fix(dcl): treat OPC UA BadResourceUnavailable as transient Bad; Bad+null keeps last-known value (ScadaBridge#112)

OtOpcUa's out-of-process script runner publishes 0x80040000 with a null value.
- OpcUaDataConnection: logs entry/recovery once per tag, names the symbolic
  status in read errors; never a disconnect (not in the reconnect status set).
- InstanceActor: a Bad update with no value is a quality-only transition
  (keep value, quality Bad, stream publish, no script/alarm/waiter re-eval),
  matching the connection-drop rule. Bad with a value is unchanged.

Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
This commit is contained in:
Joseph Doherty
2026-11-10 04:38:05 -05:00
parent 533414a16d
commit 08fe5acfe4
5 changed files with 322 additions and 2 deletions
@@ -399,6 +399,7 @@ Subscription demand survives connection transitions through coalescing and owner
The DCL manages connection lifecycle automatically:
1. **Connection drop detection**: When a connection to a data source is lost, the DCL immediately pushes a value update with quality `bad` for **every tag subscribed on that connection**. Instance Actors see the staleness immediately and publish it to the site stream / debug view; **script and alarm actors are deliberately NOT re-notified on a quality-only change** (no value changed — re-evaluating triggers would cause spurious firings). Scripts observe quality on their next attribute read; a computed alarm holds its last-known state until fresh values arrive.
**Per-tag Bad with no value is handled the same way (ScadaBridge#112).** A tag update whose quality is `bad` and whose value is null — OPC UA servers commonly omit the value on a Bad status, and OtOpcUa always does — is a quality-only transition at the Instance Actor: the last-known value is kept, quality goes `Bad`, the stream/debug view is told, scripts/alarms/`WaitForAttribute` waiters are not re-evaluated, and the next Good update recovers it. A Bad update that carries a value still stores that value. This covers OtOpcUa's `BadResourceUnavailable` (`0x80040000`, its out-of-process script runner's "worker restarted / runner unavailable" on virtual and Calculation tags, lmxopcua#780): the OPC UA adapter treats it as a plain per-node Bad — never a connection fault (it is not in the DataConnectionActor's session/secure-channel reconnect set), no subscription teardown — logs one Information line per tag on entry and one on recovery, and names it in read errors (`0x80040000 BadResourceUnavailable (source node temporarily unable to compute the value)`; every other Bad read error now carries its symbolic name too).
2. **Auto-reconnect with fixed interval**: The DCL retries the connection at a configurable fixed interval (e.g., every 5 seconds). The retry interval is a **shared setting for all data connections** (`ReconnectInterval` in the Shared Settings table). This is consistent with the fixed-interval retry philosophy used throughout the system. Individual gRPC/OPC UA operations (reads, writes) fail immediately to the caller on error; there is no operation-level retry within the adapter.
3. **Connection state transitions**: The DCL tracks each connection's state as `connected`, `disconnected`, or `reconnecting`. All transitions are logged to Site Event Logging (event type `connection`): the initial connect (`Connection established on … endpoint`, Info — added by review 2026-10-21, it previously logged nothing), connection lost / reconfigured (`Warning` / `Info`), restored on reconnect (`Info`) and failover (`Warning`).
4. **Transparent re-subscribe**: On successful reconnection, the DCL automatically re-establishes all previously active subscriptions for that connection. Instance Actors require no action — they simply see quality return to `good` as fresh values arrive from restored subscriptions.
@@ -1,3 +1,4 @@
using System.Collections.Concurrent;
using Microsoft.Extensions.Logging;
using ZB.MOM.WW.ScadaBridge.Commons.Interfaces.Protocol;
using ZB.MOM.WW.ScadaBridge.Commons.Serialization;
@@ -41,6 +42,14 @@ public class OpcUaDataConnection
private StaleTagMonitor? _staleMonitor;
private string? _heartbeatSubscriptionId;
/// <summary>
/// Tags whose latest notification is <c>BadResourceUnavailable</c> (ScadaBridge#112), so the
/// distinct "source temporarily unable to compute" log line fires once per entry and once per
/// recovery rather than per notification. Written from the SDK publish threads, hence
/// concurrent (DCL-019). Bounded by the subscribed tag set; cleared on (re)connect.
