutOfService at a standby ServiceLevel (90/50, boot 1),
so a connection that lands there sat on Bad quality forever.
- OPC UA connections with a backup poll Server_ServiceLevel (i=2267) on the connected
endpoint (IServiceLevelReadable, implemented by OpcUaDataConnection; never raises
Disconnected). A level < 200 sustained for the degraded window (default 10 s), or
the first sample after any (re)connect, triggers a probe of the other endpoint
(short-lived session: connect, read, dispose). Switch only when it reports a
Healthy (>= 200) higher level, and not within the minimum dwell (default 60 s) of
the previous ServiceLevel switch. Both degraded, other unreachable or level
unknown: stay put. 250/240 (today's OtOpcUa) never starts a streak.
- The switch reuses the failover path: SwitchToOtherEndpoint() now shared by all
three triggers, then BecomeReconnecting(ReconnectCause.ServiceLevelFailover) -
zero delay, no unstable accounting, ReSubscribeAll on the new endpoint.
- Config: OpcUaEndpointConfig.ServiceLevelFailover {enabled, degradedWindowSeconds,
minDwellSeconds}, read from the PRIMARY endpoint's JSON only; null = defaults
(enabled, 10, 60). Inside the encrypted protocol JSON, so no schema change or
migration. Central UI: fields in the Backup card next to Failover Retry Count.
Global: ScadaBridge:DataConnection:ServiceLevelPollInterval (2 s) and
ServiceLevelProbeTimeout (15 s).
- Tests: actor tests per trigger/non-trigger with positive controls, an unsolicited
promotion RefreshStart/RefreshEnd test at client and actor level, adapter tests,
and a real in-process OPC UA server pair end to end. All 15 mutants killed.
- Docs: Component-DataConnectionLayer, components/DataConnectionLayer, Component-CLI.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
This commit is contained in:
@@ -0,0 +1,22 @@
|
||||
namespace ZB.MOM.WW.ScadaBridge.Commons.Interfaces.Protocol;
|
||||
|
||||
/// <summary>
|
||||
/// Optional capability for an <see cref="IDataConnection"/> whose server publishes a redundancy
|
||||
/// ServiceLevel (OPC UA <c>Server_ServiceLevel</c>, <c>i=2267</c>). The DataConnectionActor polls it
|
||||
/// on the connected endpoint, and probes the other endpoint with it, to drive ServiceLevel-aware
|
||||
/// failover (ScadaBridge#138). An adapter without the capability is never switched on ServiceLevel.
|
||||
/// </summary>
|
||||
public interface IServiceLevelReadable
|
||||
{
|
||||
/// <summary>
|
||||
/// Reads the server's current ServiceLevel. Never raises the connection's
|
||||
/// <see cref="IDataConnection.Disconnected"/> event: a lost session is the reconnect machine's
|
||||
/// business, not this read's.
|
||||
/// </summary>
|
||||
/// <param name="cancellationToken">Bounds the read.</param>
|
||||
/// <returns>
|
||||
/// The ServiceLevel (0–255), or null when it is unknown: not connected, a Bad status, a value
|
||||
/// that is not a byte, or a failed read.
|
||||
/// </returns>
|
||||
Task<byte?> ReadServiceLevelAsync(CancellationToken cancellationToken = default);
|
||||
}
|
||||
@@ -83,6 +83,15 @@ public readonly record struct OpcUaConfigParseResult
|
||||
/// </summary>
|
||||
public static class OpcUaEndpointConfigSerializer
|
||||
{
|
||||
/// <summary>Flat-dict key for <see cref="OpcUaServiceLevelFailoverConfig.Enabled"/>.</summary>
|
||||
public const string ServiceLevelFailoverEnabledKey = "ServiceLevelFailover.Enabled";
|
||||
|
||||
/// <summary>Flat-dict key for <see cref="OpcUaServiceLevelFailoverConfig.DegradedWindowSeconds"/>.</summary>
|
||||
public const string ServiceLevelFailoverWindowKey = "ServiceLevelFailover.DegradedWindowSeconds";
|
||||
|
||||
/// <summary>Flat-dict key for <see cref="OpcUaServiceLevelFailoverConfig.MinDwellSeconds"/>.</summary>
|
||||
public const string ServiceLevelFailoverDwellKey = "ServiceLevelFailover.MinDwellSeconds";
|
||||
|
||||
private static readonly JsonSerializerOptions JsonOpts = new()
|
||||
{
|
||||
PropertyNamingPolicy = JsonNamingPolicy.CamelCase,
|
||||
@@ -216,6 +225,12 @@ public static class OpcUaEndpointConfigSerializer
|
||||
dict["Deadband.Type"] = db.Type.ToString();
|
||||
dict["Deadband.Value"] = db.Value.ToString(System.Globalization.CultureInfo.InvariantCulture);
|
||||
}
|
||||
if (config.ServiceLevelFailover is { } sl)
|
||||
{
|
||||
dict[ServiceLevelFailoverEnabledKey] = sl.Enabled.ToString();
|
||||
dict[ServiceLevelFailoverWindowKey] = sl.DegradedWindowSeconds.ToString(System.Globalization.CultureInfo.InvariantCulture);
|
||||
dict[ServiceLevelFailoverDwellKey] = sl.MinDwellSeconds.ToString(System.Globalization.CultureInfo.InvariantCulture);
|
||||
}
|
||||
return dict;
|
||||
}
|
||||
|
||||
@@ -291,6 +306,18 @@ public static class OpcUaEndpointConfigSerializer
|
||||
c.Deadband = db;
|
||||
}
|
||||
|
||||
if (dict.ContainsKey(ServiceLevelFailoverEnabledKey)
|
||||
|| dict.ContainsKey(ServiceLevelFailoverWindowKey)
|
||||
|| dict.ContainsKey(ServiceLevelFailoverDwellKey))
|
||||
{
|
||||
var sl = new OpcUaServiceLevelFailoverConfig();
|
||||
if (dict.TryGetValue(ServiceLevelFailoverEnabledKey, out var slEn) && bool.TryParse(slEn, out var slEnabled))
|
||||
sl.Enabled = slEnabled;
|
||||
TryAssignInt(dict, ServiceLevelFailoverWindowKey, v => sl.DegradedWindowSeconds = v);
|
||||
TryAssignInt(dict, ServiceLevelFailoverDwellKey, v => sl.MinDwellSeconds = v);
|
||||
c.ServiceLevelFailover = sl;
|
||||
}
|
||||
|
||||
return c;
|
||||
}
|
||||
|
||||
|
||||
@@ -96,4 +96,12 @@ public sealed class OpcUaEndpointConfig
|
||||
/// Heartbeat configuration for connection monitoring.