/// </summary>
private readonly ConcurrentDictionary<string, byte> _resourceUnavailableTags = new();
/// <summary>
/// Initializes a new instance of <see cref="OpcUaDataConnection"/>.
/// </summary>
@@ -99,6 +108,7 @@ public class OpcUaDataConnection
MaxMonitoredItemsPerSubscription: config.MaxMonitoredItemsPerSubscription);
_status = ConnectionHealth.Connecting;
_resourceUnavailableTags.Clear();
// Reconnect reuses this adapter instance (DataConnectionActor re-calls
// ConnectAsync on auto-reconnect): detach + dispose the previous client so
@@ -191,6 +201,7 @@ public class OpcUaDataConnection
(nodeId, value, timestamp, statusCode) =>
{
var quality = MapStatusCode(statusCode);
TrackResourceUnavailable(tagPath, statusCode);
callback(tagPath, new TagValue(value, quality, new DateTimeOffset(timestamp, TimeSpan.Zero)));
},
cancellationToken);
@@ -209,6 +220,7 @@ public class OpcUaDataConnection
(nodeId, value, timestamp, statusCode) =>
{
var quality = MapStatusCode(statusCode);
TrackResourceUnavailable(nodeId, statusCode);
callback(nodeId, new TagValue(value, quality, new DateTimeOffset(timestamp, TimeSpan.Zero)));
},
cancellationToken);
@@ -267,7 +279,7 @@ public class OpcUaDataConnection
var quality = MapStatusCode(statusCode);
if (quality == QualityCode.Bad)
return new ReadResult(false, null, $"OPC UA read returned bad status: 0x{statusCode:X8}");
return new ReadResult(false, null, DescribeBadRead(statusCode));
return new ReadResult(true, new TagValue(value, quality, new DateTimeOffset(timestamp, TimeSpan.Zero)), null);
}
@@ -306,7 +318,7 @@ public class OpcUaDataConnection
var quality = MapStatusCode(outcome.StatusCode);
results[outcome.NodeId] = quality == QualityCode.Bad
? new ReadResult(false, null, $"OPC UA read returned bad status: 0x{outcome.StatusCode:X8}")
? new ReadResult(false, null, DescribeBadRead(outcome.StatusCode))
: new ReadResult(true,
new TagValue(outcome.Value, quality, new DateTimeOffset(outcome.SourceTimestamp, TimeSpan.Zero)),
null);
@@ -461,6 +473,60 @@ public class OpcUaDataConnection
Disconnected?.Invoke();
}
/// <summary>
/// OPC UA <c>BadResourceUnavailable</c> — the code part (high 16 bits) of
/// <see cref="Opc.Ua.StatusCodes.BadResourceUnavailable"/>. OtOpcUa's out-of-process script
/// runner publishes it on script-computed nodes when the script worker died under the
/// evaluation or no worker is ready (ScadaBridge#112, lmxopcua#780). It is a per-node,
/// transient "cannot compute this value right now": a plain Bad quality on the tag — never a
/// connection fault, so it must not reach <c>RaiseDisconnected</c> or the connection-level
/// status set the DataConnectionActor reconnects on.
/// </summary>
internal const uint BadResourceUnavailableCode = Opc.Ua.StatusCodes.BadResourceUnavailable;
/// <summary>True when <paramref name="statusCode"/>'s code part is BadResourceUnavailable
/// (the low 16 bits are info bits and do not change the meaning).</summary>
internal static bool IsResourceUnavailable(uint statusCode) =>
(statusCode & 0xFFFF0000u) == BadResourceUnavailableCode;
/// <summary>Read-failure text naming the symbolic status, e.g.
/// <c>0x80040000 BadResourceUnavailable</c>, so a script/diagnostic reader can tell a
/// transient source-side condition from a configuration or security error.</summary>
internal static string DescribeBadRead(uint statusCode)
{
var name = Opc.Ua.StatusCodes.LookupSymbolicId(statusCode & 0xFFFF0000u);
var text = string.IsNullOrEmpty(name)
? $"OPC UA read returned bad status: 0x{statusCode:X8}"
: $"OPC UA read returned bad status: 0x{statusCode:X8} {name}";
return IsResourceUnavailable(statusCode)
? text + " (source node temporarily unable to compute the value)"
: text;
}
/// <summary>
/// Logs the entry into / recovery from <c>BadResourceUnavailable</c> once per transition per
/// tag. Hot path: a tag that is not and was not unavailable costs one status compare and an
/// empty-dictionary check.
/// </summary>
private void TrackResourceUnavailable(string tagPath, uint statusCode)
{
if (IsResourceUnavailable(statusCode))
{
if (_resourceUnavailableTags.TryAdd(tagPath, 0))
_logger.LogInformation(
"OPC UA source {Endpoint} reports BadResourceUnavailable (0x{Status:X8}) for {TagPath} — "
+ "the source node is temporarily unable to compute this value; tag quality is Bad, "
+ "last-known value kept, connection unaffected",
_endpointUrl, statusCode, tagPath);
}
else if (!_resourceUnavailableTags.IsEmpty && _resourceUnavailableTags.TryRemove(tagPath, out _))
{
_logger.LogInformation(
"OPC UA source {Endpoint} recovered {TagPath} from BadResourceUnavailable (now 0x{Status:X8})",
_endpointUrl, tagPath, statusCode);
}
}
/// <summary>
/// Maps OPC UA StatusCode to QualityCode.
/// StatusCode 0 = Good, high bit set = Bad, otherwise Uncertain.
@@ -1223,6 +1223,23 @@ public class InstanceActor : ReceiveActor
traced = true;
}
// Bad quality WITHOUT a value (ScadaBridge#112) is a quality-only transition: the
// source is saying "I cannot give you a value right now", not "the value is now
// null". OPC UA servers commonly omit the value on a Bad status — OtOpcUa always
// does, e.g. BadResourceUnavailable (0x80040000) from its out-of-process script
// runner — and the DCL's own tag-resolution failure pushes Bad+null too. Treat it
// exactly like a connection drop (HandleConnectionQualityChanged, DCL design
// "Connection drop detection"): keep the last-known value, flip quality to Bad,
// publish to the stream, and do NOT re-notify scripts/alarms or evaluate waiters —
// nulling the stored value would fire value-change scripts with a null and make a
// computed alarm re-evaluate on a value that never existed. A Bad update that DOES
// carry a value still takes the normal path below.
if (update.Quality == QualityCode.Bad && update.Value is null)
{
ApplyQualityOnlyBad(attrName, update.TagPath, update.Timestamp, traceSource, traced);
continue;
}
// A List-typed attribute coerces the incoming OPC UA array
// (a CLR array/IEnumerable from the SDK) into a typed List<T>. On an
// element-type mismatch we set the attribute's quality to Bad, log a
@@ -1271,6 +1288,22 @@ public class InstanceActor : ReceiveActor
}
}
/// <summary>
/// Marks a data-sourced attribute Bad while keeping its last-known value (ScadaBridge#112):
/// quality + timestamp move, the stored value does not, and only the site stream / debug
/// view is told — mirroring <see cref="HandleConnectionQualityChanged"/>.