|
||||
/// </summary>
|
||||
public OpcUaHeartbeatConfig? Heartbeat { get; set; }
|
||||
|
||||
// Redundancy (optional; null = defaults, see OpcUaServiceLevelFailoverConfig)
|
||||
/// <summary>
|
||||
/// ServiceLevel-aware failover settings (ScadaBridge#138). Connection-level: only the primary
|
||||
/// endpoint's value is read, and only when the connection has a backup. Null means the
|
||||
/// defaults (enabled, 10 s window, 60 s dwell).
|
||||
/// </summary>
|
||||
public OpcUaServiceLevelFailoverConfig? ServiceLevelFailover { get; set; }
|
||||
}
|
||||
|
||||
+46
@@ -0,0 +1,46 @@
|
||||
namespace ZB.MOM.WW.ScadaBridge.Commons.Types.DataConnections;
|
||||
|
||||
/// <summary>
|
||||
/// ServiceLevel-aware failover for an OPC UA connection with a primary AND a backup endpoint
|
||||
/// (ScadaBridge#138; OtOpcUa Warm redundancy, lmxopcua#717). A connection-level setting: only the
|
||||
/// <b>primary</b> endpoint's copy is read, and it has no effect on a connection without a backup.
|
||||
///
|
||||
/// <para>
|
||||
/// The connected endpoint's <c>Server_ServiceLevel</c> (<c>i=2267</c>) is polled. When it stays in
|
||||
/// the Degraded band (below 200, OPC UA Part 4 §6.6.2.4.2) for <see cref="DegradedWindowSeconds"/>
|
||||
/// and the other endpoint is reachable and reports a Healthy-band level (200 or more) that is also
|
||||
/// higher, the connection fails over to it. A switch is not repeated within
|
||||
/// <see cref="MinDwellSeconds"/>. Both endpoints degraded, or the other one unreachable, means the
|
||||
/// connection stays where it is. On connect, a Degraded endpoint is left immediately (no window) for
|
||||
/// a Healthy, higher other endpoint, subject to the same dwell.
|
||||
/// </para>
|
||||
///
|
||||
/// <para>
|
||||
/// A stored configuration without this object behaves as the defaults: enabled, 10 s window,
|
||||
/// 60 s dwell. With today's OtOpcUa pair (250 Primary / 240 Secondary, both Healthy band) it never
|
||||
/// triggers.
|
||||
/// </para>
|
||||
/// </summary>
|
||||
public sealed class OpcUaServiceLevelFailoverConfig
|
||||
{
|
||||
/// <summary>Default for <see cref="DegradedWindowSeconds"/>.</summary>
|
||||
public const int DefaultDegradedWindowSeconds = 10;
|
||||
|
||||
/// <summary>Default for <see cref="MinDwellSeconds"/>.</summary>
|
||||
public const int DefaultMinDwellSeconds = 60;
|
||||
|
||||
/// <summary>Whether ServiceLevel can trigger a failover. Default true.</summary>
|
||||
public bool Enabled { get; set; } = true;
|
||||
|
||||
/// <summary>
|
||||
/// How long, in seconds, the connected endpoint must report a Degraded-band ServiceLevel
|
||||
/// without a break before the other endpoint is checked. Default 10.
|
||||
/// </summary>
|
||||
public int DegradedWindowSeconds { get; set; } = DefaultDegradedWindowSeconds;
|
||||
|
||||
/// <summary>
|
||||
/// Minimum time, in seconds, after a ServiceLevel-driven switch before another one may happen
|
||||
/// (anti-flap). Default 60.
|
||||
/// </summary>
|
||||
public int MinDwellSeconds { get; set; } = DefaultMinDwellSeconds;
|
||||
}
|
||||
@@ -74,6 +74,14 @@ public static class OpcUaEndpointConfigValidator
|
||||
if (config.Deadband is { } db && db.Value <= 0)
|
||||
errors.Add(Err("Deadband.Value", "Must be > 0."));
|
||||
|
||||
if (config.ServiceLevelFailover is { } sl)
|
||||
{
|
||||
if (sl.DegradedWindowSeconds < 1 || sl.DegradedWindowSeconds > 3600)
|
||||
errors.Add(Err("ServiceLevelFailover.DegradedWindowSeconds", "Must be between 1 and 3600."));
|
||||
if (sl.MinDwellSeconds < 0 || sl.MinDwellSeconds > 86400)
|
||||
errors.Add(Err("ServiceLevelFailover.MinDwellSeconds", "Must be between 0 and 86400."));
|
||||
}
|
||||
|
||||
return errors.Count == 0
|
||||
? ValidationResult.Success()
|
||||
: ValidationResult.FromErrors(errors.ToArray());
|
||||
|
||||