/// </summary>
private void ApplyQualityOnlyBad(
string attrName, string tagPath, DateTimeOffset timestamp, Guid? traceSource, bool traced)
{
_attributeQualities[attrName] = "Bad";
_attributeTimestamps[attrName] = timestamp;
_attributes.TryGetValue(attrName, out var currentValue);
_streamManager?.PublishAttributeValueChanged(new AttributeValueChanged(
_instanceUniqueName, tagPath, attrName, currentValue, "Bad", timestamp,
SourceExecutionId: traceSource, Trace: traced, SourceExecutionInferred: traced));
}
/// <summary>Parses a <see cref="ResolvedAttribute.DataType"/> string, defaulting to
/// <see cref="DataType.String"/> on an unrecognized value (never throws).</summary>
private static DataType ParseDataType(string dataType) =>
@@ -0,0 +1,134 @@
using System.Collections.Concurrent;
using System.Reflection;
using Microsoft.Extensions.Logging;
using NSubstitute;
using ZB.MOM.WW.ScadaBridge.Commons.Interfaces.Protocol;
using ZB.MOM.WW.ScadaBridge.Commons.Types.Enums;
using ZB.MOM.WW.ScadaBridge.DataConnectionLayer.Actors;
using ZB.MOM.WW.ScadaBridge.DataConnectionLayer.Adapters;
namespace ZB.MOM.WW.ScadaBridge.DataConnectionLayer.Tests.Adapters;
/// <summary>
/// ScadaBridge#112: OtOpcUa's out-of-process script runner publishes
/// <c>BadResourceUnavailable</c> (0x80040000) — with a null value — on script-computed nodes
/// when its worker died or is not ready. The OPC UA adapter must treat it as a plain, transient
/// Bad quality on the tag: no disconnect, no subscription teardown, distinct log lines on entry
/// and recovery, and a read error that names the status.
/// </summary>
public class OpcUaResourceUnavailableTests
{
private const uint BadResourceUnavailable = 0x80040000u;
private const string Tag = "nsu=https://zb.com/otopcua/uns;s=Line1.Pump.Calc";
private sealed class CapturingLogger : ILogger<OpcUaDataConnection>
{
public ConcurrentQueue<(LogLevel Level, string Message)> Entries { get; } = new();
public IDisposable? BeginScope<TState>(TState state) where TState : notnull => null;
public bool IsEnabled(LogLevel logLevel) => true;
public void Log<TState>(LogLevel logLevel, EventId eventId, TState state, Exception? exception,
Func<TState, Exception?, string> formatter) => Entries.Enqueue((logLevel, formatter(state, exception)));
}
/// <summary>
/// Good / BadResourceUnavailable(null) / Good on a monitored item maps to Good / Bad / Good
/// tag quality, never raises Disconnected, never removes the subscription, and logs the
/// unavailable entry once (not per notification) plus one recovery line.
/// </summary>
[Fact]
public async Task Subscription_GoodResourceUnavailableGood_IsTransientBadQuality_NotAConnectionFault()
{
var client = Substitute.For<IOpcUaClient>();
var factory = Substitute.For<IOpcUaClientFactory>();
factory.Create().Returns(client);
client.IsConnected.Returns(true);
Action<string, object?, DateTime, uint>? publish = null;
client.CreateSubscriptionAsync(Tag, Arg.Do<Action<string, object?, DateTime, uint>>(cb => publish = cb),
Arg.Any<CancellationToken>())
.Returns("sub-1");
var logger = new CapturingLogger();
var adapter = new OpcUaDataConnection(factory, logger);
var disconnected = 0;
adapter.Disconnected += () => Interlocked.Increment(ref disconnected);
await adapter.ConnectAsync(new Dictionary<string, string>());
var received = new List<TagValue>();
await adapter.SubscribeAsync(Tag, (_, v) => received.Add(v));
Assert.NotNull(publish);
publish!(Tag, 42.0, DateTime.UtcNow, 0u);
publish(Tag, null, DateTime.UtcNow, BadResourceUnavailable);
publish(Tag, null, DateTime.UtcNow, BadResourceUnavailable); // repeated: no second log line
publish(Tag, 43.0, DateTime.UtcNow, 0u);
Assert.Equal(
new[] { QualityCode.Good, QualityCode.Bad, QualityCode.Bad, QualityCode.Good },
received.Select(v => v.Quality).ToArray());
Assert.Null(received[1].Value);
Assert.Equal(43.0, received[3].Value);
Assert.Equal(0, disconnected);
Assert.Equal(ConnectionHealth.Connected, adapter.Status);
await client.DidNotReceiveWithAnyArgs().RemoveSubscriptionAsync(default!, default);
await client.DidNotReceiveWithAnyArgs().DisconnectAsync(default);
var unavailable = logger.Entries.Where(e => e.Message.Contains("reports BadResourceUnavailable")).ToList();
var recovered = logger.Entries.Where(e => e.Message.Contains("recovered") && e.Message.Contains(Tag)).ToList();
Assert.Single(unavailable);
Assert.Contains(Tag, unavailable[0].Message);
Assert.Single(recovered);
}
/// <summary>A read that returns BadResourceUnavailable fails the read without a disconnect and
/// names the symbolic status so it reads as a transient source-side condition.</summary>
[Fact]
public async Task Read_ResourceUnavailable_FailsReadWithNamedStatus_NoDisconnect()
{
var client = Substitute.For<IOpcUaClient>();
var factory = Substitute.For<IOpcUaClientFactory>();
factory.Create().Returns(client);
client.IsConnected.Returns(true);
client.ReadValueAsync(Tag, Arg.Any<CancellationToken>())
.Returns(((object?)null, DateTime.UtcNow, BadResourceUnavailable));
var adapter = new OpcUaDataConnection(factory, new CapturingLogger());
var disconnected = 0;
adapter.Disconnected += () => disconnected++;
await adapter.ConnectAsync(new Dictionary<string, string>());
var result = await adapter.ReadAsync(Tag);
Assert.False(result.Success);
Assert.Contains("0x80040000", result.ErrorMessage);
Assert.Contains("BadResourceUnavailable", result.ErrorMessage);
Assert.Contains("temporarily unable", result.ErrorMessage);
Assert.Equal(0, disconnected);
Assert.Equal(ConnectionHealth.Connected, adapter.Status);
}
/// <summary>Other Bad reads still get the symbolic name but not the transient wording.</summary>
[Fact]
public void DescribeBadRead_OtherCodes_NamedWithoutTransientWording()
{
var text = OpcUaDataConnection.DescribeBadRead(0x80340000u);
Assert.Contains("BadNodeIdUnknown", text);
Assert.DoesNotContain("temporarily", text);
}
/// <summary>
/// BadResourceUnavailable is a per-node status: the DataConnectionActor must never classify it
/// as a session/secure-channel failure, which would drive a reconnect and a subscription rebuild.
/// </summary>
[Fact]
public void ResourceUnavailable_IsNotConnectionLevelStatus()
{
var method = typeof(DataConnectionActor).GetMethod("IsConnectionLevelStatus",
BindingFlags.NonPublic | BindingFlags.Static);
Assert.NotNull(method);
Assert.False((bool)method!.Invoke(null, new object[] { BadResourceUnavailable })!);
// Positive control: a genuine session code IS connection-level.
Assert.True((bool)method.Invoke(null, new object[] { 0x80250000u /* BadSessionIdInvalid */ })!);
}
}
@@ -768,6 +768,92 @@ public class InstanceActorTests : TestKit, IDisposable
Assert.Equal(1450, response.Value);
}
/// <summary>
/// ScadaBridge#112: a Bad-quality update that carries NO value (OtOpcUa sends a null Value
/// with every Bad status, e.g. BadResourceUnavailable from its out-of-process script runner)
/// is a quality-only transition — the last-known value survives, quality goes Bad, waiters
/// and children are not re-evaluated against a null that never existed, and the next Good
/// update recovers the attribute. Pins the Good / Bad(null) / Good sequence.
/// </summary>
[Fact]
public void InstanceActor_BadQualityWithNullValue_KeepsLastKnownValue_AndRecoversOnGood()
{
const string tag = "nsu=https://zb.com/otopcua/uns;s=Line1.Pump.Calc";
var config = new FlattenedConfiguration
{
InstanceUniqueName = "Pump-BadNull",
Attributes =
[
new ResolvedAttribute
{
CanonicalName = "Calc", Value = "0", DataType = "Int32",
DataSourceReference = tag, BoundDataConnectionName = "OtOpcUa"
}
]
};
var dcl = CreateTestProbe();
var actor = CreateInstanceActorWithDcl("Pump-BadNull", config, dcl);
actor.Tell(new TagValueUpdate("OtOpcUa", tag, 1450, QualityCode.Good, DateTimeOffset.UtcNow));
// A waiter that would fire if the stored value were ever nulled.
actor.Tell(new WaitForAttributeRequest(
"wfa-null", "Pump-BadNull", "Calc",
null, v => v is null, TimeSpan.FromSeconds(30), DateTimeOffset.UtcNow));
ExpectNoMsg(TimeSpan.FromMilliseconds(200));
// Source goes BadResourceUnavailable: Bad quality, null value.
actor.Tell(new TagValueUpdate("OtOpcUa", tag, null, QualityCode.Bad, DateTimeOffset.UtcNow));
ExpectNoMsg(TimeSpan.FromMilliseconds(300));
actor.Tell(new GetAttributeRequest("corr-bad", "Pump-BadNull", "Calc", DateTimeOffset.UtcNow));
var bad = ExpectMsg<GetAttributeResponse>(TimeSpan.FromSeconds(5));
Assert.True(bad.Found);
Assert.Equal("Bad", bad.Quality);
Assert.Equal(1450, bad.Value);
// Next good evaluation recovers.
actor.Tell(new TagValueUpdate("OtOpcUa", tag, 1500, QualityCode.Good, DateTimeOffset.UtcNow));
actor.Tell(new GetAttributeRequest("corr-good", "Pump-BadNull", "Calc", DateTimeOffset.UtcNow));
var good = ExpectMsg<GetAttributeResponse>(TimeSpan.FromSeconds(5));
Assert.Equal("Good", good.Quality);
Assert.Equal(1500, good.Value);
}
/// <summary>
/// Guard for ScadaBridge#112: a Bad update that DOES carry a value keeps the historical
/// behaviour — the carried value is stored with Bad quality.
/// </summary>
[Fact]
public void InstanceActor_BadQualityWithValue_StoresCarriedValue()
{
const string tag = "ns=3;s=Pump.BadWithValue";
var config = new FlattenedConfiguration
{
InstanceUniqueName = "Pump-BadValue",
Attributes =
[
new ResolvedAttribute
{
CanonicalName = "Speed", Value = "0", DataType = "Int32",
DataSourceReference = tag, BoundDataConnectionName = "PLC"
}
]
};
var dcl = CreateTestProbe();
var actor = CreateInstanceActorWithDcl("Pump-BadValue", config, dcl);
actor.Tell(new TagValueUpdate("PLC", tag, 1450, QualityCode.Good, DateTimeOffset.UtcNow));
actor.Tell(new TagValueUpdate("PLC", tag, 1300, QualityCode.Bad, DateTimeOffset.UtcNow));
actor.Tell(new GetAttributeRequest("corr-bv", "Pump-BadValue", "Speed", DateTimeOffset.UtcNow));
var response = ExpectMsg<GetAttributeResponse>(TimeSpan.FromSeconds(5));
Assert.Equal("Bad", response.Quality);
Assert.Equal(1300, response.Value);
}
/// <summary>